Honeywell
Control Panel 33
7
7.4.5 Fault history menu
Figure 7.6: Fault history menu
In Fault history menu you can browse through 9 latest faults (see Figure 7.6). If a fault
is active, the relevant fault number (e.g. F1 02) alternates in the display with main
menu. When you browse between the faults, the fault codes of active faults are blink-
ing. The active faults can be reset by pressing the STOP button for 1 second. If the
fault cannot be reset, the blinking continues. It is possible to navigate in the menu
structure also when there are active faults present, but the display returns automati-
cally to the fault menu if buttons or navigation wheel are not pressed or navigation is
not rotated. The operating hour, minute and second values at the fault instant are
shown in the value menu (operating hours = displayed reading x 1000 h).
Note! The whole fault history can be cleared by pressing STOP
button for 5 sec time when the drive is stopped and Fault history
menu is selected in the diisplay. When you are in main
menu pressing STOP button will start the Start Up
Wizard and return all parameter settings to
factory defaults.
See Chapter 5 in for fault descriptions.
FAULT
ALARM
STOP
READY RUN
REF
MON
PAR
FLT
FWD
REV
I/O KEYPAD
BUS
FAULT
ALARM
STOP
READY RUN
REF
MON
PAR
FLT
FWD
REV
I/O KEYPAD BUS
FAULT
ALARM
STOP
READY RUN
REF
MON
PAR
FLT
FWD
REV
I/O KEYPAD
BUS
FAULT
ALARM
STOP
READY RUN
REF
MON
PAR
FLT
FWD
REV
I/O KEYPAD BUS
Browse
faults 1-9
Push
Push
Browse
for hours (H),
minutes (M)
and seconds (S)