T410A,B ELECTRIC HEAT THERMOSTATS

3

68-0145EF

Location

Install a vertical outlet box, which is used to mount the 

thermostat, about 5 ft (1.5 m) above the floor in an area with 

good air circulation at room temperature.

Do not install the thermostat where it may be affected by:

— drafts or dead spots behind doors, in corners or under 

cabinets.

— hot air from convectors.

— radiant heat from sun or appliances.

— concealed pipes and chimneys.

— unheated (uncooled) areas such as an outside wall behind 

the thermostat.

Wiring and Mounting

CAUTION

1. To avoid damaging the sensing element, handle the 

thermostat with care. 

2. Use a separate limit control in the heating 

appliance.

3. To prevent damage to dial stop when mounting the 

thermostat, turn the temperature setting dial until 

the setpoint indicator is at the 12 o’clock position.

Replacement Applications

1.

Disconnect power to the thermostat to prevent electrical 

shock or equipment damage. All wiring must comply 

with local electrical codes and ordinances.

2.

Remove the old thermostat from the wall, taking care 

not to damage the wiring insulation.

3.

Check the old wire insulation for cracks, nicks or fraying. 

If necessary, apply approved electrical tape to insulate 

old wires or replace with new wires.

4.

Do not remove the T410 Thermostat Cover. Using wire 

connectors approved for No. 12 wires, make line volt-

age connections directly to the leadwires on the thermo-

stat. See Figs. 2 and 3 for typical wiring connections.

5.

Prebend and push solid wires into the outlet box.

6.

Remove thermostat cover by grasping the top and bot-

tom cover edge and pulling it outward away from the 

thermostat base. 

7.

Turn the temperature setting dial so the setpoint indica-

tor is at the 12 o’clock position to prevent damaging the 

dial stop.

8.

Mount the thermostat on the outlet box. Tighten the two 

mounting screws (included) to secure the thermostat, 

taking care to avoid excessive pressure on the setting 

dial. See Fig. 4.

Fig. 2.  Typical wiring connections for T410A.

Fig. 3. Typical wiring connections for T410B.

M5811B

L1 

(HOT)
L2

1

2

3

SOLDERLESS

CONNECTORS

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 

OVERLOAD PROTECTION AS REQUIRED.

USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS 

WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE

HAZARD MAY RESULT.

USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE.

BREAKS AND REMAKES BELOW -31 F (-35 C); NORMALLY

THERMAL ACTIVATED. BREAKS ON TEMPERATURE RISE; 

MAKES ON TEMPERATURE FALL. 

1

2

3

4

T410A

ELECTRIC 

HEATER

L1

T1

4

M5812B

L1 

(HOT)

L2

1

2

4

SOLDERLESS

CONNECTORS

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 

OVERLOAD PROTECTION AS REQUIRED.

USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS 

WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE

HAZARD MAY RESULT.

BREAKS AT POSITIVE OFF AND REMAKES UNDER –31 F (–35 C);

NORMALLY THERMALLY ACTIVATED.  BREAKS ON TEMPERATURE

RISE;   MAKES ON TEMPERATURE FALL.

USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE.

BREAKS AT POSITIVE OFF ONLY; NOT THERMALLY ACTIVATED.

DO NOT CONNECT GROUNDED CONDUCTOR (NEUTRAL) ON

120 OR 227V CIRCUITS. INSULATE AND TAPE OR CUT OFF

RED WIRES IF UNUSED.

1

2

3

4

5

6

ELECTRIC

HEATER

RED 

WIRE

6

T410B

L1

T1

5

L2

T2

3

Содержание T410A

Страница 1: ...ell sales representa tive FEATURES Energy efficient and economical UL listed up to 5 kW at 277 Vac ncludes long lasting Micro Switch mechanism Rugged plastic mounting base one piece cover Contemporary white finish complements any decor Replaces virtually any wall mounted electric heating thermostat Models T410A Electric Heating Thermostat Spst switching heating circuit makes on temperature fall T4...

Страница 2: ...Cover Assembly Includes locking cover screws Tinnerman clips wrench and range stops two plastic pins to insert inside cover for field selec tion of minimum and maximum temperature settings Fig 1 T410 approximate dimensions in in mm MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube do not place your old control in the trash Dispose of properly Contact your...

Страница 3: ...end and push solid wires into the outlet box 6 Remove thermostat cover by grasping the top and bot tom cover edge and pulling it outward away from the thermostat base 7 Turn the temperature setting dial so the setpoint indica tor is at the 12 o clock position to prevent damaging the dial stop 8 Mount the thermostat on the outlet box Tighten the two mounting screws included to secure the thermostat...

Страница 4: ...ase 6 Turn the temperature setting dial so the setpoint indica tor is at the 12 o clock position to prevent damaging the dial stop 7 Mount the thermostat on the outlet box Tighten the two mounting screws included to secure the thermostat taking care to avoid excessive pressure on the setting dial See Fig 4 SETTINGS AND CHECKOUT Setting The thermostat temperature setting can be adjusted by turning ...

Страница 5: ...présentant de Honeywell CARACTÉRISTIQUES Éconergétique et économique Répertorié UL jusqu à 5 kW sous 277 V c a Comporte un mécanisme Micro SwitchMC de longue durée Plaque de montage en plastique robuste couvercle monopièce Fini blanc contemporain s harmonisant à tous les décors Remplace presque tout thermostat mural pour chauffage électrique Modèles T410A Thermostat pour chauffage électrique commu...

Страница 6: ...no E47434 guide no XAPX Certifié par l Association canadienne de normalisation CSA dossier no LR1322 Accessoire 272804A Jeu de butées d arrêt et de vis de verrouillage com prend des vis pour couvercle verrouillable des pinces Tin nerman une clé et des butées deux butées de plastique à insérer sous le couvercle pour sélectionner sur place les réglages minimal et maximal de la température Fig 1 Enco...

Страница 7: ...fils et les insérer dans la boîte de sortie 6 Retirer le couvercle du thermostat en le tenant par les rebords supérieur et inférieur et en tirant vers soi en l éloignant de la base 7 Faire tourner le cadran de réglage du point de consigne jusqu à ce que l indicateur soit à la position midi 12 heures pour éviter d endommager les butées d arrêt du cadran 8 Installer le thermostat dans la boîte de so...

Страница 8: ...ntihoraire le circuit de chauffage s ouvre et l appareil de chauffage cesse de fonctionner et com mence à refroidir Fig 5 Réglage du point de consigne MF5812B L1 SOUS TENSION L2 1 2 4 CONNECTEURS SANS SOUDURE ALIMENTATION FOURNIR AU BESOIN UN DISPOSITIF DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES UTILISER DES CONNECTEURS SANS SOUDURE CO ALR POUR SERVICE SPÉCIAL LORSQUE LES CONDUCTEURS SONT ...

Отзывы: