14
32-00009—01
Configuration
Min
Optimum Range for Performance Max
Thermocouple J -50°C
1025°C ± 4 °C
K -50°C
1000°C ± 4 °C
RTD
-135°C
250°C
± 2 °C
NTC
25°C
125°C
± 1°C
Current Out
4 mA
20 mA
± .05 mA
Voltage: In / Out
2 V
10 V
0.3 %,
typical
Table 7. Suggested Sensor Selection Based on Application.
Application
Recommended Wire
Size
Recommended
Part Numbers
Analog Cell
terminals
18 AWG wire insulat-
ed for voltages and
temperatures for given
application.
TTW60C,
THW75C,
THHN90C
Table 8. Recommended Wire Sizes and Part Numbers.
Recommended Grounding Practices
Use an Earth ground or a signal ground as described below.
Earth ground (Base, Rectification Flame Amp
Module, other modules optional)
1.
Use to provide a connection between the base and the
control panel of the equipment. Earth ground must be capable
of conducting enough current to blow the breaker in the event
of an internal short circuit.
2.
Use wide straps or brackets to provide minimum length,
maximum surface area ground conductors. If a leadwire is
required, use 14 AWG copper wire.
3.
Make sure that mechanically tightened joints along the ground
path are free of nonconductive coatings and protected against
corrosion on mating surfaces.