T7147 REMOTE SENSOR AND OVERRIDE MODULE

63-4065—1

4

WIRING

CAUTION

Erratic System Operation Hazard.
Failure to follow proper wiring practices can 
introduce disruptive electrical interference (noise).

Keep wiring at least one foot away from large inductive 

loads such as motors line starters, lighting ballasts, 
and large power distribution panels.

Shielded cable is required in installations where these 

guidelines cannot be met.

Ground shield only to grounded controller case.

IMPORTANT

All wiring must comply with local codes and 
ordinances.

NOTES:

Terminal screws are provided on the device for 
wiring connections.

Wiring to device is low voltage and need not be 
in conduit unless required by code.

1.

Connect correct control wires from the Q7300 subbase 
to the T7147 (see Fig. 4 and 5).

2.

Ensure that Q7300 subbase switch 5 (local/remote 
sensor select switch) is in the OFF position. (Refer to 
the T7300/Q7300 Specification sheet, form 63-4038, 
for details).

IMPORTANT

The ground (GND) connection at the T7147 is 
required. Use the junction box or conduit for a 
convenient grounding location.

3.

Ensure all connections are tight and secure. Loose or 
intermittent wire connections cause inconsistent system 
operation.

4.

When installation is complete, perform the checkout 
procedure (see the Checkout section).

Averaging Sensors

When the controlled zone is a large area, it can be 
advantageous to use a T7147 and several remote 
temperature sensors dispersed throughout the area to obtain 
an average zone temperature signal. (See Fig. 6 and 7.)

NOTE:

Only one T7147 can be used in any one 
T7300/Q7300 system.

Fig. 4. Connecting wires to T7147.

T

T

CA5

CA4

CA3

CA2

CA1

GND

CONNECTIONS TO CA3 AND CA4 NOT REQUIRED 
ON T7147A2000.

ROUTE EXCESS WIRING AWAY FROM SENSOR 
ELEMENT FOR OPTIMUM PERFORMANCE.

M17880

1

1

2

2

CA5

CA4

CA3

CA2

CA1

GND

Содержание T7147

Страница 1: ...ith the T7300 Q7300 Programmable Commercial Thermostat system The T7147 provides space temperature sensing switch initiation and indication of overrides from a remote location FEATURES Locking cover Override key Warmer Cooler keys on some models Key lock override security available Contents Application 1 Features 1 Specifications 2 Ordering Information 2 Installation 3 Wiring 4 Operation 6 Checkou...

Страница 2: ...tches to invoke 3 Hour Occupied and Warmer Cooler setpoint adjustments from remote location T7147A1028 Remote Temperature Sensor Override Module Connects to Q7300 Same as T7147A1010 except includes key lock switch to enable disable remote override operation Mounting Mounts on wall or 2 x 4 inch vertical outlet box with screws provided Dimensions See Fig 1 Wiring Maximum cable length between T7300 ...

Страница 3: ... unheated areas behind the thermostat wall Locate the T7147 about 5 ft 1 5 m above the floor in an area with good air circulation within easy reach of users Mounting 1 Loosen the cover locking screw with the Allen wrench provided and remove the T7147 cover 2 Run wire to the selected location 3 Thread wire through T7147 base semicircular hole 4 Make connections to T7147 see Wiring section 5 If air ...

Страница 4: ... subbase switch 5 local remote sensor select switch is in the OFF position Refer to the T7300 Q7300 Specification sheet form 63 4038 for details IMPORTANT The ground GND connection at the T7147 is required Use the junction box or conduit for a convenient grounding location 3 Ensure all connections are tight and secure Loose or intermittent wire connections cause inconsistent system operation 4 Whe...

Страница 5: ...LOCATION M10193 T7300 Q7300 T7147 C1 C2 C3 C4 C5 T T CA1 CA2 CA3 CA4 CA5 GND T T T T7300 Q7300 T T T T T T T T T T7047C2007 T7047C2007 T7047C2007 T7147A ONLY ONE T7417 ALLOWED PER SYSTEM SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS THE GROUND GND CONNECTION TO THE T7417 IS REQUIRED USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT GROUNDING LOCATION 1 1 2 2 3 3 M10194 C1 C2 C3 C4 C5 T T CA1...

Страница 6: ...ur override This override may be performed at any time regardless of whether the thermostat system is operating in the occupied or unoccupied mode NOTES For additional details consult the T7300 Q7300 Specification sheet form 63 4038 Premature exit from either override can be achieved by pressing the 3 Hour Occupied key again The T7300 then returns to normal operation CHECKOUT 1 Allow the sensor to...

Страница 7: ...7 63 4065 1 ...

Страница 8: ...well Asia Pacific Inc Honeywell Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Room 3213 3225 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario No 30 Harbour Road Belgium Suite 200 M1V 4Z9 Wanchai Sunrise FL 33325 Hong Kong ...

Отзывы: