S9361A207X INTEGRATED BOILER CONTROLLERS
9
69-2751—05
Temperature Control
Temperature control setpoint on the module can be
adjusted as described in the following sections. Some
modules with temperature control also include a
three-digit display on the printed circuit board to
facilitate adjustments and troubleshooting.
A separate automatic gas shutoff device is not
required in a system that uses this control to meet
requirements for CSA International ANSI Z21.87 and
UL 353.
The overall range of the setpoint is model-dependent
but is within 140°F to 220°F (60°C to 104°C) with a
default to 180°F (82°C). Select devices may have
different ranges.
Adjusting Settings for Models
with “On-Board” Display
To discourage unauthorized changing of settings, a
procedure to enter the adjustment mode is required.
To enter the adjustment mode, press the UP, DOWN,
and
I
buttons (see Fig. 1) simultaneously for three
seconds. Press and release the
I
button until the
parameter requiring adjustment is displayed.
Display
In the RUN mode, status items and parameters are
viewable. For example, to display setpoint, the control
will flash “SP” (setpoint) followed by the temperature
(i.e., 135), followed by °F or °C.
To read settings, press and release the I key to find the
parameter of interest. For example, press and release
I
until setpoint (SP) is displayed, followed by a three-
digit number, i.e., 220, followed by °F or °C. Pressing
the
I
button again will display the (bt) Boiler
Temperature followed by a three-digit number and the
corresponding degree designator. See Display
Readout.
Integrated Boiler Control One
Rod (Combined Ignitor and
Sensor) Model Displays
See Table 6–8 for the IBC display screens.
Wait for vent
damper to open
18
Damper actuator is energized and the system waits for damper to close
Wait for vent
damper to close
19
Damper actuator is de-energize and the system waits for damper to open
Wait for vent
damper to open –
failed closed
20
Damper actuator is energized, system waits for damper to open, but the damper is
stuck in closed position (damper end switch is open)
Wait for vent
damper to close –
failed open
21
Damper actuator is de-energized, system waits for damper to close, but the damper
is stuck in open position (damper end switch is closed)
Table 5. State Code Definitions. (Continued)
State
State
code
Specific Description
General
Description
Table 6. 7-Segment LED Display - Installer Mode Options.
3-Digit 7-Segment Display
Default
Range
Description
1st
Screen
2nd Screen
3rd
Screen
HL_
<High Limit>
°
F
or
°
C
180
140 to 220 °F
Adjust High Limit Setting
HdF
<High Limit Differential>
°
F
or
°
C
15
10 to 30 °F
Adjust High Limit Differential
Or_
<Pump Overrun Time>
0
0 to 10 minutes
Pump Overrun Time (minutes)
PP_
<Pump Pre-purge Time>
2
2 to 20 minutes
Pump Pre-purge Time (minutes)
St_
<Start Temperature>
°
F
or
°
C
140
140 to 180 °F
Start Temperature
Pt_
On
or
OFF
On
On
or
OFF
Priority Time on or off
dh_
dh
or
tt2
dh
dh
or
tt2
Select the domestic input as a
second heating zone. Note that the
text of parameter value is right-
adjusted, unlike the rest of the
parameters.
rSt
On
or
OFF
NA
NA
Reset Hard or Soft Lockout
F-C
°
F
or °
C
F
F or C
Select degrees F or C Mode