62-0128—2
7
T7200D,E SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTATS
Heat
Auto
System
Fan
Off
Auto
Un
Mon
Wait
Lo
In
Room
Remote
%Humid
Auto
Sav
AM
PM
Comm
Cool
Duct
Only
On
Recovery
Hi
Med
Cool
TueWedThuFriSatSun
Occupied 12 Override
M4916
Aux Ht
Em Ht
Em Ht
Set Program
Set Day/Time
Set Day/Time
Start Time
Temporary Setting Enrg
Em Heat
M10257A
TEST NUMBER
NOTE:
If a duct temperature sensor is installed, the duct
temperature is also displayed.
Refer to Table 4 and Thermostat Information section for
directions and results of the specific system tests.
NOTE:
Press Run Program to exit the system test. The
system test times out after four minutes if there
are no additional key presses.
Fig. 10. LCD display of all segments.
Fig. 11. Test number display.
Table 4. Installer System Test Options.
Key to Press
Test
Number
Description
Heating Equipment Test
Heat/Cool Settings
10
Enter heating equipment test.
▲
11
Heat turns on. The system fan is also energized.
▼
10
Heat and system fan turn off.
Cooling Equipment Test
Heat/Cool Settings
30
Change from heating to cooling equipment test.
▲
31
Cool and system fan turn on.
▼
30
Cool and system fan turn off.
Fan Equipment Test
Heat/Cool Settings
40
Change from cooling to fan equipment test.
▲
41
Fan turns on.
▼
40
Fan turns off.
Key Operation Test
Heat/Cool Settings
60 2
Change from fan to key operation test.
Unoccupied Temp
60 0
Unoccupied Temp test number is displayed.
Occupied Temp
60 1
Occupied Temp test number is displayed.
▲
60 3
Increase test number is displayed.
▼
60 5
Decrease test number is displayed.
Clear Start Time
60 7
Clear Start Time test number is displayed.
Day
60 8
Day test number is displayed.
Copy
60 9
Copy test number is displayed.
Unoccupied Start
TIme
60 10
Unoccupied Start Time test number is displayed.
System
(select models)
60 11
System test number is displayed.
Fan (select models)
60 12
Fan test number is displayed.
Set Current Day/Time
60 14
Set Current Day/Time test number is displayed.
Run Program
60 15
Run Program test number is displayed.
Temporary Occupied
60 16
Temporary Occupied test number is displayed.
Occupied Start Time
60 17
Occupied Start Time test number is displayed.
Continuous
Unoccupied
60 19
Continuous Unoccupied test number is displayed.