Honeywell S9361A207 Series Скачать руководство пользователя страница 3

S9361A207X INTEGRATED BOILER CONTROLLERS

3

69-2751—05

14,000,485-016 1/4 in. (6.35 mm) diameter, 1-1/4 in.

(31.75 mm) length glass cartridge Fuse, 1 A, 
Slow-Blow.

120650 Heat Conductive Compound. 

Ignition Cables:

32004766-012—36-in. standard ignition cable (one 

end with 90° boot, and other end with 1/4-in. quick 
connect).

Use cable types recommended in Table 3.

Table 3. Recommended Ignition Cables.

Transformer Requirement:

Add current ratings of module, pilot valve, main valve, 

vent damper and any other components of the con-
trol system to determine transformer size require-
ment.

The AT150B1260—commonly used 50 VA transformer.

Approvals:

Varies with control model.
ANSI Z21.20 Automatic Gas Ignition Systems and 

Components.

ANSI Z21.23 Gas Appliance Thermostats.
ANSI Z21.87: Automatic Gas Shutoff Devices for Hot 

Water Supply Systems.

UL353 Limit Controls.

INSTALLATION

Automatic Ignition Control domestic and commercial 
boiler systems are used on a wide variety of 
equipment. Some of these applications may make 
heavy demands on the controls, either because of 
frequent cycling, or because of moisture, corrosive 
chemicals, dust or excessive heat in the environment. 
In these situations, special steps may be required to 
prevent nuisance shutdowns and premature control 
failures. These applications require Honeywell 
Engineering review; contact your Honeywell Sales 
Representative for assistance.

Frequent Cycling

These controls are designed for use on domestic and 
commercial boiler systems that typically cycle less 
than 10,000 cycles per year. In an application with 
significantly greater cycling rates, we recommend 
monthly checkout because the controls may wear out 
more quickly.

Water or Steam Cleaning

Once a module or gas control has been wet, it may 
operate unreliably and must be replaced. If the 
appliance is likely to be cleaned with water or steam, 
the controls and associated wiring should be covered 
so that water or steam cannot reach them. The 
controls should be high enough above the bottom of 
the cabinet so they will not be subjected to flooding or 
splashing during normal cleaning procedures. If 
necessary, shield the controls to protect them from 
splashing water. A NEMA 4 enclosure is 
recommended.

High Humidity or Dripping Water

Over time, dripping water or high ambient humidity 
can create unwanted electrical paths on the module 
circuit board, causing the module to fail. 

Never

 install 

an appliance where water can drip on the controls.

In addition, high ambient humidity can cause the 
control to corrode and finally fail.

Where the appliance may be installed in a humid 
atmosphere, make sure air circulation around the 
module and gas control is adequate to prevent 
condensation. It is also important to regularly check 
out the system. A NEMA 4 enclosure may be needed.

Corrosive Chemicals

Corrosive chemicals can also attack the module and 
gas control and eventually cause a failure. Where 
chemicals may be used routinely for cleaning, make 
sure the cleaning solution cannot reach the controls. 
Where chemicals are likely to be suspended in the air, 
as in some industrial and agricultural applications, 
protect the module from exposure with a NEMA 4 
enclosure.

Dust or Grease Accumulation

Heavy accumulation of dust or grease may cause the 
controls to malfunction. Where dust or grease may be 
a problem, provide covers for the module and gas 
control that limit environmental contamination. A 
NEMA 4 enclosure is recommended for the module.

Heat

The controls can be damaged by excessively high 
temperatures. Make sure the maximum ambient 
temperature at the control locations will not exceed 
the rating of the control. If the appliance normally 
operates at very high temperatures, insulation, 
shielding, and air circulation may be necessary to 
protect the controls. Proper insulation or shielding 
should b provided by the appliance manufacturer; 
make sure adequate air circulation is maintained 
when the appliance is installed.

Table 1. Wells for Controller.

Part 

Number

Spud Size

in. (mm)

Insertion 

in. (mm)

Insulation 

in. (mm)

123869A 1/2 (12.7) NPT 3 (76.2)

1-1/2 (38.1)

123870A 3/4 (19.05) 

NPT

3 (76.2)

1-1/2 (38.1)

Table 2. Sensors for Controller.

Part Number

Length in. 

(mm)

Application

50001464-001 12 (304.8) Well-mounted 

controls

50001464-003 24 (609.6) Flush-mounted 

controls

50001464-004 36 (914.4)

50001464-005 48 

(1219.2)

Cable Type

Voltage 

Rating 

(rms)

Temperature Rating

°C

°F

UL Style 
3217

10,000

150

302

UL Style 
3257

10,000

250

484

Содержание S9361A207 Series

Страница 1: ...culator and Domestic Hot Water Circulator output Enabled with EnviraCOM communication capability to support remote monitoring and diagnostics Limit rated Temperature Sensing Probe One Sensor Model SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not match the listed specifications exactly Also this...

Страница 2: ...c 0 5 to 0 6 PF Ambient Ratings Humidity 0 to 95 percent relative humidity noncondensing Operating Ambient Temperature 4 F to 150 F Shipping Ambient Temperature 40 F to 175 F Flame Monitoring May vary by model Flame Establishing Period FEP Maximum 2 sec onds Flame Failure Response Time FFRT Maximum 2 5 seconds 1 µA Flame Lost Threshold 0 23 µA Accessories Ordered Separately W8735Y1000 Wireless Out...

