The steps in Figures 4a and 4b describe and illustrate mod-
ule installation when the rear chassis position and the posi-
tion in front of it will be filled.  Front position installation 
is possible only if the rear position is filled with a module.

1

Figure 4a: Installation of IDP-Zone-6 module in a rear  

chassis position, method two

Step 1:  Insert the bottom edge of the IDP-Zone-6    

 

module down into a rear slot of the chassis.

Step 2:  Carefully swing the upper edge of the board  

 

towards the back of the chassis until it touches  

 

the short standoff attached to the chassis.

Step 3:  Align the long standoff with the short standoff  

 

and tighten.

2

3

1

Figure 4b: Installation of IDP-Zone-6 module in    

front chassis position

Step 1:  Insert the bottom edge of the IDP-Zone-6    

 

module down into a front slot of the chassis.

Step 2:  Carefully  swing  the  upper  edge  of  the  board  

 

towards the back of the chassis until it touches  

 

the 1

1

/

4

˝ (31.75mm) standoffs installed on the  

 

rear module.

Step 3:  Align two 4-40 screws with the two standoffs  

 

and tighten.

Step 4:  Address and wire the modules according    

 

to the instructions in this manual.

WIRING

NOTE: 

All wiring must conform to applicable local 

codes, ordinances, and regulations.
1.  Install module wiring in accordance with the job draw-

ings and appropriate wiring diagrams.

K200-16-00 

I56-2733-003

C0225-00

2.  All  wiring  to  the  IDP-Zone-6  is  done  via  terminal 

blocks.  In  order  to  properly  make  electrical  connec-
tions  strip  approximately 

1

/

4

˝  of  insulation  from  the 

end of wire, sliding the bare end of the wire under the 
clamping plate screw.  

3. Set the address on the modules per the job drawing. Use 

the rotary code switches to set the address of the first 
module (between 01 and 94).

In Class B operation, the remaining modules are automati-
cally assigned to the next five higher addresses. For ex-
ample, if the base address switch is set to 28, the next five 
modules will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position, remove 
shunts for Class A. When operating in Class A, alternate 
modules are paired together (+0/+1, +2/+3, +4/+5), re-
sulting in a total of three modules. For example, if the 
base address switch is set to 28, then 30 and 32 will be 
automatically assigned to the modules while 29, 31 and 
33 are available to be used for other modules on the SLC. 
For Class A and B operation, DO NOT set the lowest ad-
dress above 94, as the other modules will be assigned to 
nonexistent addresses.

NOTE: 

The IDP-Zone-6 must have power cycled for  

shunt changes to take effect.
4.  A  shunt  is  provided  to  disable  a  maximum  of  two 

unused modules in Class B operation and Class A op-
eration. Modules are disabled from the highest address 
and work downward. If two modules are disabled, the 
lowest  four  addresses  will  be  functional,  while  the 
highest two will be disabled. For example, in Class B 
operation,  if  the  shunt  for Address  Disable  is  placed 
on “two” and the base switch is set to 28, the modules 
will be assigned to 28, 29, 30 and 31 while disabling 
the highest two positions.

NOTE:

  Place unused shunts on single pin to store on 

board for future use.

WIRING NOTES

•  Power-limited circuits must employ type FPL, FPLR,  
  or FPLP cable as required by Article 760 of the NEC.
•  All wiring must be in accordance with the NEC,    
  NFPA 72 and all other applicable codes and standards.  
  All external power supplies must be power limited  
  with battery back-up. All external power supplies and  
  detectors must be UL listed for fire protection 
  signaling applications.

PROGRAMMING

The modules are programmed as devices in each system 
according to the programming instructions in the appro-
priate FACP manual.  

C0226-00

Содержание SILEN KNIGHT IDP-Zone-6

Страница 1: ...0 2W B A SYSTEM SENSOR N A 20 2W TB A SYSTEM SENSOR N A 20 DH100LP A SYSTEM SENSOR N A 20 Class B Style B only No Accessory will be supported by 2100AT BEFORE INSTALLING If the modules will be installed in an existing operational system inform the operator and local authority that the system will be temporarily out of service Disconnect the power to the control panel before installing the modules ...

Страница 2: ...and wire the modules according to the instructions in this manual Included 5 1 x 4 Terminal Blocks 2 11 4 Stand offs 3 Shunts 4 Machine Screws 1 Long Power Supply Jumper 2 Nuts 6 3 9k Ohm End of Line Resistors Shipped on Board 2 Shunts in Class A B position Shipped in Class B position remove shunts for Class A COMPATIBILITY REQUIREMENTS To ensure proper operation this module shall be con nected to...

Страница 3: ...n Class B operation the remaining modules are automati cally assigned to the next five higher addresses For ex ample if the base address switch is set to 28 the next five modules will be addressed to 29 30 31 32 and 33 The module is shipped in Class B position remove shunts for Class A When operating in Class A alternate modules are paired together 0 1 2 3 4 5 re sulting in a total of three module...

Страница 4: ...long power supply jumper from T5 or T6 to T5 or T6 on the adjacent IDP Zone 6 module 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS CLASS A ID...

Страница 5: ... 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC A B SELECT A B SELECT DISABLE 1 DISABLE 2 T6 T5 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC A B SELECT A B SELECT DISABLE 1 DISABLE 2 T6 T5 IN OUT EXTERNAL SUPPLY IN OUT EXTERNAL SUPPLY EXTERNAL POWER SUPPLY PCB 1 PCB 2 VIEW A A 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 Figu...

Страница 6: ...tructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures R...

Отзывы: