Model SK-FFT Manual — P/N 54711:B2 12/18/2020
SLC Device Installation
Addressing SK-MINIMON SLC Devices
NOTE 1:
Class A does not require the use of isolator modules.
.
4.4 Addressing SK-MINIMON SLC Devices
All SK-MINIMON devices are addressed using the two rotary dials that appear on the device board. Use the
ONES
rotary dial to set the ones
place in a one or two digit number, and use the
TENS
rotary dial to set the tens place in a two digit number.
SK-MINIMON modules can be assigned any unique address from 1 to 48.
Example 1:
To select device address 10, turn the
ONES
rotary dial to
0
and the
TENS
rotary dial to
1
Example 2:
To select device address 42, turn the ONES rotary dial to
2
and the TENS rotary dial to
4
Figure 4.4 SK-MINIMON SLC Device Addressing using the Rotary Dials
NOTE 2:
There are no T-taps allowed on Class A SLC loops.
!
CAUTION:
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors. Break wire runs to
provide supervision of connections.
Example 1: Device set to 10
Example 2: Device Set to 42