62-0125—3
4
T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL
OR HEAT PUMP THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
(Continued)
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.
Installer Setup
Number
(Press
Unoccupied
Temp key
Factory Setting
Other Choices
(Press
∆
or
∇
key to change)
Actual
Setting
Select
to change)
Display
Description
Display
Description
Not used.
13
—
—
—
—
—
Degree
temperature
display.
14
0
Temperature is
displayed in °F.
1
Temperature is displayed
in °C.
Displaying
temperature.
15
0
Temperature is
displayed.
1
Temperature is not
displayed.
Clock format. 16
0
12-hour clock format. 1
24-hour clock format.
Intelligent
Fan™
operation.
17
2
Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.
0 or 1
0—Fan only operates with
calls for heating or
cooling in Occupied
and Unoccupied
modes.
1—Fan operates
continuously in
Occupied mode. Fan
operates with calls for
heating or cooling in
Unoccupied mode.
Auxiliary
Contact
Operation.
18
0
0
Time-of-day
contacts.
1
1—Economizer contacts.
Extended fan
operation in
heating
a
.
19
0
No extended fan
operation after the
call for heat ends.
1
Fan operation is extended
90 seconds after the call
for heat ends.
Extended fan
operation in
cooling.
20
0
No extended fan
operation after the
call for cool ends.
1
Fan operation is extended
90 seconds after the call
for cool ends.
Fan key adjust-
ment (models
with Fan key).
21
0
Fan setting key is
operational.
1
Fan setting key is Auto
only.
Remote
sensing.
22
0
Remote sensing not
activated.
1
Remote sensing
activated.
Temperature
averaging
network
b
.
23
0
Temperature
averaging disabled.
1
Temperature averaging
between local sensor and
remote sensor(s)
activated.
Not used.
24
—
—
—
—
—
Keypad lockout
level (keypad
lockout is
enabled and
disabled by dip
switch 1 on
back of
thermostat).
25
0
No lockout.
1 or 2
1—Lockout all keys on
thermostat except
system and fan
settings, temporary
setpoint, clock and day
adjustments.
2—Lockout all keys except
set Current Day/Time,
increase
∆
and
decrease
∇
keys.
3
Lockout all keys except
temporary occupied,
Set Current Day/Time
(for clock, day
adjustments).