INSTALLATION STEPS

1.  Cabinet Mounting

 

 

In  a  clean,  dry  area,  mount  the  backbox  using  the 
four holes provided in the back surface of the cabinet 
(Figure 2).

Backbox
Mounting
Holes

Figure 2: Typical mounting hole locations

2.  Module Installation

 

There are two methods for installing a module in the 
rear position of a chassis. Method one is for installa-
tion of a rear module only, when no module will be in-
stalled in front of it. Refer to Figure 3 for instructions. 
Method two is for installation of a rear module when 
another module will be installed in the chassis position 
in front of it.  Refer to Figures 4a and 4b for method 
two. All  necessary  screws  and  standoffs  are  supplied 
with the modules.

2

3

1

Figure 3: Installation of rear module only, method one

Step 1:  Insert the bottom of the IDP-Zone-6 module  

 

down into a rear slot on the chassis. 

Step 2:  Carefully swing the upper edge of the board  

 

back towards the back of the chassis until it   

 

touches the two standoffs.

Step 3:  Align two 4-40 screws with the two standoffs  

 

and tighten.

Step 4:  Address and wire the modules according to the  

 

instructions in this manual.

Included:

(5) 1 x 4 Terminal Blocks (2) 1

1

/

4

˝ Stand offs  (3) Shunts

(4) Machine Screws         (1) Long Power Supply Jumper

 

 

(2) Nuts

(6) 3.9k Ohm 
End of Line Resistors

Shipped on Board:

(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control panel 
(list available from Silent Knight).

COMPONENTS

The following is a description of the IDP-Zone-6 mount-
ing framework:
•  One or two IDP-Zone-6 modules can be installed in a  
  IDP-ACB cabinet

Figure 1: IDP-ACB Cabinet

The IDP-ACB cabinet has a built-in chassis that will ac-
commodate one or two IDP-Zone-6 modules. For cabinet 
dimensions refer to the IDP-ACB instruction manual.
The front IDP-Zone-6 module positions of each chassis 
are offset below the rear IDP-Zone-6 module positions so 
that all of the status indicators are visible.

K200-16-00 

I56-2733-003

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

101

1

12

13

14

15

BASE 

ADDRESS

ADDRESS

DISABL

E

N

O

N

E

O

N

E

TW

O

TH

R

EE

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

BASE 

ADDRESS

ADDRESS

DISABLE

NONE

ONE

TW
O

THREE

C0234-04

C0235-00

C0237-00

Содержание SILEN KNIGHT IDP-Zone-6

Страница 1: ...0 2W B A SYSTEM SENSOR N A 20 2W TB A SYSTEM SENSOR N A 20 DH100LP A SYSTEM SENSOR N A 20 Class B Style B only No Accessory will be supported by 2100AT BEFORE INSTALLING If the modules will be installed in an existing operational system inform the operator and local authority that the system will be temporarily out of service Disconnect the power to the control panel before installing the modules ...

Страница 2: ...and wire the modules according to the instructions in this manual Included 5 1 x 4 Terminal Blocks 2 11 4 Stand offs 3 Shunts 4 Machine Screws 1 Long Power Supply Jumper 2 Nuts 6 3 9k Ohm End of Line Resistors Shipped on Board 2 Shunts in Class A B position Shipped in Class B position remove shunts for Class A COMPATIBILITY REQUIREMENTS To ensure proper operation this module shall be con nected to...

Страница 3: ...n Class B operation the remaining modules are automati cally assigned to the next five higher addresses For ex ample if the base address switch is set to 28 the next five modules will be addressed to 29 30 31 32 and 33 The module is shipped in Class B position remove shunts for Class A When operating in Class A alternate modules are paired together 0 1 2 3 4 5 re sulting in a total of three module...

Страница 4: ...long power supply jumper from T5 or T6 to T5 or T6 on the adjacent IDP Zone 6 module 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS CLASS A ID...

Страница 5: ... 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC A B SELECT A B SELECT DISABLE 1 DISABLE 2 T6 T5 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC A B SELECT A B SELECT DISABLE 1 DISABLE 2 T6 T5 IN OUT EXTERNAL SUPPLY IN OUT EXTERNAL SUPPLY EXTERNAL POWER SUPPLY PCB 1 PCB 2 VIEW A A 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 Figu...

Страница 6: ...tructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures R...

Отзывы: