![Honeywell STT850 Series Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/honeywell/stt850-series/stt850-series_user-manual_155005020.webp)
Page 10
STT
850 Series HART/DE Option User’s Manual
Revision 4.0
3.4 MC Toolkit Participation
Before using the MC Toolkit, be sure that you are aware of the potential consequences of
each procedure, and that you use appropriate safeguards to avoid possible problems. For
example, if the Transmitter is an element in a control loop, the loop needs to be put in manual
mode, and alarms and interlocks (i.e., trips) need to be disabled, as appropriate, before
starting a procedure.
3.4.1 MC Toolkit Software Applications
The MC Toolkit has two software applications to work with STT850 SmartLine Temperature
Transmitters:
Field Device Configurator (FDC)
. This application is used for configuring, calibrating,
monitoring, and diagnosing HART devices. FDC conforms to the IEC 61804-3 EDDL
(Electronic Data Description Language) standard specification. The FDC application is an
open solution that supports devices with a registered device description (DD) file compatible
with HART Communication Foundation (HCF) requirements.
MC Toolkit
. This application is used for configuring, calibrating, monitoring, and diagnosing
Honeywell Digitally Enhanced (DE) devices.
Details for working with the MC Toolkit are provided in the
MC Toolkit User Manual,
document #
34-ST-25-20. In subsequent sections of this manual, explicit operating instructions are provided only
in so far as necessary to complete required tasks and procedures.
3.4.2 Configuration Databases
The MC Toolkit is used to establish and/or change selected operating parameters in a Transmitter
database.
3.4.3 Configuration
Configuration can be accomplished both online and offline with the Transmitter powered up and
connected to the MC Toolkit. Online configuration immediately changes the Transmitter operating
parameters. For offline configuration, Transmitter operating characteristics are entered into Toolkit
memory for subsequent downloading to a Transmitter.
When you set up or configure a Transmitter, it can take up to 30 seconds for the value
to be stored in it. If you change a value and Transmitter power is interrupted before the
change is copied to nonvolatile memory, the changed value will not be moved to nonvolatile
memory.
Содержание STT850 Series
Страница 8: ...Page viii STT850 Series HART DE Option User s Manual Revision 4 0 ...
Страница 16: ...Page 6 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 22: ...Page 12 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 36: ...Page 26 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 73: ...Revision 4 0 STT850 Series HART DE Option User s Manual Page 63 This page is left blank intentionally ...
Страница 115: ...Revision 4 0 STT850 Series HART DE Option User s Manual Page 105 ...