Honeywell Q348A Скачать руководство пользователя страница 4

Home and Building Control

Home and Building Control

Helping You Control Your World

Honeywell Inc.

Honeywell Limited—Honeywell Limitée

1985 Douglas Drive North

740 Ellesmere Road

Golden Valley, Minnesota  55422

Scarborough, Ontario
M1P 2V9

Printed in U.S.A.

QUALITY IS KEY

Fig. 7—Example of unsatisfactory pilot flames.

CHECK IGNITION CABLE

1. Assure that ignition cable is not in contact with

metal surfaces.

2. Assure that ignition cable is not more than

3 feet [1 m] long.

3. Assure connections to the ignition module stud

terminal and the igniter-sensor are clean and tight.

4. Check electrical continuity of ignition cable.

CHECK GROUNDING

1. If ground is poor or erratic, safety shutdown will

occur. Therefore, if nuisance shutdowns are reported,
check the ground precautions in Wire Igniter-Sensor
section.

2. If leadwire is damaged or deteriorated, use

no. 14 to 18 gauge, moisture-resistant, thermoplastic,
insulated wire with 221

°

 F [105

°

 C] minimum rating as

replacement.

3. Excessive temperature at the ceramic flame rod

insulator will permit electrical leakage to ground.

a. If bracket is bent, bend it back to correct

position.

b. If insulator is cracked, replace pilot burner/

igniter-sensor.

TEST SAFETY LOCKOUT

Refer to appliance manufacturer instructions to test

for proper safety lockout times.

LAZY YELLOW FLAME

WAVING BLUE FLAME

NOISY LIFTING BLOWING FLAME

HARD SHARP FLAME

SMALL BLUE FLAME

CHECK FOR LACK OF GAS FROM:

• CLOGGED ORIFICE FILTER

• CLOGGED PILOT FILTER

• LOW GAS SUPPLY PRESSURE

• PILOT ADJUSTMENT AT MINIMUM

CHECK FOR LACK OF AIR FROM:

• DIRTY ORIFICE

• DIRTY LINT SCREEN, IF USED

• DIRTY PRIMARY AIR OPENING,
  IF THERE IS ONE

• PILOT ADJUSTMENT AT MINIMUM

CHECK FOR:

• EXCESSIVE DRAFT AT PILOT 
  LOCATION

• RECIRCULATING PRODUCTS
  OF COMBUSTION

CHECK FOR:

• HIGH GAS PRESSURE

THIS FLAME IS CHARACTERISTIC 
OF MANUFACTURED GAS

CHECK FOR:

• HIGH GAS PRESSURE

• ORIFICE TOO SMALL

M3778

APPEARANCE

CAUSE

NOISY LIFTING BLOWING FLAME

LAZY YELLOW FLAME

WAVING BLUE FLAME

HARD SHARP FLAME

SMALL BLUE FLAME

APPEARANCE

Содержание Q348A

Страница 1: ...low appliance manufacturer instructions if avail able otherwise use instructions provided below LOCATION 1 Position pilot burner igniter sensor for easy access and observation In replacement applications replace pilot burner igniter sensor with an identical unit and position new pilot burner igniter sensor in the same location and orientation as the original one Fig 1 Mount pilot burner igniter se...

Страница 2: ...essary to prevent cable from contacting metal surfaces INSTALL BLEED GAS TUBE optional 1 Route bleed tube from bleed tap on gas control to the pilot burner igniter sensor 2 Push clip into place See Fig 4 3 Insert bleed gas tube until 3 8 in 10 mm to tubing is above pilot burner igniter sensor bracket Tip of bleed gas tube must not extend into pilot flame Fig 3 Always use new compression fitting PI...

Страница 3: ...nition sequence as follows Reconnect main valve wire Set thermostat to call for heat Watch ignition sequence at burner If spark still does not stop after pilot lights replace ignition module If main burner does not light or if main burner lights but system locks out check module ground wire and gas control as described in control module instructions 3 8 TO 1 2 INCH 10 TO 13 mm PROPER FLAME ADJUSTM...

Страница 4: ...astic insulated wire with 221 F 105 C minimum rating as replacement 3 Excessive temperature at the ceramic flame rod insulator will permit electrical leakage to ground a If bracket is bent bend it back to correct position b If insulator is cracked replace pilot burner igniter sensor TEST SAFETY LOCKOUT Refer to appliance manufacturer instructions to test for proper safety lockout times LAZY YELLOW...

Отзывы: