Honeywell S8921D Скачать руководство пользователя страница 9

69-0924—2

9

S8921D HOT SURFACE IGNITION MODULE

Status LED Used to Troubleshoot

The LED can be used to check the appliance status. A
description of the LED signals follows.

IMPORTANT:

The LED shows system status for the current call
for heat. When the call for heat is interrupted
(thermostat satisfied or system power switched
off), the LED goes off and the status information
is lost.

Pulsing heartbeat (on, pulsing) is the normal operating
mode during a call for heat (24V terminal is powered).
The system can be in any of the normal operating
modes including warmup, combustion air proving,
ignition trial, normal run, or between trial delay.

One flash indicates the S8921D is in an air proving
switch safe start failure mode. This means that the air
proving switch (normally open) is being detected as a
closed circuit. The control is not locked out. Reset the
thermostat and retry. Replace the air proving switch if
indication continues.

Two flashes indicate the S8921D is in lockout due to
insufficient combustion air flow. Check combustion air
flow. Reset the thermostat and retry. Rectify combus-
tion air flow if indication continues.

Three flashes indicate a lockout due to ignition failure.
The most probable cause is the main burner failing to
light or failure to detect the flame. Run the appliance
through a call for heat and if the burner does not light,
check the:
—gas supply
—input voltage
—hot surface igniter
—gas control
—wiring
If the main burner lights, but goes out at the end of
ignition trial, check the:
—flame rod for weak flame rectification signal. The
most probable causes are:
—contaminated or mislocated igniter/sensor or flame
rod
—poor flame sense leadwire insulation or connections
—poor gas pressure
—burner ground connections
—wiring

Four flashes indicate a lockout due to an internal error.
The most probable cause is a S8921D logic failure.
Start a new call for heat and if the four-flash signal
returns, replace the S8921D.

On steadily indicates a control defect. Start a new call
for heat. If LED comes on steadily (no pulsing heart-
beat) replace the S8921D.

Off indicates control defect or no power. Check system
power and wiring. If there is 24 Vac between the
S8921D 24V and 24V (GND) terminals, but LED is off,
replace the S8921D.

Ignition System Checks

Step 1: Check wiring harness.

Make sure:

1. Connections to the ignition module, air proving

switch, and gas control are clean and tight.

2. Hot surface ignition cable provides good electrical

continuity.

Step 2: Check ignition system grounding.
Nuisance shutdowns are often caused by a poor
or erratic ground.

A common ground is required for the module, flame
sensor, and main burner.

1. Check for good metal-to-metal contact between the

igniter bracket and the main burner.

2. Check the ground path from the GND (BURNER)

terminal on the module to the main burner. Make
sure connections are clean and tight. If the wire is
damaged or deteriorated, replace it by following the
appliance manufacturer instructions. A temporary
leadwire connection between the GND (BURNER)
terminal and the main burner can help confirm a
ground path problem.

3. Check temperature at the igniter ceramic or flame

sensor insulator. Excessive temperature will permit
leakage to ground. Contact appliance manufacturer
if temperature exceeds rating of igniter or sensor.

4. If flame sensor or bracket is bent out of position,

restore to correct position.

5. Replace igniter or flame sensor with identical unit if

insulator is cracked.

Step 3: Check flame sensing circuit.

1. Make sure burner flame is capable of providing a

good rectification signal. See Fig. 3.

2. Make sure about 3/4 to 1 in. of the flame sensor is

continuously immersed in the flame for best flame
signal. See Fig. 3.

3. Check for excessive (over 1000

°

F [538

°

C]) tempera-

ture at the ceramic insulator on the flame sensor.
Excessive temperature can cause a short to ground.

4. Check for cracked igniter or sensor ceramic

insulator, which can cause short to ground, and
replace unit if necessary.
• Make sure electrical connections are clean and

tight. Replace damaged wire with moisture-
resistant No. 18 wire rated for continuous duty up
to 221

°

F (105

°

C).

5. If the igniter is other than a Norton 271, make sure it

meets the following specifications:

• Igniter must reach 1832

°

F (1000

°

C) within 17

seconds with 102 Vac applied.

• Igniter must maintain at least 500M ohm insulation

resistance between the igniter leadwires and the
igniter mounting bracket.

• Igniter must not develop an insulating layer on its

surface (over time) that would prevent flame
sensing.

• Igniter surface area immersed in flame must not

exceed one-fourth of the grounded area immersed
in flame. This would prevent flame sensing.

• Igniter current draw at 132 Vac must not exceed 5A.

Содержание S8921D

Страница 1: ... 60 Hz Contact Rating at 120 Vac Hot Surface Igniter 5A Combustion Air Blower 3 FLA 10 LRA IMPORTANT The S8921D is to be used only in a 60 Hz system Be sure the system is not 50 Hz Hot Surface Igniter Norton Model 271 or equivalent NOTE If an igniter other than a Norton Model 271 is used the igniter must meet the following minimum specifications required over the life of the igniter Igniter must r...

Страница 2: ...A 4 enclosure is recommended for the ignition module see the Electronic Ignition Service manual 70 6604 Corrosive Chemicals Corrosive chemicals can attack the module and gas control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the controls Where chemicals are suspended in air as in some industrial or agricultural applications NEMA 4 enclosure is recom ...

Страница 3: ...ly before doing any work on the unit Disconnect and tag the wires from the old module Label each wire as it is removed Remove the old module from its mounting location Mount New Ignition Module Mount the new module in the same location as the old module Protect the module from exposure to water moisture corrosive chemicals and excessive dust and grease Make certain that the ambient temperature at ...

Страница 4: ...ormer has adequate VA The ignition module requires 0 4A at 24 Vac Add the current draws of all other devices in the control circuit including the pilot and main valves in the gas control and multiply by 24 to determine the total VA requirement of these components Add this total to 9 6 VA for the ignition module The result is the minimum transformer VA rating Use a Class II trans former when replac...

Страница 5: ... gas control is energized 5 Gas control is energized for the trial for ignition time This time can be measured by connecting a voltmeter range set to measure approximately 24 Vac across the gas valve terminals 6 After the trial for ignition the between trial delay begins and the combustion air blower is turned off 7 The second trial begins with the hot surface igniter warmup followed by the combus...

Страница 6: ...nition The gas control opens for the ignition trial time The hot surface igniter stays powered for the ignition activation period and then the igniter turns off Near the end of the ignition trial time the flame rectification sensing circuit determines if the main burner flame is present If so the gas control remains open and the burner operation phase begins Burner Operation When the main burner i...

Страница 7: ...onsiderations are Cycling frequency Appliances that may cycle 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environment Since th...

Страница 8: ... of module Re establish call for heat Check for 24 Vac across VALVE and VALVE GND terminals during trial for ignition Note Voltage present only during trial for ignition after air proving switch confims combustion air flow Replace module Check replace wiring to gas control Check replace gas control Note Ignition module will continue ignition cycle to lockout after 5 trials for ignition Troubleshoo...

Страница 9: ...em Checks Step 1 Check wiring harness Make sure 1 Connections to the ignition module air proving switch and gas control are clean and tight 2 Hot surface ignition cable provides good electrical continuity Step 2 Check ignition system grounding Nuisance shutdowns are often caused by a poor or erratic ground A common ground is required for the module flame sensor and main burner 1 Check for good met...

Страница 10: ...69 0924 2 10 S8921D HOT SURFACE IGNITION MODULE ...

Страница 11: ...69 0924 2 11 S8921D HOT SURFACE IGNITION MODULE ...

Страница 12: ...ted Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 69 0924 2 J S Rev 6 98 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: