Function Parameter Index Reference
86
RS232 Communications Reference Manual
8/99
Static Configuration Parameters:
Table 5-55 ON/OFF Static Configuration Parameters
Parameter
Index
Type
Description
pv_hi
0
REAL
pv High Range value –99999 to 99999 (default 100)
pv_lo
1
REAL
pv Low Range value –99999 to 99999 (default 0)
sp_hi_lim
6
REAL
set point high limit, -99999 to 99999 (default 100)
sp_lo_lim
7
REAL
set point low limit, -99999 to 99999 (default 0)
sp_rate_dn
9
REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
sp_rate_up
10
REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
devbar_hi
11
REAL
High scale value for deviation bar graph (0 to 99999) (default
100)
devbar_low
12
REAL
Low scale value for deviation bar graph [always = -devbar_hi]
Output
Hysteresis
13
REAL
Off – 0 to 10% of Input Span
al_sp[4]
14-17
REAL
alarm set points al1sp1, al1sp2, al2sp1, al2sp2, -99999 to 99999
(default 0)
al_hyst
22
REAL
alarm hysterysis 0 to 5 (%)
Fail Safe Out
23
BOOL
Fail Safe Out = On/Off
Содержание RS-232
Страница 12: ...Overview 2 RS232 Communications Reference Manual 8 99 ...
Страница 24: ...Protocol Description 14 RS232 Communications Reference Manual 8 99 ...
Страница 36: ...PC Communication Driver 26 RS232 Communications Reference Manual 8 99 ...
Страница 121: ...Function Parameter Index Reference 8 99 RS232 Communications Reference Manual 111 Static Configuration Parameters None ...
Страница 143: ...Function Parameter Index Reference 8 99 RS232 Communications Reference Manual 133 ...
Страница 150: ...Index 140 RS232 Communications Reference Manual 8 99 ...
Страница 151: ......
Страница 152: ...Industrial Automation and Control Honeywell Inc 1100 Virginia Drive Fort Washington Pennsylvania 19034 ...