T7022A 

Remote Temperature Sensor 

INSTALLATION INSTRUCTIONS 

APPLICATION 

The T7022 Remote Temperature Sensor is a non-

adjustable thermistor sensor. Its primary use is with the 
T7300 Programmable Commercial Thermostat (

only

 in 

return air) to control heating or cooling equipment. 

NOTE:

  

The T7022 can also be used with a T7100F, 
provided the proper Q7100 subbase√one 

capable of handling more than one stage of 
heat√is used. 

INSTALLATION 

When Installing this Product... 

1.

  

Read these instructions carefully. Failure to follow 

them could damage the product or cause a 
hazardous condition. 

2.

  

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 

your application. 

3.

  

Installer must be a trained, experienced service 

technician. 

4.

  

After installation is complete, check out product 

operation as provided in these instructions. 

CAUTION 

Erratic System Operation Hazard.

 

Failure to follow proper wiring practices can 

introduce disruptive electrical interference

 

(noise).

 

Keep wiring at least one foot away from large 

inductive loads such as motors line starters, 
lighting ballasts, and large power distribution 

panels. 

Shielded cable is required in installations where 

these guidelines cannot be met. 

Ground shield only to grounded controller case. 

CAUTION 

Electrical Shock or Equipment Damage 

Hazard.

 

Can shock individuals or short equipment

 

circuitry.

 

Disconnect power supply before installation. 

IMPORTANT

 

All wiring must agree with applicable codes, 
ordinances and regulations. 

Wiring (Fig. 1) 

Wiring for the T7022 Remote Temperature Sensor can 

be run with class 2 wire in accordance with the National 
Electrical Codes. Conduit and/or shielding are not 

necessary for satisfactory operation, but conduit may be 
required by local codes or practices. 

Q7300

 

T7022

 

M17843 

Fig. 1. Typical wiring diagram. 

Location 

The T7022 Thermostat must be mounted in the return-air 

flow in ducts (see Fig. 2 and 3) or light troffers (see Fig. 4 
and 5). All mounting locations must be where the sensor 

is not affected by heat from the lights or other sources. 

Mounting 

The T7022 can be mounted in a duct with the furnished 
bracket, or in a light troffer as shown in Fig. 4 and 5 with 

two rubber grommets (not supplied) if proper spacing 
is available. Mounting can be directly in the return-air 

passage or in an air-sampling box. The rubber grommets 
can be used to wedge the sensor in slot openings of 

approximately 3/8 in. to 1/2 in. wide. 

When using the mounting bracket, the maximum duct 
insertion length for the T7022 is approximately 2-3/4 in. 

NOTE:

  

A piece of 3/8 in. diameter conduit can be 

used to extend the sensor further inside a duct 
(see Fig. 3). The use of such an extension can 

increase the maximum insertion length to 
approximately 9-1/2 in. 

® U.S. Registered Trademark 
Copyright © 2001 Honeywell • All Rights Reserved 