69-0845—2
13
S8910U UNIVERSAL HOT SURFACE IGNITION MODULE
Purge/Prepurge
When the S8910U is used in a fan-assisted combustion
system, the combustion air blower starts on a call for heat
from the thermostat. On proof of airflow, the air proving
switch closes and energizes the S8910U. When the
S8910U is used in an atmospheric system, the call for heat
energizes the module.
In either case, the S8910U first initiates a 32-second delay
to allow system prepurge.
Igniter Warmup
After prepurge, the S8910U energizes the igniter to start
the igniter warmup. The module energizes the hot surface
igniter for a 34-second warmup period, during which the
gas control is closed.
Fig. 7. S8910U normal operating sequence.
START
PREPURGE/
IGNITER
WARMUP
CALL FOR HEAT (24V
TERMINAL POWERED)
INTERNAL SAFE START
CHECK BEGINS.
FLAME
SIMULATING
FAILURE
SYSTEM WILL
NOT START
PREPURGE
IGNITER WARMS UP
BETWEEN
TRIAL
PURGE
TRIAL FOR
IGNITION
GAS CONTROL OPENS
FOR TIMED TRIAL
FOR IGNITION.
.LOCKOUT OCCURS;
SYSTEM MUST BE
RESET.
GAS
CONTROL
CLOSES
NO
FLAME
IGNITER OFF;
FLAME SENSING BEGINS.
ONE TRIAL
(TABS A
AND C)
LESS
THAN
THREE
ONE TRIAL
(TABS A AND C)
THREE TRIALS
(TABS B AND D)
HOW MANY IGNITION
TRIALS COMPLETED THIS
CALL FOR HEAT?
THREE
LOCKOUT OCCURS;
SYSTEM MUST BE
RESET.
GAS CONTROL CLOSES
(MAIN BURNER OFF).
GAS
CONTROL
CLOSES
THREE TRIALS
(TABS B AND D)
FLAME
FAILURE
GAS CONTROL STAYS
OPEN (MAIN BURNER
RUNS).
MAIN BURNER
OPERATION
END
NO FLAME
SIMULATING
FAILURE
FLAME
PRESENT
M8527A
CALL FOR HEAT
IS SATISFIED.