62-0125—3
7
T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL
OR HEAT PUMP THERMOSTAT
M4954A
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Auto
System
Fan
Mon
Room
AM
Occupied 1
Heat
Run
Program
4. Press Run Program.
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
Table 3. Installer System Tests.
Test
Number
System Test Description
10 to 19
Heating equipment can be turned on and
off.
20 to 29
Emergency heat (Q7300C,D,H [heat
pump models only]) equipment can be
turned on and off.
30 to 39
Cooling equipment can be turned on and
off.
40 to 49
Fan equipment can be turned on and off.
60 0 to
60 19
Keyboard keys test.
70 to 79
Thermostat information including date
code, software versions and subbase
identification are displayed.
Press and hold the increase
▲
▲
and
▼
▼
decrease keys, at
the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Fig. 5 and 6.
M10257A
TEST NUMBER
Heat
Auto
System
Fan
Off
Auto
Un
Mon
Wait
Lo
In
Room
Remote
%Humid
Auto
Sav
AM
PM
Comm
Cool
Duct
Only
On
Recovery
Hi
Med
Cool
TueWedThuFriSatSun
Occupied 12 Override
M4916
Aux Ht
Aux Ht
Em Ht
Em Ht
Set Program
Set Day/Time
Set Day/Time
Start Time
Temporary Setting Enrg
Em Heat
To start the system test:
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor is
cycled too quickly.
The minimum off time for compressors is
bypassed during the Installer System Test.
Fig. 5. LCD Display of all segments.
Fig. 6. Test number display.
NOTE:
If a duct temperature sensor is installed, the duct
temperature is also displayed.
Refer to Table 4 and Thermostat Information section for
directions and results of the specific system tests.
NOTE:
Press Run Program to exit the system test. The
system test times out after four minutes without
any key presses.
Table 4. Installer System Test Options.
Key to
Press
Test
Number
Description
Heating Equipment System Test
Heat/Cool Settings
10
Enter heating equipment system test.
∆
11
Stage-one heat turns on. The system fan is also energized.
∆
12
Stage-two heat turns on. Stage-one heat and system fan remain on.
∆
13
Stage-three heat turns on. Stage-one and stage-two heat with the system fan
are on.
∇
12
Stage-three heat turns off.
∇
11
Stage-two heat turns off.
∇
10
Stage-one heat and system fan turn off.