Honeywell S8910U Скачать руководство пользователя страница 12

69-0845—2

12

S8910U UNIVERSAL HOT SURFACE IGNITION MODULE

Step 4:

 Reset the ignition module.

a. Turn the thermostat or controller to the lowest

setting.

b. Turn on the system power.
c. Wait one minute.

As you do Steps 5 and 6, watch for points where operation
deviates from normal. Refer to Troubleshooting section to
correct problem.

Step 5:

 Check safety lockout operation.

a. Turn off the gas supply.
b. Set the thermostat or controller above the room

temperature to call for heat.

c. Watch for igniter warmup following prepurge. Igniter

starts to glow several seconds after it is powered.

d. Time the length of time the gas control is energized;

measure the time by connecting a voltmeter across
the gas valve terminals:

Selection tabs A and B—4 seconds.
Selection tabs C and D—7 seconds.

e. When using a three-trial ignition selection tab (tabs

B or D), watch for the start of 96-second between-
trial purge, followed by 34-second igniter warmup
and second try for ignition. After a third purge,
warmup and trial for ignition sequence, the S8910U
should lock out. LED goes into one flash mode after
lockout.

f. Open the manual gas control knob and make sure

no gas is flowing to the burner.

g. Set the thermostat below the room temperature and

wait one minute before continuing.

Step 6:

 Check normal operation.

a. Set the thermostat or controller above the room

temperature to call for heat.

b. Observe the lightoff sequence and make sure the

main burner lights smoothly without flashback.

c. Make sure the burner operates smoothly without

floating, lifting, or flame rollout to the furnace
vestibule or heat buildup in the vestibule.

d. Test for a gas leak downstream of the gas control if

piping has been disturbed.

GAS LEAK TEST: Paint the gas control gasket edges and
all pipe connections downstream of the gas control with a
rich soap and water solution. Bubbles indicate a gas leak.
Tighten the joints and screws or replace component to
stop a gas leak. Recheck with soap and water solution.

e. Check the burner flame condition. The igniter-sensor

or sensor must be constantly immersed in flame.
Check the burner flame condition as shown in Fig. 6.
Do not relocate the hot surface igniter or flame rod.

f. Turn the thermostat or controller below the room

temperature. Make sure the main burner and pilot
flames go out.

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.

Improper location of the 120 Vac hot surface
igniter or any flame sensing rod can result in
appliance malfunction.
1. Never attempt to relocate the 120 Vac hot

surface igniter or the flame sensing rod from the
original position established by the appliance
manufacturer.

2. Be sure the 120 Vac hot surface igniter or the

flame sensing rod is replaced in exactly the
original position after removal for inspection,
service or replacement.

Fig. 6. Check burner flame condition.

OPERATION

The S8910U is a direct ignition control used with a
120 Vac timed warmup hot surface igniter. The control
provides operating control and shuts off all gas flow on
ignition failure or loss of main burner flame in central heat
furnaces and other heating appliances.

Module operation is in three phases—prepurge/igniter
warmup, trial for ignition and burner operation. The
S8910U provides one or three trials for ignition, depending
on which selection tab is installed. Fig. 7 shows the normal
operating sequence.

CHECK BURNER FLAME CONDITION

NOISY
LIFTING
FLAME

BURNER

WAVING
FLAME

SMALL
BLUE
FLAME

LAZY
YELLOW
FLAME

GOOD
RECTIFYING
FLAME

3/4 TO 1 IN. (19 TO 25 MM)

1/4 TO 1/2 IN. (6 TO 13 MM)

M8446

CHECK FOR:
•  HIGH GAS PRESSURE
•  EXCESS PRIMARY AIR 
   OR DRAFT

CHECK FOR:
•  POOR DRAFT
•  EXCESS DRAFT
•  HIGH VELOCITY OR
   SECONDARY AIR
INSTALL SHIELD IF NECESSARY

CHECK FOR:
•  CLOGGED PORTS OR
   ORIFICE FILTER
•  WRONG SIZE ORIFICE

CHECK FOR LACK OF 
AIR FROM:
  •  DIRTY PRIMARY 
     AIR OPENING
  •  LARGE PORTS 
     OR ORIFICES

Содержание S8910U

Страница 1: ...and seven wire labels The wiring labels are included to assure proper marking of the wires attached to the existing module A complete list of the specific Honeywell and other modules that the SUPER TRADELINE S8910U is designed to replace is provided in Tables 1 through 3 NOTE The S8910U is intended to replace only defective ignition controls The service technician should make sure that the other p...

Страница 2: ...59 B Yes R 4 3 30 45 90 50E47 260 thru 269 B Yes R 4 3 0 17 60 Sensor A separate sensor is required for remote sensing applica tions Wiring Use the existing appliance wiring If repair or replacement of leadwires is required follow the instructions on the appliance label Use the included quick connect terminals according to the instructions Prepurge 32 seconds Igniter Warmup 34 seconds Between Tria...

Страница 3: ...hru 119 C Yes R 7 1 0 45 NA 50F47 120 thru 129 C Yes R 7 1 17 17 NA 50F47 130 thru 139 C Yes R 7 1 17 45 NA 50F47 140 thru 149 D Yes R 7 3 17 17 77 50F47 150 thru 159 D Yes R 7 3 17 45 77 50F47 160 thru 169 D Yes R 7 3 0 17 60 50F47 170 thru 179 D Yes R 7 3 0 45 60 50F47 201 thru 209 A Yes R 4 1 0 17 NA 50F47 210 thru 219 A Yes R 4 1 0 45 NA 50F47 220 thru 229 A Yes R 4 1 17 17 NA 50F47 230 thru 2...

Страница 4: ... No L 4 3 0 34 34 HS780 34NL 306A D No L 6a 3 0 34 34 HS780 34NL 308A D No L 8a 3 0 34 34 HS780 34NL 312A D No L 12b 3 0 34 34 HS780 34NR 104A A Yes R 4 1 0 34 NA HS780 34NR 306A D Yes R 6a 3 0 34 34 HS780 34NR 308A D Yes R 8a 3 0 34 34 HS780 34NR 312A D Yes R 12b 3 0 34 34 HS780 34PL 308A D No L 8a 3 34 34 34 Table 2 Robertshaw Control to Honeywell S8910U Cross Reference NOTE Robertshaw product i...

Страница 5: ...under a variety of input conditions to assure reliable operation REVIEW THE INSTALLATION WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Follow these warnings exactly 1 Review the installation as outlined in this section 2 Plan for frequent maintenance as described in the Maintenance section When hot surface ignition systems are used on central heating equipment i...

Страница 6: ...onent and appliance operation as provided in these instructions WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH 1 If the ignition module gets wet it can malfunc tion leading to accumulation of explosive gas Never install where water can flood drip or condense on the module Never use a module that has been wet Replace it 2 Liquefied petroleum LP gas is heavier than...

Страница 7: ...check out the S8910U and selection tabs Use only the selection tab specified in Tables 1 through 3 for the existing module being replaced Always remove all unused selection tabs from the job site and discard them at a remote location Improper use of the selection tabs can result in appliance malfunction Fig 2 Separating and installing selection tab Wire the Module CAUTION 1 Check the wiring diagra...

Страница 8: ...s ground c Do not use the S8910U VALVE GND terminal VALVE GND and 24V GND are interconnected in the appliance wiring d Remove quick connect and replace with the included 3 16 in quick connect e Do not use this terminal if model being replaced does not have 120V neutral power supply connection f Use the black wire on the included adapter cable g Use the orange wire on the included adapter cable h O...

Страница 9: ...UICK CONNECT SUPPLIED BURNER GROUND M8528B AUTO IGNITION SYSTEMS ANSI Z21 20 STATUS LED 1 Flash Ignition Lockout 2 Flash Weak Flame Signal 3 Flash Internal Error Replace Control Pulsing Heartbeat Normal Operation S8910U HOT SURFACE IGNITION INPUT VOLTAGES 120 24 VAC 60HZ HSI 120V 6 5A MAX VALVE 24V 1A MAX TOTAL 24V LOAD 0 2 VALVE LOAD 120VAC HOT 570A0056 WARNING Explosion hazard Can cause serious ...

Страница 10: ... GROUND ADAPTER SUPPLIED TO CONNECT S8910U GND BURNER TO APPLIANCE CHASSIS BURNER GROUND M8529B AUTO IGNITION SYSTEMS ANSI Z21 20 STATUS LED 1 Flash Ignition Lockout 2 Flash Weak Flame Signal 3 Flash Internal Error Replace Control Pulsing Heartbeat Normal Operation S8910U HOT SURFACE IGNITION INPUT VOLTAGES 120 24 VAC 60HZ HSI 120V 6 5A MAX VALVE 24V 1A MAX TOTAL 24V LOAD 0 2 VALVE LOAD 120VAC HOT...

Страница 11: ...HSI HSI SENSE STARTUPAND CHECKOUT Check out the gas control system At initial installation of the appliance As part of regular maintenance procedures At maintenance intervals determined by the application As the first step in troubleshooting Any time work is done on the system Maintenance frequency must be determined individually for each application see Maintenance section WARNING FIRE OR EXPLOSI...

Страница 12: ...water solution Bubbles indicate a gas leak Tighten the joints and screws or replace component to stop a gas leak Recheck with soap and water solution e Check the burner flame condition The igniter sensor or sensor must be constantly immersed in flame Check the burner flame condition as shown in Fig 6 Do not relocate the hot surface igniter or flame rod f Turn the thermostat or controller below the...

Страница 13: ...e gas control is closed Fig 7 S8910U normal operating sequence START PREPURGE IGNITER WARMUP CALL FOR HEAT 24V TERMINAL POWERED INTERNAL SAFE START CHECK BEGINS FLAME SIMULATING FAILURE SYSTEM WILL NOT START PREPURGE IGNITER WARMS UP BETWEEN TRIAL PURGE TRIAL FOR IGNITION GAS CONTROL OPENS FOR TIMED TRIAL FOR IGNITION LOCKOUT OCCURS SYSTEM MUST BE RESET GAS CONTROL CLOSES NO FLAME IGNITER OFF FLAM...

Страница 14: ... initiates a between trial purge warmup and trial for ignition After the third trial during a single call for heat the module locks out The module must be manually reset following the lockout MAINTENANCE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not attempt to take apart the module or to clean it Improper assembly and cleaning can cause unreliable operati...

Страница 15: ...nections to the ignition module and to the igniter or igniter sensor are clean and tight c Ignition cable provides good electrical continuity Step 2 Check the ignition system grounding Nuisance shutdowns are often caused by a poor or erratic ground a A common ground is required for the module igniter flame sensor and main burner Check for good metal to metal contact between the igniter bracket and...

Страница 16: ...CE S8910U MODULE NOTE SYSTEM FAILURE DURING A RUN CYCLE HAS A LOW PROBABILITY OF BEING THE S8910U MAIN BURNER REMAINS POWERED AND LIT MAIN BURNER LIGHTS CHECK FOR 120 VAC ACROSS HOT SURFACE IGNITER TERMINALS NOTE IF S8910U GOES INTO LOCKOUT RESET SYSTEM CHECK CONTINUITY OF GROUND WIRE AND GROUND PATH FROM MAIN BURNER TO GND BURNER TERMINAL OF S8910U CONFIRM THAT 120 VAC HOT LEAD IS CONNECTED TO L1...

Отзывы: