Function Parameter Index Reference
8/99
RS232 Communications Reference Manual
91
BCO
15
REAL
O
R
Back Calculation Out (%)
ATI
16
BOOL
O
R
Auto Tune Indicator. ON = Auto Tune in
progress
PVI
17
REAL
I
R
Process Variable Input (eu) (pv_lo <= PV <=
pv_hi)
RSP
18
REAL
I
R
Remote Set Point (% or eu per sp_units)
FFV
19
REAL
I
R
Feed Forward Value (%)
TRV
20
REAL
I
R
Output Track Value (%)
TRC
21
BOOL
I
R
Output Track Command {OFF, ON}
BCI
23
REAL
I
R
Back Calculation Input (%)
BIAS
24
REAL
I
R
Remote bias value for ratio PID
Static Configuration Parameters:
Table 5-60 PID Static Configuration Parameters
Parameter
Index
Type
Description
GAIN
0
REAL
proportional gain, 0.1 to 1000 or proportional band, 0.1% to
1000% [Tune Set 1]
RATE
1
REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 1]
RESET
2
REAL
integration time, 0 or 0.02 to 50 (minutes) or repeats per minute, 0
or 0.02 to 50 (repeats) [Tune Set 1]
pv_hi
4
REAL
pv High Range value –99999 to 99999 (default 100)
pv_lo
5
REAL
pv Low Range value –99999 to 99999 (default 0)
sp_hi_lim
11
REAL
set point high limit, -99999 to 99999 (default 100)
sp_lo_lim
12
REAL
set point low limit, -99999 to 99999 (default 0)
outhilim
14
REAL
output high limit, -5 to 105
outlolim
15
REAL
output low limit, -5 to 105
failsafe
16
REAL
failsafe output value, -5 to 105, (default 0)
al_sp[4]
17-20
REAL
alarm set points al1spl, al1sp2, al2spl, al2sp2, -99999 to 99999
(default 0)
al_hyst
25
REAL
alarm hysterysis 0 to 5 (%)
man_reset
26
REAL
Manual Reset, -100 to 100 (in % output) (default 0) [used for both
tune sets]
FUZZY
28
BOOL
ON enables fuzzy logic overshoot suppression (default OFF)
TUNESET2
29
BOOL
Use tune set 2 (default OFF)
GAIN2
30
REAL
proportional gain, 0.1 to 1000 or proportional band, 0.1% to
1000% [Tune Set 2]
RATE2
31
REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 2]
Содержание RS-232
Страница 12: ...Overview 2 RS232 Communications Reference Manual 8 99 ...
Страница 24: ...Protocol Description 14 RS232 Communications Reference Manual 8 99 ...
Страница 36: ...PC Communication Driver 26 RS232 Communications Reference Manual 8 99 ...
Страница 121: ...Function Parameter Index Reference 8 99 RS232 Communications Reference Manual 111 Static Configuration Parameters None ...
Страница 143: ...Function Parameter Index Reference 8 99 RS232 Communications Reference Manual 133 ...
Страница 150: ...Index 140 RS232 Communications Reference Manual 8 99 ...
Страница 151: ......
Страница 152: ...Industrial Automation and Control Honeywell Inc 1100 Virginia Drive Fort Washington Pennsylvania 19034 ...