62-0128—2
6
T7200D,E SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTATS
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
M4954A
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Auto
System
Fan
Mon
Room
AM
Occupied 1
Heat
Run
Program
Test
Number
System Test Description
10 to 19
Heating equipment can be turned on and
off
30 to 39
Cooling equipment can be turned on and
off
40 to 49
Fan equipment can be turned on and off
60 0 to
60 19
Keyboard keys test
70 to 79
Thermostat information including date
code, software versions and subbase
identification are displayed
Table 3. Tests Available in Installer System Test.
IMPORTANT
Review the settings to confirm that they match
the system. Press Run Program to exit the
Installer Setup. Set the current day and time
immediately.
Setting Current Day and Time
1. Press Set Current Day/Time.
NOTE:
On initial power up or after an extended
power loss, 1:00 pm flashes on the LCD
until a key is pressed.
M4951B
Set Current
Day/Time
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Mon
PM
Set Day/Time
2. Press Day until the current day is displayed.
NOTE:
Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday,
Thu=Thursday, Fri=Friday, Sat=Saturday.
3. Press increase
▲
or decrease
▼
until the current
time is displayed.
NOTE:
Tapping the Set Current Day/Time changes
the time in one hour increments.
M4952B
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Day
PM
Tue
Set Day/Time
M4953B
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
PM
Tue
Set Day/Time
4. Press Run Program.
To start the system test:
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor is
cycled too quickly.
The minimum off-time for compressors is bypassed
during the Installer System Test.
Press and hold the increase
▲
and
decrease
▼
keys, at
the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Fig. 10 and 11.
Table 2. Thermostat Installer Setup Options (Continued).
Installer Setup
Number
(Press
Unoccupied
Temp key
Factory Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Select
to change)
Display
Description
Display
Description
Setting
Minimum off-
times in heating.
38
4
4—4-minute
minimum off-time.
0, 1, 2, 3,
or 5
Minimum number of minutes
(0 thru 5) the heating
equipment will be off
between calls for heat.
Installer Setup
lockout (keypad
lockout is
enabled and
disabled by dip
switch 1 on back
of thermostat).
40
0
0—No Installer Setup
lockout.
1
1—Installer Setup lockout
activated.