EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
5
66-1092—2
Fig. 3. Wiring subbase and sequence chart for EC/RM7830A.
L1
N
1
G
12
N
13
3
14
4
15
5
16
6
17
7
18
8
19
(L1)
9
20
10
21
F
22
AL
FAN
RT
LD2
PV1
MV
IGN
ES2
LOS
PV2
FLAME
DETECTOR
1
12O VAC, 50/60 Hz POWER SUPPLY (RM7830A). 220-240 VAC, 50/60 Hz POWER SUPPLY
(EC7830A). PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
SEE FLAME DETECTOR INSTRUCTIONS FOR CORRECT WIRING.
LEGEND
ALARM
(NORMALLY OPEN)
PREIGNITION
INTERLOCK INPUT
BURNER/BLOWER
MOTOR
IGNITION
LINE VOLTAGE SUPPLY
LOCKOUT INPUT
AIRFLOW SWITCH INPUT
MAIN FUEL VALVE
PILOT VALVE 1
(INTERRUPTED)
PILOT VALVE 2
(INTERMITTENT)
LIMITS AND BURNER
CONTROL
AL
ES2
FAN
IGN
L1
LOS
LD2
MV
PV1
Q7800
2
2
INITIATE
POWER
PILOT
FLAME
MAIN
ALARM
STANDBY
RUN
STANDBY
PRE
IGNITION
PILOT
STABIL.
MAIN
STABIL.
IGNITION
BURNER
POSTPURGE
MAIN VALVE
LIMITS AND BURNER CONTROL CLOSED
LOCKOUT INPUT
10 sec
AIRFLOW SWITCH CHECK
PILOT VALVE
V2
PREIGNITION INTERLOCK
OPTIONS
SAFE START CHECK
FLAME PROVING
3 sec
5 sec
5 sec
1
IF ON AT CALL FOR HEAT, HOLD (120 sec). LOCK OUT IF STILL ON.
3 or 5 sec
3 or 5 sec
,,
,,
SAFE START CHECK
IF OFF AFTER 10 SEC OF FAN, LOCK OUT.
2
2, 15 or 30 sec
3
4
5
TAKE LOCKOUT ACTION, CONTINUE POSTPURGE TIMING.
SELECT VIA ST7800A PURGE TIMER CARD.
4
5
6
SELECT VIA CONFIGURATION JUMPERS OR MODEL NUMBERS.
AFS CHK
1
2 sec
AFS CHK
AFS CHK
DUE TO ONE EXTRA SECOND FOR SAFETY RELAY TEST, TIMING CAN VARY FROM 3 TO 4 SECONDS.
6
LED
DISPLAY
"PREPURGE"
WAITING
FIRST SAFETY
TIME
MAIN TRIAL
TIME
OPERATING
CONTROLS
AND
INTERLOCKS
FLAME
SIGNAL
EC/RM7830A Power Burner ON/OFF, GAS or OIL Sequence
2
3
6
6
M15185B
PV2
RT
8
21
9
6
20
7
10
17
BURNER/BLOWER MOTOR
4