62-0125—3
5
T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL
OR HEAT PUMP THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
(Continued)
Installer Setup
Number
(Press
Unoccupied
Temp Key
to
Factory Setting
Other Choices
(Press
∆
or
∇
key to change)
Actual
Setting
Select
change)
Display
Description
Display
Description
Duration of
temporary
override.
26
3
3—Three hour
override.
1, 8 or
12
1—One hour override.
8—Eight hour override.
12—Twelve hour override.
Not used.
27 thru 29
—
—
—
—
—
Deadband.
30
2
Heating and cooling
setpoints can be set
no closer than 2°F
(1.1°C).
3 thru
10
Heating and cooling
setpoints can be set no
closer than the chosen
value:
3—3°F (1.7°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Interstage
control point
(Q7300C,D
only).
31
0
Disabled.
1 thru
12
Temperature has to
change more than the
chosen value before the
system calls for the next
stage. (Example: 68°F
(20°C) is the heat
setpoint, 2°F (1.1°C) is
the interstage setting,
temperature is 65.5°F
(18.5°C), the second
stage turns on, brings the
temperature to 66°F
(19°C) and turns off. The
heat pump continues to
run until the setpoint is
met.)
Minimum on-
time.
32
2
2-minute minimum
on- time for heating
and cooling.
0 or 1
No minimum on-time or
1-minute minimum on -
time for heating and
cooling.
Minimum off-
time for the
compressor.
33
4
4-minute minimum
off- time for the
compressor.
0, 1, 2,
3 or 5
Minimum number of
minutes (0 thru 5) the
compressor will be off
between calls for the
compressor.
Temperature
range stops in
heating.
34
90
Highest setpoint for
heating.
40 to
89
Temperature range (1°F
[0.6°C] increments) for
heating setpoint.
Temperature
range stops in
cooling.
35
45
Lowest setpoint for
cooling.
46 to
99
Temperature range (1°F
[0.6°C] increments) for
cooling setpoint.
Not used.
36
—
—
—
—
—