Страница 3: ...sary shield the controls to protect them from splashing water A NEMA 4 enclosure is recommended High Humidity or Dripping Water Over time dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board causing the module to fail Never install an appliance where water can drip on the controls In addition high ambient humidity can cause the control to corrode...

Страница 4: ...ecially so in commercial agricultural and industrial applications because 1 In such applications particularly commercial the equipment can operate 100 000 to 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years A normal boiler application for which the controls were intended typically operate fewer than 10 000 cycles per year 2 Exposure to water dirt chemical...

Страница 5: ...EGRATED BOILER CONTROLLERS 5 69 2751 05 Fig 2 Recommended slot hole pattern in appliance in mm Fig 3 Align module with slots in manufacturer s control box 100 M24198 16 16 55 4 99 5 4 WATER HEATER CONTROL BOX M24229 ...

Страница 6: ...ic standoff insulators as required 1 Connect one end of the cable to the male quick connect SPARK terminal on the module 2 Connect the other end of the cable to the igniter or igniter sensor stud on the pilot burner igniter sensor Connect Vent Damper Vent Damper Models A vent damper can be used with modules provided with a vent damper plug connector The Molex plug provided simplifies wiring connec...

Страница 7: ...etail Fig 4 Spark to Pilot Ignition Wiring S936X M533506 C R D DHW CIRCULATOR ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 DAMPER OPTIONAL INDUCER OPTIONAL 24VAC TRANSFORMER SENSOR DHW T STAT LIMIT SWITCH PRESSURE SWITCH PV PV MV GAS CONTROL SPARK IGNITER FLAME SENSE MV ...

Страница 8: ...n running mode flame signal must be present Postpurge 9 System is purging at the end of a call for heat Inter purge Retry Recycle Delay 10 If the control loses flame signal during state 7 or 8 it will recycle through the 30 seconds purge time and last 2secs part of prepurge time Re Start delay due to flame failure Wait for pressure switch to open failed closed 11 The inducer is still off and the p...

Страница 9: ...a three digit number and the corresponding degree designator See Display Readout Integrated Boiler Control One Rod Combined Ignitor and Sensor Model Displays See Table 6 8 for the IBC display screens Wait for vent damper to open 18 Damper actuator is energized and the system waits for damper to close Wait for vent damper to close 19 Damper actuator is de energize and the system waits for damper to...

Страница 10: ...reen 3rd Screen StA State number Status bt Sensed temperature F or C Boiler Temperature SP Operating Setpoint F or C Operating Setpoint the lowest of the IQ Outdoor air reset EnviraCOM message Desired Boiler Setpoint high limit setpoint and setpoint from the remote user interface device HL_ High Limit F or C Adjust High Limit Setting HdF High Limit Differential F or C Adjust High Limit Differentia...

Страница 11: ...mpound Honeywell part no 107408 to fill the space between the bulb and the well to improve heat transfer characteristics optional Make sure the sensor is held firmly in the well WIRING IMPORTANT For maximum trouble free operation run the sensor leadwires separately from any other current carrying wires All wiring must comply with local codes and ordinances Disconnect power supply before beginning ...

Страница 12: ...e heating cycle returns to idle and waits for the temperature to drop again The circulator is turned on throughout the Call for Heat See Fig 7 for a graphical representation of a simple control cycle Note that the setpoint differential may vary based on OS number High Limit Controller All models include a 3 wire temperature sensor interface Boiler temperature which is utilized for High Limit funct...

Страница 13: ...H OR CALL FOR HEAT LOST SWITCH OPEN SWITCH CLOSE SWITCH OPEN FLAME DEB ON FLAME DEB OFF TIME OUT TIME OUT OR MANUAL RESET LIMIT SWITCH OPEN TIME OUT FLAME SENSED FLAME PROVED TIME OUT WATER TEMPERATURE HIGH OR THERMOSTAT CALL FOR HEAT LOST RETRY DELAY TIME OUT A TIME OUT RECYCLE DELAY DAMPER PRESSURE SWITCH OPEN CHECK FLAME POST TRIAL FLAME DEB ON FLAME DEB OFF FLAME LOST A TIME OUT A TIME OUT TIM...

Страница 14: ...out of posi tion restore to correct position STEP 3 Check spark ignition circuit Disconnect the ignition cable at the SPARK terminal on the module WARNING The ignition circuit generates over 10 000 volts and electrical shock can result Energize the module and listen for the audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second for a d...

Страница 15: ...s duringA D conversion Err 35 Duplicate Zone alarm was received from zone panel Err 55 Atmospheric Damper End Switch failed to close end switch contacts stuck open Err 56 Atmospheric Damper End Switch failed to open end switch contacts stuck closed Err 57 Flame Rod shorted to burner ground Err 58 AC line frequency error signal is too noisy or frequency is incorrect Err 59 Line voltage error voltag...

Страница 16: ...risk Tamper evident tape has been placed on the bulk pack box to indicate if the package was opened Do not accept or use product received with damaged or missing tape Reverse engineering or modification of device is not permitted and may pose a safety risk LAZY YELLOW FLAME WAVING BLUE FLAME NOISY LIFTING BLOWING FLAME HARD SHARP FLAME SMALL BLUE FLAME CHECK FOR LACK OF GAS FROM CLOGGED ORIFICE FI...

Отзывы: