3

3. Lock out and reset

The unit can be reset or brought into lock out mode in two
different ways:

Internal
In the lock out case the unit can be reset by pushing the built-
in button meaning a new start-up cycle is performed.

External
Instead of using the built-in lock out button the same
function can be achieved by using an external button which
connects terminal 9 with A (see also circuit and block
diagram).

If the  pushputton (internal or external) is pressed during
normal operation or during the start sequence for more then
3 sec. and afterwards released, the control box will perform
a shutdown.

Please note
The unit can only be brought to lockout mode or
be reseted if power is applied to the unit.

4. Low-voltage protection

at 220 / 240V (110 / 120V) nominal voltage

The mains voltage has to be more than 187 V

eff

 (94 V

eff 

) in

order to allow the unit to perform a start-up.
The mains voltage is not only monitored in the start-up
phase but also permanently during operation. If the voltage
drops below < 160 V

eff

 (80 V

eff 

) during start-up or run time the

control box proceed to safety shut-down and goes into a
waiting status. If the voltage rises again, the control box
performs automatically a start-up as soon as the mains
voltage is > 187 V

eff

 (94 V

eff 

).

5. Safety

The design and control sequence of the DMG 970 controls
will comply with the currently applicable standards and
regulations (see also TECHNICAL DATA).

6. Burner with an air damper motor

The position of the air damper during pre-purge
has to be assured by suitable actions
(EN 676, 4.4.1.2).

7. Mounting and electrical wiring

Wiring base:
– 3 earth terminals with additional terminal for burner

earthing

– 3 neutral terminals with internal permanent connection to

neutral terminal 8

– 2 independant spare terminals (S1 and S2)
– extra terminals A, B and C are standard (wiring base S98

12-pin)

– 2 slide-in plates and 2 easy knock out holes plus 2 knock

out holes in the base bottom faciliate the base wiring

Please note
To assist trouble-free operation the main neutral
connection terminal 8 in the wiring base must be
fully tightened. The terminal screws are already in
the undone position. To connect a wire to the
terminal, the screw only needs to be fastened.

General: The control box and detector probes should not be
subjected to excessive vibration.

DMG 973

Содержание Satronic DMG 973

Страница 1: ...a variety of cable entry points utmost flexibility of electrical wiring The DMG 973 is funstionally compatible to MMI 813 and MMI 813 1 Please note Is the DMG 973 to be used to replace the MMI 813 or 813 1 care has to be taken to make sure the air proving switch LW is wired between terminals 4 and 7 and not like on the MMI between 5 and 7 DMG 973 Gas Burner Safety Control For 2 stage forced draugh...

Страница 2: ... short pulse long pulse short pause _ long pause 1 2 Lock out diagnoses In case of a failure the LED is permanently illuminated Every 10 seconds the illumination is interrupted by a flash code whichindicatesthecauseoftheerror Thereforethefollowing sequence is performed which is repeated as long as the unit is not reset Sequence illuminated phase dark phase Flash Code dark phase for 10 sec for 0 6 ...

Страница 3: ...trol box proceed to safety shut down and goes into a waiting status If the voltage rises again the control box performs automatically a start up as soon as the mains voltage is 187 Veff 94 Veff 5 Safety The design and control sequence of the DMG 970 controls will comply with the currently applicable standards and regulations see also TECHNICAL DATA 6 Burner with an air damper motor The position of...

Страница 4: ...switch LW contact is still in it s closed position e g welded contacts Has the air proving switch LW changed to it s open position in the meantime e g by a run down motor a normal start sequence follows 3 Fault finding The built in information system facilitates the trouble shoot ing in the case of problems occurring during start up or during operation A list of possible lock out messages can be f...

Страница 5: ...er motor tlw max reaction time for air proving switch tv1 Supervised pre purge time tlk LK open command during pre purge tr LK close movement tf Stray light monitoring tvz Pre ignition time tn Post ignition time ts Safety time tv2 Delay terminal 6 C rv1 rs 2 C 6 5 7 4 3 B 8 9 A rz rv2 Flame amplifier Reset µC Reset and lock out Power supply monitoring RZ RV1 RV2 RS Fault display Information system...

Страница 6: ...IRD Holder M93 for IRD 1020 59093 Support for UVD Holder M74 for UVD 59074 Connection cable Plug type 3 core cable 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice VARIATION IRD right left axial 62 5 4 5 38 5 24 86 60 24 30 30 44 M4 Earth Reset butto...

Отзывы: