GB
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
http://www.hls-nordic.com
MODULE FOR SINGLE LAMP SELECTION AND MONITORING
Switching of one selected light in the electric circuit
SET010 select
DIP-switch 1
ON for non-maintained mode (Default)
DIP-switch 2
OFF for lighting address 1-16 (Default)
ON for lighting address 17-32
Indicator LED
Rotary coding switch
for setting the exact lamp adress
DIP-switch 3 (OFF)
Attention!
Connect L and N correctly!
Exchanging L and N causes malfunction.
Setting the lighting address is carried out by a rotary coding switch that is easily accessible from the
outside.
The module is already prepared for administering a total of 32 lighting addresses.
Function
By means of a suitable control, it is possible with the aid of the SET010 select to determine whether the
lamp connected to it is ready for use or faulty.
Lighting addresses 1 to 16 can be slected when DIP switch 2 is set at OFF.
The address range 17 to 32 can be selected by setting DIP switch 2 to ON.
Settings
(DIP switch 2 = ON and rotary coding switch = 1 is equivalent to lighting address 17 etc.)
Technical description
Cross section:
Temperature:
Dimensions (L x W x H in mm)
78 x 30 x 20
2
Max: 1.5mm
-30°C up to +60°C, T
=+75°C
cmax
SET
010 select
Prewired