SLATE
™
ANALOG I/O MODULE
13
R8001U3001
Frequency / PWM
Functions
Min
Typical Max
Units
PWM Out
T1
Amplitude
5.0
-
10.0
VDC
Low output
state = 0V
Frequency
100.0 -
1000.0 Hz
Duty Cycle
2.0
-
98.0
%DC
Allowable
output %DC
Resolution
-
1.0
-
%
Accuracy
-0.5
-
0.5
%DC
10V amplitude
Frequency In
T2
Amplitude
5.0
10.0
15.0
VDC
Range
2
-
1000
Hz
Min. “on” pulse width
(low %DC)
-
50.0
-
usec
10V amplitude
Min. “off” pulse width
(high %DC)
-
130.0
-
usec
10V amplitude
Duty Cycle 2 – 100
Hz
2.0
-
98.0
%DC
10V amplitude
1000 Hz
5.0
-
85.0
%DC
10V amplitude
Resolution
-
1
-
Hz
Accuracy
-5.0
-
0
%
Whichever is
greater
-1
-
0
Hz
PWM In
T2
Amplitude
5.0
10.0
15.0
VDC
Frequency
125
-
500
Hz
Min. “on” pulse width
(low %DC)
-
50.0
-
usec
10V amplitude
Min. “off” pulse width
(high %DC)
-
130.0
-
usec
10V amplitude
Duty Cycle 125 –
500 Hz
5.0
-
90.0
%DC
10V amplitude
Resolution
-
1.0
-
%DC
Accuracy
125 Hz
-1.5
-
1.5
%DC
10V amplitude
500 Hz
-7.5
-
7.5
%DC
10V amplitude
Table 6. Specifications for Cell Frequency Functions.