T7200D,E SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTATS

Table 2. Thermostat Installer Setup Options.

(continued)

a

Number 2 must be set to 1 to extend fan operation.

b

Some models may not have this feature.Table 2.

Installer Setup

Number

(Press

Unoccupied

Temp key

Factory Setting

Other Choices  

(Press 

 or 

 

 key to change)

Actual

Select

to change)

Display

Description

Display

Description

Setting

Not used.

1

Fan operation

a

(T7200D only).

2

0

Conventional applica-
tions where
equipment controls
fan operation in heat
mode.

1

Electric heat applications
where thermostat controls
fan operation in heat mode.

Degree
temperature
display.

14

0

Temperature is
displayed in °F.

1

Temperature is displayed  
in °C.

Intelligent Fan™
operation.  

17

2

Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.

0 or 1

0—Fan only operates with

calls for heating or cooling
in Occupied and
Unoccupied modes.

1—Fan operates

continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.

Keypad lockout
level (keypad
lockout is
enabled and
disabled by dip
switch 1 on
thermostat
back).

25

0

No lockout.

1 or 2

1—Lockout all keys on

thermostat except system
and fan settings, temporary
setpoint; clock and day
adjustments.

2—Lockout all keys except

set Current Day/Time,
increase 

 and decrease

 keys.

3—Lockout all keys except

Temporary Occupied, Set
Current Day/Time (for
clock, day adjustments).

O/B Operation

b

(T7200E only).

29

0

0—Energize in Cool

mode.

1

1—Energize in Heat Mode.

Minimum off-
time for the
compressor.

33

4

4-minute minimum
off-time for the
compressor.

0, 1, 2, 3
or 5

Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor.

Temperature
display
adjustment.

37

0

No difference in
displayed
temperature and
actual room
temperature.

1 thru 6

1—Display adjusts to 1°F

(0.6°C) higher than actual
room temperature.

2—Display adjusts to 2°F

(1.1°C) higher than actual
room temperature.

3—Display adjusts to 3°F

(1.7°C) higher than actual
room temperature.

4—Display adjusts to 1°F

(0.6°C) lower than actual
room temperature.

5—Display adjusts to 2°F

(1.1°C) lower than actual
room temperature.

6—Display adjusts to 3°F

(1.7°C) lower than actual
room temperature.

Содержание T7200D

Страница 1: ...stat X XX UL INSTALLATION INSTRUCTIONS U S Registered Trademark Copyright 1998 Honeywell Inc All Rights Reserved T7200D ESeries2000Commercial MicroelectronicThermostats INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product...

Страница 2: ...cause electrical shock Disconnect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the wallplate and connect the system wires See Fig 3 IMPORTANT Use 18 gauge solid conductor color coded thermostat cable for proper wiring If using 18 gauge stranded wire do not use more than ten wires Do not use larger than 18 gauge wire 2 Securely tighten each ter...

Страница 3: ...emp Unoccupied Start Time Day System Fan Copy Occupied Start Time Run Program Temporary Occupied Continuous Unoccupied Set Current Day Time Clear Start Time Unoccupied Temp Heat Cool Settings Auto System Fan Mon Room AM Occupied Heat M10233A SET OVERRIDE TEMPERATURE OFFSET AND ACTIVATE TEMPORARY OVERRIDE ENTER HOLD MODE SET CURRENT DAY AND TIME CLEAR PROGRAM PERIOD COPY ONE PROGRAMMED DAY TO ANOTH...

Страница 4: ...ode The Intelligent Fan operation Installer Setup number 17 offers three choices for the fan operation in Occupied mode fan turns on only when there is a call for heating or cooling fan operates continuously in Occupied mode fan is on continuously in Occupied and recovery modes Setting Temperature Refer to Table 1 for the default temperature setpoints See Owners Guide form number 63 4356 for compl...

Страница 5: ...heating or cooling in Unoccupied mode Keypad lockout level keypad lockout is enabled and disabled by dip switch 1 on thermostat back 25 0 No lockout 1 or 2 1 Lockout all keys on thermostat except system and fan settings temporary setpoint clock and day adjustments 2 Lockout all keys except set Current Day Time increase and decrease keys 3 Lockout all keys except Temporary Occupied Set Current Day ...

Страница 6: ...ent day is displayed NOTE Sun Sunday Mon Monday Tue Tuesday Wed Wednesday Thu Thursday Fri Friday Sat Saturday 3 Press increase or decrease until the current time is displayed NOTE Tapping the Set Current Day Time changes the time in one hour increments M4952B Set Program Set Temperature Change Time Temp Occupied Temp Unoccupied Start Time Day System Fan Copy Occupied Start Time Run Program Tempor...

Страница 7: ...est Heat Cool Settings 30 Change from heating to cooling equipment test 31 Cool and system fan turn on 30 Cool and system fan turn off Fan Equipment Test Heat Cool Settings 40 Change from cooling to fan equipment test 41 Fan turns on 40 Fan turns off Key Operation Test Heat Cool Settings 60 2 Change from fan to key operation test Unoccupied Temp 60 0 Unoccupied Temp test number is displayed Occupi...

Страница 8: ...er Example 001 revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the increase key again to display the wallplate identification code Example HP heat pump wallplate 7 Press Run Program to exit the system test The system test times out after four minutes without any key presses Setting Keypad Lockout Switch The dip switch 1 o...

Страница 9: ...onfigure Installer Setup Installer Setup is locked out Reset the dip switch 1 on the back of the thermostat to enable keypad Temperature settings change from original setting Heating and cooling setpoints are set too close together There is a deadband in automatic changeover thermostat models Example cool setpoint 72 deadband 3 heat setpoint 68 changing heat setpoint to 70 automatically changes th...

Страница 10: ...nd HVAC equipment and replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated and wait indicator is displayed Wait up to five minutes for the system to respond Enter Installer Setup number 33 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool System o...

Страница 11: ...62 0128 2 11 T7200D E SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTATS ...

Страница 12: ...IC THERMOSTATS Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 62 0128 2 J S Rev 12 98 Home and Building Control Honeywell 1985 Douglas Drive North Minneapolis MN 55422 4386 www honeywell com yourhome ...

Отзывы: