T7147 REMOTE SENSOR AND OVERRIDE MODULE

63-4065—1

6

OPERATION

Sensor

The remote sensor control element is a negative temperature 
coefficient (NTC) thermistor. As room temperature increases, 
the resistance of the thermistor decreases. As room 
temperature decreases, the resistance of the thermistor 
increases. The T7300 detects the thermistor resistance 
change and controls the space temperature by sequentially 
staging the heating/cooling equipment on and off.

NOTE:

The T7047C1025 uses the same sensor element.

3 Hour Occupied

When correctly wired, pressing the 3 Hour Occupied key 
sends a signal from the T7147 to the T7300/Q7300. Upon 
receipt of this signal, the T7300/Q7300 proceeds into the 
3 Hour Occupied override. In response, the T7300/Q7300 
sends a signal back to the T7147 to turn on the 3 Hour 
Occupied LED. The 3 Hour Occupied LED remains on for 
the duration of the 3 hour override.

NOTE:

For additional details, consult the T7300/Q7300 
Specification sheet, form 63-4038.

3 Hour Setpoint Adjust

When wired correctly, pressing the 3 Hour Occupied key, 
followed by the Warmer or Cooler key sends a signal from the 
T7147 to the T7300/Q7300. The T7300/Q7300, upon receipt 
of this signal, proceeds into the 3 Hour Setpoint Adjust 
override. In response, the T7300/Q7300 sends a signal back 
to the T7147 that turns on the 3 Hour Occupied LED and the 
appropriate Warmer or Cooler LED. The 3 Hour Occupied 
LED and Warmer or Cooler LED remains on for the duration 
of the 3 hour override.

This override may be performed at any time, regardless of 
whether the thermostat system is operating in the occupied 
or unoccupied mode.

NOTES:

For additional details, consult the T7300/Q7300 
Specification sheet, form 63-4038.

Premature exit from either override can be 
achieved by pressing the 3 Hour Occupied key 
again. The T7300 then returns to normal operation.

CHECKOUT

1.

Allow the sensor to stabilize to ambient conditions 
before taking a resistance measurement. The sensor 
resistance measurement should be in accordance with 
the device temperature curve (see Fig. 2).

2.

Check operation of the 3 Hour Occupied key:
a. Press the 3 Hour Occupied key once.
b. The LED above the key turns on.

3.

Go to the T7300 thermostat and check it to see that the 
display arrow indicator points to 3 Hr Occupied.

4.

On models with Warmer and Cooler keys:
a. Press the Warmer key once.
b. The LED above the Warmer key comes on.
c. Press the Cooler key.
d. The LED above the Warmer key turns off and the 

LED above the Cooler key turns on.

e. Press the 3 Hour Occupied key once.
f.

The LED above this key turns off, as well as those 
above either the Warmer or Cooler keys.

5.

Go to the T7300 thermostat and check to see that the 
arrow indicator on the display no longer points to 3 Hr 
Occupied
 and has returned to its currently programmed 
occupied or unoccupied period.

NOTE:

If the T7147 does not check out, review the 
wiring and connections between the Q7300 
and the T7147. Replace the T7147 if wiring 
continuity checks out. If the new T7147 does 
not check out, replace the Q7300.

6.

Check operation of the complete control system as 
directed in the T7300/Q7300 Specification sheet, form 
63-4038.

Содержание T7147

Страница 1: ...ith the T7300 Q7300 Programmable Commercial Thermostat system The T7147 provides space temperature sensing switch initiation and indication of overrides from a remote location FEATURES Locking cover Override key Warmer Cooler keys on some models Key lock override security available Contents Application 1 Features 1 Specifications 2 Ordering Information 2 Installation 3 Wiring 4 Operation 6 Checkou...

Страница 2: ...tches to invoke 3 Hour Occupied and Warmer Cooler setpoint adjustments from remote location T7147A1028 Remote Temperature Sensor Override Module Connects to Q7300 Same as T7147A1010 except includes key lock switch to enable disable remote override operation Mounting Mounts on wall or 2 x 4 inch vertical outlet box with screws provided Dimensions See Fig 1 Wiring Maximum cable length between T7300 ...

Страница 3: ... unheated areas behind the thermostat wall Locate the T7147 about 5 ft 1 5 m above the floor in an area with good air circulation within easy reach of users Mounting 1 Loosen the cover locking screw with the Allen wrench provided and remove the T7147 cover 2 Run wire to the selected location 3 Thread wire through T7147 base semicircular hole 4 Make connections to T7147 see Wiring section 5 If air ...

Страница 4: ... subbase switch 5 local remote sensor select switch is in the OFF position Refer to the T7300 Q7300 Specification sheet form 63 4038 for details IMPORTANT The ground GND connection at the T7147 is required Use the junction box or conduit for a convenient grounding location 3 Ensure all connections are tight and secure Loose or intermittent wire connections cause inconsistent system operation 4 Whe...

Страница 5: ...LOCATION M10193 T7300 Q7300 T7147 C1 C2 C3 C4 C5 T T CA1 CA2 CA3 CA4 CA5 GND T T T T7300 Q7300 T T T T T T T T T T7047C2007 T7047C2007 T7047C2007 T7147A ONLY ONE T7417 ALLOWED PER SYSTEM SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS THE GROUND GND CONNECTION TO THE T7417 IS REQUIRED USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT GROUNDING LOCATION 1 1 2 2 3 3 M10194 C1 C2 C3 C4 C5 T T CA1...

Страница 6: ...ur override This override may be performed at any time regardless of whether the thermostat system is operating in the occupied or unoccupied mode NOTES For additional details consult the T7300 Q7300 Specification sheet form 63 4038 Premature exit from either override can be achieved by pressing the 3 Hour Occupied key again The T7300 then returns to normal operation CHECKOUT 1 Allow the sensor to...

Страница 7: ...7 63 4065 1 ...

Страница 8: ...well Asia Pacific Inc Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Room 3213 3225 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario No 30 Harbour Road Belgium Suite 200 M1V 4Z9 Wanchai Sunrise FL 33325 Hong Kong ...

Отзывы: