background image

5

69-0685

FIG. 3—S9201A1010 TROUBLESHOOTING GUIDE.

NO

YES

REPLACE BLOWER MOTOR

YES

REPLACE GAS CONTROL

NO

NO

REPLACE IFC IF WIRING TO IGNITER IS OK

YES

NO

CHECK LINE VOLTAGE POWER
CHECK LOW VOLTAGE TRANSFORMER

PWR LIGHT ON

YES

YES

NO

IGNITER WARMS UP

AND GLOWS RED

(36 SECOND WARMUP)

¥
¥

30 SEC PREPURGE

NO

REPLACE IFC

YES

NO

YES

NO

REPLACE SWITCH

REPLACE IFC IF WIRING TO 
IDB MOTOR IS OK

REPLACE IDB MOTOR

START

SET THERMOSTAT  TO 

CALL FOR HEAT

SET FAN SWITCH TO AUTO

¥  CHECK LIMITS (CLOSED)
¥  CHECK WIRING

¥  CHECK AIR PROVING SWITCH (OPEN)

¥  CHECK FOR 120 VAC TO IDB MOTOR

OK LIGHT ON

YES

¥  CHECK FOR  BLOCKED VENT
¥  CHECK AIR PROVING SWITCH (CLOSED)

¥  CHECK WIRING TO IGNITER
¥  CHECK FOR 120 VAC AT IGNITER

¥

  TERMINALS AND AT IFC TERMINALS

REPLACE IGNITER

NO

MAIN BURNER

LIGHTS

System will attempt to light 5 times (30 second delay between tries).  Voltage is present at the valve 
for only 9 seconds during each trial for ignition.  System will lock out after 5 tries.

¥  CHECK FOR  24 VAC ACROSS THE P1-2 AND P1-4 TERMINALS ON THE IFC

NO

NOTE:  If IFC goes into lockout  wait 30 seconds then reset system.

¥  CHECK LINE VOLTAGE POLARITY
¥  CHECK CONTINUITY OF GROUND WIRE
¥  CHECK INSULATION ON IGNITER LEADS
¥  CHECK INSULATION ON SENSOR LEADS
¥  CHECK SENSOR POSITION
¥  IF CHECKS ARE OK, REPLACE IFC

NO

MAIN BURNER 

REMAINS 

POWERED AND LIT

YES

YES

YES

YES

NO

NO

INDOOR BLOWER 

MOTOR STARTS 

AFTER 30 SECONDS

¥  CHECK FOR  120 VAC ACROSS BLOWER 

¥

  MOTOR AND BLOWER MOTOR 

¥ 

 TERMINALS ON IFC

REPLACE IFC IF WIRING TO 
BLOWER MOTOR IS OK

M890

NOTE:  If IFC goes into lockout  wait 30 seconds then reset system.

¥  CHECK CONTINUITY OF GROUND WIRE.  NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWN MAY 

¥

  OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL AT THE TIME OF CHECKOUT.

¥  CHECK FOR EXCESSIVE HEAT AT IGNITER BASE.  TEMPERATURE ABOVE 1000F (538 C) CAUSES 

¥

  SHORT TO GROUND

¥  IF CHECKS ARE OK, REPLACE IFC

NO

SYSTEM RUNS 

UNTIL CALL FOR 

HEAT ENDS

YES

YES

¥  CHECK FOR PROPER TEMPERATURE CONTROLLER OPERATION
¥  REMOVE GAS CONTROL LEAD AT IFC.  IF GAS CONTROL CLOSES, RECHECK TEMPERATURE 

¥

  CONTROLLER AND WIRING.  IF NOT, REPLACE GAS CONTROL

NO

YES

INDUCED DRAFT

MOTOR STARTS

SET THERMOSTAT TO OFF,

GAS CONTROL CLOSES,

FLAME OFF

NO

INDOOR BLOWER 

MOTOR STOPS AFTER 

90/45/60/75 SECS

YES

TROUBLESHOOTING

ENDS

¥  CHECK FOR OPEN LIMIT.  REPLACE IFC

REPEAT PROCEDURE UNTIL TROUBLEFREE 
OPERATION IS OBTAINED

IFC = Integrated Furnace Control
IDB = Induced Draft Blower

KEY:  

NOTE: STATIC DISCHARGE CAN DAMAGE IFC

WARNING

ELECTRICAL SHOCK HAZARD
MAY CAUSE SERIOUS INJURY OR DEATH

Dangerous line voltage is exposed during troubleshooting.  
Disconnect power before touching control.  Service must be 
by trained, experienced service technician.

REPLACE SWITCH

¥  CHECK IGNITER POSITION
¥  CHECK FOR GAS FLOW TO AND FROM

¥

  GAS CONTROL

REPLACE IFC IF WIRING TO 
GAS CONTROL IS OK

Содержание S9201A1010

Страница 1: ...ing Igniter surface area immersed in flame must not ex ceed1 4ofthegroundedareaimmersedinflame This would prevent flame sensing Igniter current draw at 132 Vac must not exceed 5 A 2 Check the ratings given in these instructions to make sure the integrated furnace control is suitable for your appli cation 3 Installer must be a trained experienced service techni cian 4 After installation is complete...

Страница 2: ...en burner and S9201 1 4 in male Transformer secondary quick connects Field 120 Vac Screw terminals Humidifier and electronic air cleaner 24 Vac Screw terminals Thermostat WIRING CAUTION 1 Check the wiring diagram furnished by the appli ance manufacturer if available for circuits differing from the general hookup shown Carefully follow anyspecialinstructionsaffectingthegeneralproce dures outlined b...

Страница 3: ...roubleshooting Check Safety Shutoff Operation Shut off gas supply at manual gas valve ahead of appli ance Set thermostat to call for heat System should operate as indicated in Table 4 Following lockout open manual gas valve and make sure no gas is flowing to burner TABLE 4 S9201A1010 SEQUENCE ON FAILURE TO LIGHT FIG 2 LADDER DIAGRAM OF S9201 INTEGRATED FURNACE CONTROL 1 POWER SUPPLY PROVIDE DISCON...

Страница 4: ...neral guide Follow appliance manufacturer s service in structions if available 2 All meter readings must be taken within the trial for ignition period Once the ignition period ends the system must be reset by setting the thermostat down for at least 45 sec before continuing 3 If any component does not function properly make sure it is correctly installed and wired before replac ing it 4 Staticdisc...

Страница 5: ...NS POWERED AND LIT YES YES YES YES NO NO INDOOR BLOWER MOTOR STARTS AFTER 30 SECONDS CHECK FOR 120 VAC ACROSS BLOWER MOTOR AND BLOWER MOTOR TERMINALS ON IFC REPLACE IFC IF WIRING TO BLOWER MOTOR IS OK M890 NOTE If IFC goes into lockout wait 30 seconds then reset system CHECK CONTINUITY OF GROUND WIRE NOTE IF GROUND IS POOR OR ERRATIC SHUTDOWN MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL ...

Страница 6: ...ng You Control Your World Building Controls Division Building Controls Division Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 QUALITY IS KEY ...

Отзывы: