Honeywell S9361A207 Series Скачать руководство пользователя страница 9

S9361A207X INTEGRATED BOILER CONTROLLERS

9

69-2751—05

Temperature Control

Temperature control setpoint on the module can be 
adjusted as described in the following sections. Some 
modules with temperature control also include a 
three-digit display on the printed circuit board to 
facilitate adjustments and troubleshooting.

A separate automatic gas shutoff device is not 
required in a system that uses this control to meet 
requirements for CSA International ANSI Z21.87 and 
UL 353.

The overall range of the setpoint is model-dependent 
but is within 140°F to 220°F (60°C to 104°C) with a 
default to 180°F (82°C). Select devices may have 
different ranges.

Adjusting Settings for Models 
with “On-Board” Display

To discourage unauthorized changing of settings, a 
procedure to enter the adjustment mode is required. 
To enter the adjustment mode, press the UP, DOWN, 

and 

I

 buttons (see Fig. 1) simultaneously for three 

seconds. Press and release the 

I

 button until the 

parameter requiring adjustment is displayed.

Display

In the RUN mode, status items and parameters are 
viewable. For example, to display setpoint, the control 
will flash “SP” (setpoint) followed by the temperature 
(i.e., 135), followed by °F or °C.

To read settings, press and release the I key to find the 
parameter of interest. For example, press and release 

I

 

until setpoint (SP) is displayed, followed by a three-
digit number, i.e., 220, followed by °F or °C. Pressing 
the 

I

 button again will display the (bt) Boiler 

Temperature followed by a three-digit number and the 
corresponding degree designator. See Display 
Readout.

Integrated Boiler Control One 
Rod (Combined Ignitor and 
Sensor) Model Displays

See Table 6–8 for the IBC display screens.

Wait for vent 
damper to open

18

Damper actuator is energized and the system waits for damper to close

Wait for vent 
damper to close

19

Damper actuator is de-energize and the system waits for damper to open

Wait for vent 
damper to open – 
failed closed

20

Damper actuator is energized, system waits for damper to open, but the damper is 
stuck in closed position (damper end switch is open)

Wait for vent 
damper to close – 
failed open

21

Damper actuator is de-energized, system waits for damper to close, but the damper 
is stuck in open position (damper end switch is closed)

Table 5. State Code Definitions. (Continued)

State

State 

code

Specific Description

General 

Description

Table 6. 7-Segment LED Display - Installer Mode Options.

3-Digit 7-Segment Display

Default

Range

Description

1st 

Screen

2nd Screen

3rd 

Screen

HL_

<High Limit>

°

F

 or 

°

C

180

140 to 220 °F

Adjust High Limit Setting

HdF

<High Limit Differential>

°

F

 or 

°

C

15

10 to 30 °F

Adjust High Limit Differential

Or_

<Pump Overrun Time>

0

0 to 10 minutes

Pump Overrun Time (minutes)

PP_

<Pump Pre-purge Time>

2

2 to 20 minutes

Pump Pre-purge Time (minutes)

St_

<Start Temperature>

°

F

 or 

°

C

140

140 to 180 °F

Start Temperature

Pt_

On

 or 

OFF

On

On

 or 

OFF

Priority Time on or off

dh_

dh

 or 

tt2

dh

dh

 or 

tt2

Select the domestic input as a 
second heating zone. Note that the 
text of parameter value is right-
adjusted, unlike the rest of the 
parameters.

rSt

On

 or 

OFF

NA

NA

Reset Hard or Soft Lockout

F-C

°

F

 or °

C

F

F or C

Select degrees F or C Mode

Содержание S9361A207 Series

Страница 1: ...culator and Domestic Hot Water Circulator output Enabled with EnviraCOM communication capability to support remote monitoring and diagnostics Limit rated Temperature Sensing Probe One Sensor Model SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not match the listed specifications exactly Also this...

Страница 2: ...c 0 5 to 0 6 PF Ambient Ratings Humidity 0 to 95 percent relative humidity noncondensing Operating Ambient Temperature 4 F to 150 F Shipping Ambient Temperature 40 F to 175 F Flame Monitoring May vary by model Flame Establishing Period FEP Maximum 2 sec onds Flame Failure Response Time FFRT Maximum 2 5 seconds 1 µA Flame Lost Threshold 0 23 µA Accessories Ordered Separately W8735Y1000 Wireless Out...

Страница 3: ...sary shield the controls to protect them from splashing water A NEMA 4 enclosure is recommended High Humidity or Dripping Water Over time dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board causing the module to fail Never install an appliance where water can drip on the controls In addition high ambient humidity can cause the control to corrode...

Страница 4: ...ecially so in commercial agricultural and industrial applications because 1 In such applications particularly commercial the equipment can operate 100 000 to 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years A normal boiler application for which the controls were intended typically operate fewer than 10 000 cycles per year 2 Exposure to water dirt chemical...

Страница 5: ...EGRATED BOILER CONTROLLERS 5 69 2751 05 Fig 2 Recommended slot hole pattern in appliance in mm Fig 3 Align module with slots in manufacturer s control box 100 M24198 16 16 55 4 99 5 4 WATER HEATER CONTROL BOX M24229 ...

Страница 6: ...ic standoff insulators as required 1 Connect one end of the cable to the male quick connect SPARK terminal on the module 2 Connect the other end of the cable to the igniter or igniter sensor stud on the pilot burner igniter sensor Connect Vent Damper Vent Damper Models A vent damper can be used with modules provided with a vent damper plug connector The Molex plug provided simplifies wiring connec...

Страница 7: ...etail Fig 4 Spark to Pilot Ignition Wiring S936X M533506 C R D DHW CIRCULATOR ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 DAMPER OPTIONAL INDUCER OPTIONAL 24VAC TRANSFORMER SENSOR DHW T STAT LIMIT SWITCH PRESSURE SWITCH PV PV MV GAS CONTROL SPARK IGNITER FLAME SENSE MV ...

Страница 8: ...n running mode flame signal must be present Postpurge 9 System is purging at the end of a call for heat Inter purge Retry Recycle Delay 10 If the control loses flame signal during state 7 or 8 it will recycle through the 30 seconds purge time and last 2secs part of prepurge time Re Start delay due to flame failure Wait for pressure switch to open failed closed 11 The inducer is still off and the p...

Страница 9: ...a three digit number and the corresponding degree designator See Display Readout Integrated Boiler Control One Rod Combined Ignitor and Sensor Model Displays See Table 6 8 for the IBC display screens Wait for vent damper to open 18 Damper actuator is energized and the system waits for damper to close Wait for vent damper to close 19 Damper actuator is de energize and the system waits for damper to...

Страница 10: ...reen 3rd Screen StA State number Status bt Sensed temperature F or C Boiler Temperature SP Operating Setpoint F or C Operating Setpoint the lowest of the IQ Outdoor air reset EnviraCOM message Desired Boiler Setpoint high limit setpoint and setpoint from the remote user interface device HL_ High Limit F or C Adjust High Limit Setting HdF High Limit Differential F or C Adjust High Limit Differentia...

Страница 11: ...mpound Honeywell part no 107408 to fill the space between the bulb and the well to improve heat transfer characteristics optional Make sure the sensor is held firmly in the well WIRING IMPORTANT For maximum trouble free operation run the sensor leadwires separately from any other current carrying wires All wiring must comply with local codes and ordinances Disconnect power supply before beginning ...

Страница 12: ...e heating cycle returns to idle and waits for the temperature to drop again The circulator is turned on throughout the Call for Heat See Fig 7 for a graphical representation of a simple control cycle Note that the setpoint differential may vary based on OS number High Limit Controller All models include a 3 wire temperature sensor interface Boiler temperature which is utilized for High Limit funct...

Страница 13: ...H OR CALL FOR HEAT LOST SWITCH OPEN SWITCH CLOSE SWITCH OPEN FLAME DEB ON FLAME DEB OFF TIME OUT TIME OUT OR MANUAL RESET LIMIT SWITCH OPEN TIME OUT FLAME SENSED FLAME PROVED TIME OUT WATER TEMPERATURE HIGH OR THERMOSTAT CALL FOR HEAT LOST RETRY DELAY TIME OUT A TIME OUT RECYCLE DELAY DAMPER PRESSURE SWITCH OPEN CHECK FLAME POST TRIAL FLAME DEB ON FLAME DEB OFF FLAME LOST A TIME OUT A TIME OUT TIM...

Страница 14: ...out of posi tion restore to correct position STEP 3 Check spark ignition circuit Disconnect the ignition cable at the SPARK terminal on the module WARNING The ignition circuit generates over 10 000 volts and electrical shock can result Energize the module and listen for the audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second for a d...

Страница 15: ...s duringA D conversion Err 35 Duplicate Zone alarm was received from zone panel Err 55 Atmospheric Damper End Switch failed to close end switch contacts stuck open Err 56 Atmospheric Damper End Switch failed to open end switch contacts stuck closed Err 57 Flame Rod shorted to burner ground Err 58 AC line frequency error signal is too noisy or frequency is incorrect Err 59 Line voltage error voltag...

Страница 16: ...risk Tamper evident tape has been placed on the bulk pack box to indicate if the package was opened Do not accept or use product received with damaged or missing tape Reverse engineering or modification of device is not permitted and may pose a safety risk LAZY YELLOW FLAME WAVING BLUE FLAME NOISY LIFTING BLOWING FLAME HARD SHARP FLAME SMALL BLUE FLAME CHECK FOR LACK OF GAS FROM CLOGGED ORIFICE FI...

Отзывы: