Q7055C BUILDING NETWORK ADAPTERS BNA-1C/2CS

5

95-7735

CONNECTIONS

This section describes how to connect power and the field bus 
to the BNA device. A supply pack with installation material 
containing the required connectors for power and the field bus 
are shipped with the device.

Power Connection

The BNA device requires a UL 864 listed external power 
supply with the following specifications: 24 VAC, 50 to 60 Hz, 
or 24 VDC.

Typical power supplies include:
DC Power Supply: 50017367-001 Jameco

®

 Model No. 

DDU240050, 120 VAC, 60 Hz 15 VA input, 24 VDC, 0.500 
Amp output, wall mounted power cube Class 2 (included).

AC Power Supply: 120 VAC/50 to 60 Hz input, 24 VAC output, 

14507287 series.

Power consumption of the BNA device is 8 VA. 

For the power connection, the 3-pole Phoenix connector is 
required (included).

Wire the power cable as follows:

1.

Cut off the original connector at the end of the cable. In 
case of a DIN connector equipped power cable, identify 
the 24 VDC cable pair using a multimeter. If the power 
supply has screw terminals, wire a cable to the 24 V and 
GND terminals on the power supply.

2.

Strip the two power cable ends and insert each cable 
end into the openings of the 3-pole Phoenix connectors 
that are marked for power.

3.

Fasten them with a screwdriver.

4.

Connect a chassis ground 

to the third position on 

this connector as marked.

NOTE:

The polarity (+/-) of the 3-pole Phoenix power con-
nector for DC power supplies is 

don't care.

Field Bus Connection (Ch1/Ch2)

For connecting the field bus, the 2-pole or 3-pole Phoenix 
connectors (included) are required. Field bus connection can 
be configured only as class B/style 4. All field wiring is 
supervised. 

Consult form no. 74-4047, Q7055C Building Network Adapter 
BNA-1C/2CS Checkout & Test for additional information on 
field bus wiring.

CABLES AND CONNECTORS

DB9F Null Modem Connector

Fig. 6 illustrates a serial connector for the field bus. Fig. 7 
shows how to configure a Null Modem Cable DB9F.

Fig. 6. Serial connector (female connector is numbered as 

shown).

Fig. 7. Signal connections for DB9F Null Modem Cable.

9 = RI

5 = GROUND

8 = CTS

7 = RTS

6 = DSR

M19592

2 = RxD

3 = TxD

4 = DTR

1 = DCD

DCD

DSR

GND

RTS 

CTS

DTR 

RxD 

2

3

4

1

6

5

7

8

2

3

6

1

4

5

7

8

TxD

RI 

DCD

DTR

GND

RTS 

CTS

DSR 

RxD 

TxD

RI 

M19594

9

9

Содержание Q7055C Series

Страница 1: ...n to provide a seamless communication to the requesting device Status information such as LAN communication activity field bus traffic communication and system Heartbeat of the BNA is indicated by LEDs on the front of the device The BNA models provide an interface from various Honeywell controller buses that use RS 485 signals to a local area network using 802 3 Ethernet protocol This allows data ...

Страница 2: ... product has been received without dam age 2 Verify that the correct BNA device has been delivered 3 Check the package contents The following items are included in each product package Building Network Adapter device 50017367 001 Power Supply Building Network Adapter Installation Instructions Bag of installation materials as follows one 3 pole Phoenix power connector one or two Phoenix con troller...

Страница 3: ...x Tx 100 Boot NML M25115 Place the BNA adapter with the topside down on the desk Remove the four feet from the bottom of the BNA by pushing horizontally away from the housing with a flat screwdriver Push the four inserts included fully and horizontally into the housing Adjust the four retaining clips included on top of the inserts Fasten the retaining clips with the included four screws Use the ho...

Страница 4: ...ICLE 760 ALL POWER LIMITED WIRING MUST BE SEPARATED FROM ALL NON POWER LIMITED WIRING BY A MINIMUM DISTANCE OF 1 4 IN 6 MM NOTE TYPICAL MOUNTING LOCATION FOR Q7055 BUILDING NETWORK ADAPTER BNA 1 G GROUNDING CONDUCTOR 2 GROUND CONNECTION 8 32 STUD WITH 8 32 KEPS NUT 3 GROUND CONNECTION FOR 14507678 SERIES ETHERNET PROTECTOR AND OTHER LOW VOLTAGE EQUIPMENT 4 DRILLED MOUNTING HOLES FOR 14507719 001 8...

Страница 5: ...crew terminals wire a cable to the 24 V and GND terminals on the power supply 2 Strip the two power cable ends and insert each cable end into the openings of the 3 pole Phoenix connectors that are marked for power 3 Fasten them with a screwdriver 4 Connect a chassis ground to the third position on this connector as marked NOTE The polarity of the 3 pole Phoenix power con nector for DC power suppli...

Страница 6: ...ct a BNA device to a LAN via an Ethernet Hub the required cable should be configured as shown in Fig 9 Fig 9 Straight through pinning for BNA to EthernetHub connections Connect BNA to Workstation When a BNA needs a direct connection to a workstation without using an Ethernet Hub a crossover cable is required Fig 10 shows how the different signals should be connected Fig 10 Crossover pinning for BN...

Страница 7: ...atus using three LEDs 10LNK Ethernet speed of 10 mbps indicator Green If this LED is lit then the Ethernet link is operating at 10 mbps 100LNK Ethernet speed of 100 mbps indicator Green If this LED is lit then the Ethernet link is operating at 100 mbps Activity Link activity indicator Green will blink if there is any activity transmission reception on the LAN Fig 12 Parts and controls on rear side...

Страница 8: ...ures and practices contained in applicable NFPA and UL standards The Q7055C BNA has no user replaceable fuses For service contact your local Honeywell Automation Control Solutions office as listed in the phone book or contact a regional office as shown at the end of this document Jameco IS A REGISTERED TRADEMARK OF ARNDT ELECTRONICS ELPAC IS A REGISTERED TRADEMARK OF JSR CORPORATION HONEYWELL EXCE...

Страница 9: ...Q7055C BUILDING NETWORK ADAPTERS BNA 1C 2CS 9 95 7735 ...

Страница 10: ...Honeywell Pacific Level 3 2 Richardson Place North Ryde NSW 2113 In North America Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 In Asia Zhang Jiang Hi Tech Park No 430 Li Bing Rd Pudong New Area Shangai 201203 China In Europe Middle East Africa India Hermes Plaza Hermeslaan 1H B 1831 Diegem Belgium www honeywell com buildingsolutions ...

Отзывы: