3

60-0653—8

Fig. 5—Igniter-sensor tip must be in pilot flame.

Fig. 6—Proper shielding of pilot flame.

M1273

TYPICAL
SHIELD

J

Set the thermostat to call for heat.

J

Watch the pilot burner during the ignition sequence.

See if:

• Ignition spark continues after the pilot is lit.
• The pilot lights and the spark stops, but main

burner does not light.

• S8600B,H; S86H only: The pilot lights, the spark

stops and main burner lights, but the system locks
out.

J

If so, assure adequate flame current as follows:
• Turn off furnace at circuit breaker or fuse box.
• Clean the flame rod with emery cloth.
• Make sure electrical connections are clean and tight.

Replace damaged wire with moisture-resistant
no. 18 wire rated for  continuous duty up to
221

°

 F [105

°

 C].

• Check for cracked ceramic insulator, which can

cause  short to ground, and replace pilot burner/
igniter-sensor if necessary.

• At the gas control, disconnect main valve wire

from the TH or MV terminal.

• Turn on power and set thermostat to call for heat.

The pilot should light but the main burner will
remain off because the main valve actuator is dis-
connected.

• Check the pilot flame. Make sure it is blue, steady

and envelops 3/8 to 1/2 in. [10 to 13 mm] of the
flame rod. See Fig. 7 for possible flame problems
and their causes.

• If necessary, adjust pilot flame by turning the pilot

adjustment screw on the gas control clockwise to
decrease or counterclockwise to increase pilot
flame. After adjustment, always replace pilot
adjustment cover screw and tighten firmly to
assure proper gas control operation.

• Set thermostat below room temperature to end call

for heat.

J

Recheck ignition sequence as follows:
• Reconnect main valve wire.
• Set thermostat to call for heat.
• Watch ignition sequence at burner.
• If spark still does not stop after pilot lights, replace

ignition module.

• If main burner does not light or if main burner

lights but system locks out, check module, ground
wire, and gas control as described in control
module instructions.

3/8 TO 1/2 INCH
[10 TO 13 mm]

PROPER FLAME
ADJUSTMENT

IGNITER-SENSOR

3/8 TO 1/2 INCH
[10 TO 13 mm]

PROPER FLAME
ADJUSTMENT

IGNITER-SENSOR

M3777

Q373A

Q345A, Q348A-B, Q362A AND Q 381A

ADJUST PILOT FLAME

The pilot flame should envelop 3/8 to 1/2 in.

[10 to 13 mm] of the igniter-sensor tip. See Fig. 5. To
adjust pilot flame:

1. Turn off system by setting thermostat below

temperature to call for heat.

2. Disconnect lead to MV terminal on gas control.
3. Light pilot by setting thermostat to call for heat.
4. Remove pilot adjustment cover screw from gas

control.

5. Turn inner pilot adjustment screw clockwise to

decrease or counterclockwise  to increase pilot flame.

6. Always replace pilot adjustment cover screw and

tighten firmly after completing adjustment to assure
pro-per operation.

Service

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Perform Gas Leak Test anytime work is done to
the system.

PILOT OUTAGE

1. If pilot flame goes out during ignition, but is

pro-perly adjusted, recheck mounting and location
instructions in Location section.

2. Refer to ignition module instructions to check

wiring between igniter-sensor and ignition module or
between gas control and ignition module.

3. If all mounting and location instructions are fol-

lowed but pilot continues to go out, construct shielding
to protect pilot flame from main burner ignition and
extinction and drafts. See Fig. 6.

4. Check pilot and main burner lightoff.

Содержание Q348A

Страница 1: ...low appliance manufacturer instructions if avail able otherwise use instructions provided below LOCATION 1 Position pilot burner igniter sensor for easy access and observation In replacement applications replace pilot burner igniter sensor with an identical unit and position new pilot burner igniter sensor in the same location and orientation as the original one Fig 1 Mount pilot burner igniter se...

Страница 2: ...essary to prevent cable from contacting metal surfaces INSTALL BLEED GAS TUBE optional 1 Route bleed tube from bleed tap on gas control to the pilot burner igniter sensor 2 Push clip into place See Fig 4 3 Insert bleed gas tube until 3 8 in 10 mm to tubing is above pilot burner igniter sensor bracket Tip of bleed gas tube must not extend into pilot flame Fig 3 Always use new compression fitting PI...

Страница 3: ...nition sequence as follows Reconnect main valve wire Set thermostat to call for heat Watch ignition sequence at burner If spark still does not stop after pilot lights replace ignition module If main burner does not light or if main burner lights but system locks out check module ground wire and gas control as described in control module instructions 3 8 TO 1 2 INCH 10 TO 13 mm PROPER FLAME ADJUSTM...

Страница 4: ...astic insulated wire with 221 F 105 C minimum rating as replacement 3 Excessive temperature at the ceramic flame rod insulator will permit electrical leakage to ground a If bracket is bent bend it back to correct position b If insulator is cracked replace pilot burner igniter sensor TEST SAFETY LOCKOUT Refer to appliance manufacturer instructions to test for proper safety lockout times LAZY YELLOW...

Отзывы: