EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
15
66-1092—2
HONEYWELL
DUST
COVER
PURGE
TIMER
WIRING
SUBBASE
CAPTIVE
MOUNTING
SCREW
RUN/TEST
SWITCH
CONFIGURATION
JUMPERS
RELAY
MODULE
SEQUENCE
STATUS
LED PANEL
RESET
BUTTON
FLAME
AMPLIFIER
BURNER CONTROL
M15187A
Fig. 5. EC/RM7830A and EC/RM7850A Relay Modules exploded view.
4. Main Trial (MAIN TRIAL):
a.
The MAIN TRIAL time is selectable as three or
five seconds. After PILOT STAB., and with the
presence of a flame, the main fuel valve, terminal
9, is powered. If a flameout occurs, the relay
module locks out within one or two seconds,
depending on the amplifier Flame Failure
Response Time (FFRT). Thus, the second safety
time is defined as MAIN TRIAL time plus the
amplifier FFRT.
b.
During MAIN TRIAL, the Low Fire Switch Input
must be closed (EC/RM7850A). If it opens, a
safety shutdown occurs.
c.
After three or five seconds of MAIN TRIAL,
terminal 8 is de-energized for main stabilization.
Flame must remain proven during this five-
second period.
Run
1. The firing rate motor releases to modulation.
2. The relay module is now in RUN and remains in RUN
until the controller input, terminal 6, opens, indicating
that the demand is satisfied or a limit has opened.
Postpurge
The relay module (model specific) provides a two-, 15- or 30-
second POSTPURGE following the completion of the RUN
period. The blower motor output is powered to drive all
combustion products and any unburned fuel from the
combustion chamber. It also supplies combustion air to burn
fuel being purged from the fuel line downstream from the fuel
shutoff valve.
1. The main fuel valve and the intermittent pilot valve,
terminals 9 and 21, are de-energized and the firing rate
motor is commanded to the low fire position
(EC/RM7850A) to begin the POSTPURGE period.
2. The Preignition Interlock Input is ignored during
POSTPURGE.
3. After the POSTPURGE period is completed, the relay
module re-enters STANDBY.
Run/Test Switch
The Run/Test Switch is located on the top side of the relay
module, see Fig. 5. The Run/Test Switch allows the burner
sequence to be altered as follows:
1. In Purge Drive to High Fire position, the Run/Test
Switch, when placed in the TEST position, holds in
PURGE with the firing rate motor in the High Fire
position (EC/RM7850A).