TROUBLESHOOTING

WARNING

FIRE, EXPLOSION OR SHOCK HAZARD.
MAY CAUSE PROPERTY DAMAGE, SEVERE IN-
JURY OR DEATH.
Do not attempt to modify the physical or electrical
characteristics of this device in any way. Replace
it if troubleshooting indicates a malfunction.

The integrated furnace control has two status lights:

PWR—is on whenever the control has 24 Vac input
power from the system transformer.

OK—comes on if control’s internal checks are OK.
Light pulses at approximately six second intervals as
long as control’s continuous self-check indicates
normal operation. If the light goes out during opera-
tion, control must be replaced.

IMPORTANT

1. The service procedure outlined in Fig. 3 is a general

guide. Follow appliance manufacturer’s service in-
structions if available.

2. All meter readings must be taken within the trial for

ignition period. Once the ignition period ends, the
system must be reset by setting the thermostat
down for at least 45 sec. before continuing.

3. If any component does not function properly, make

sure it is correctly installed and wired before replac-
ing it.

4. Static discharge can damage the integrated furnace

control. Touch metal surface to discharge static
electricity before touching furnace control.

5. The integrated furnace control cannot be repaired.

If it malfunctions, it must be replaced.

6. Only trained, experienced service technicians should

service integrated furnace control systems. Per-
form the checkout steps on page 3 before beginning
the troubleshooting procedure in Fig. 3. Following
troubleshooting, check out the system again to be
sure it is operating normally.

Содержание S9201A1010

Страница 1: ...ing Igniter surface area immersed in flame must not ex ceed1 4ofthegroundedareaimmersedinflame This would prevent flame sensing Igniter current draw at 132 Vac must not exceed 5 A 2 Check the ratings given in these instructions to make sure the integrated furnace control is suitable for your appli cation 3 Installer must be a trained experienced service techni cian 4 After installation is complete...

Страница 2: ...en burner and S9201 1 4 in male Transformer secondary quick connects Field 120 Vac Screw terminals Humidifier and electronic air cleaner 24 Vac Screw terminals Thermostat WIRING CAUTION 1 Check the wiring diagram furnished by the appli ance manufacturer if available for circuits differing from the general hookup shown Carefully follow anyspecialinstructionsaffectingthegeneralproce dures outlined b...

Страница 3: ...roubleshooting Check Safety Shutoff Operation Shut off gas supply at manual gas valve ahead of appli ance Set thermostat to call for heat System should operate as indicated in Table 4 Following lockout open manual gas valve and make sure no gas is flowing to burner TABLE 4 S9201A1010 SEQUENCE ON FAILURE TO LIGHT FIG 2 LADDER DIAGRAM OF S9201 INTEGRATED FURNACE CONTROL 1 POWER SUPPLY PROVIDE DISCON...

Страница 4: ...neral guide Follow appliance manufacturer s service in structions if available 2 All meter readings must be taken within the trial for ignition period Once the ignition period ends the system must be reset by setting the thermostat down for at least 45 sec before continuing 3 If any component does not function properly make sure it is correctly installed and wired before replac ing it 4 Staticdisc...

Страница 5: ...NS POWERED AND LIT YES YES YES YES NO NO INDOOR BLOWER MOTOR STARTS AFTER 30 SECONDS CHECK FOR 120 VAC ACROSS BLOWER MOTOR AND BLOWER MOTOR TERMINALS ON IFC REPLACE IFC IF WIRING TO BLOWER MOTOR IS OK M890 NOTE If IFC goes into lockout wait 30 seconds then reset system CHECK CONTINUITY OF GROUND WIRE NOTE IF GROUND IS POOR OR ERRATIC SHUTDOWN MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL ...

Страница 6: ...ng You Control Your World Building Controls Division Building Controls Division Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 QUALITY IS KEY ...

Отзывы: