7.2 Analog Output Signal Calibration
With a Transmitter in its constant current source mode, its analog output circuit can be calibrated at
0 (zero) % and 100% levels. It is not necessary to remove the Transmitter from service.
The following procedure is used for analog output signal calibration. You can calculate milliamperes
of current from a voltage measurement as follows: Dc milliamps = 1000 X voltage/resistance
IMPORTANT: Be sure that the accuracy of the resistor is 0.01% or better for current
measurements made by voltage drop
.
1.
Check that the Write Protect Jumper is in the “OFF” position.
2.
Connect the MC Toolkit across loop wiring, and turn it on. See
equipment hookup.
3.
Launch the FDC application.
4.
On the Home page, select Online and establish a connection with the device as follows
5.
Check that the device is not in the Write Protect mode.
6.
Select the My Device menu, and choose from the following menus:
a.
Device setup \ Calibration \ Calibration Methods \ D/A trim
7.
You will be prompted to remove the loop from automatic control; after removing the loop
from automatic control, press OK.
8.
When a prompt appears, connect a precision milliammeter or voltmeter (0.03% accuracy or
better) in the loop to check readings, and press OK. The following prompts will be displayed:
Setting field device to output to 4mA. Press OK
Enter meter value. Key in the meter value, and press ENTER.
Field device output 4.000 mA equal to reference meter?
1 Yes, 2 No
-
If the reference meter is not equal to the field device output then select No and
press Enter
-
Key in the new meter value
-
Return back to the “Enter Meter Value” prompt until the field device output
equals the reference meter
-
Select Yes and press Enter
9.
The following display prompts will appear:
Setting field device output to 20mA. Press OK
Enter meter value. Key in the meter value, and press ENTER.
Field device output 20.000 mA equal to reference meter?
1 Yes, 2 No
-
If the reference meter is not equal to the field device output then select No and
press Enter
-
Key in the new meter value
-
Return back to the ”Enter Meter Value” prompt until the field device output
equals the reference meter
-
Select Yes and press Enter
10.
The prompt notifies you that the field device will be returned to its original output
Содержание STT850 Series
Страница 8: ...Page viii STT850 Series HART DE Option User s Manual Revision 4 0 ...
Страница 16: ...Page 6 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 22: ...Page 12 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 36: ...Page 26 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 73: ...Revision 4 0 STT850 Series HART DE Option User s Manual Page 63 This page is left blank intentionally ...
Страница 115: ...Revision 4 0 STT850 Series HART DE Option User s Manual Page 105 ...