Page 46
STT
850 Series HART/DE Option User’s Manual
Revision 4.0
Online/Device
Setup/Detailed Setup
Output Condition
PV AO: displays the current value of AO (analog
output) in milliamps
PV AO Alm Type: displays the current position of the
failsafe jumper on the electronics board (upscale/
lowscale burnout)
Loop mA: Select the Loop Current Mode
configuration:
“Enable”: enables loop current mode (analog output
will operate as a 4 to 20 mA signal consistent with the
transmitter output)
“Disable”: disables loop current mode (analog output
will be fixed at 4 mA)
Loop test: This function enables the user to test the
Analog Output measurement at any value over the
full operational range. Select a current value to apply
and verify the current output on the loop with a
calibrated meter.
Note that this function is only available when “Loop
mA” (Loop Current mode) is Enabled.
D/A trim: perform an analog output calibration at 4.00
and 20.00 mA (0% and 100% output).
Online/Device
Setup/Sensors
Sensors
Sensor1 Config
Parameters
Sensor2 Config
Parameters
Change Sensor Type: select the specific type of
thermocouple, RTD, ohms or millivolt sensor for both
Sensor 1 and Sensor 2 inputs.
Sensor 1: Sensor 1 Config Parameters: Displays the
basic configuration parameters and allows
configuration of parameters relevant to Sensor 1,
including:
-
Sensor type: TC, RTD, ohms or mv as
configured above
-
Sensor ID: Specific sensor type as configured
above
-
LRL, URL: Lower and Upper Range Limits
-
LTL, UTL: Lower and Upper Transducer Limits
-
Sensor 1 Install Date: A one-time writable date
used for Advanced Diagnostics on the Sensor
health.
-
Lower and Upper Calibration Points: Enter the
Calibration values to be used during the LRV
Correct and URV Correct procedures
-
Sensor 1 Bias: Enter any desired bias value to
be used for Sensor 1 measurement. Bias is
generally applied to compensate for input drift
due to sensor deterioration. Final Sensor 1
value = Sensor 1 input + Sensor 1 Bias.
Sensor 2: Sensor 2 Config Parameters: Displays the
basic configuration parameters and allows
configuration of parameters relevant to Sensor 2,
Содержание STT850 Series
Страница 8: ...Page viii STT850 Series HART DE Option User s Manual Revision 4 0 ...
Страница 16: ...Page 6 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 22: ...Page 12 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 36: ...Page 26 STT850 Series HART DE Option User s Manual Revision 4 0 This page is left blank intentionally ...
Страница 73: ...Revision 4 0 STT850 Series HART DE Option User s Manual Page 63 This page is left blank intentionally ...
Страница 115: ...Revision 4 0 STT850 Series HART DE Option User s Manual Page 105 ...