Startup and Checkout

PERFORM GAS LEAK TEST

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Check for gas leaks with soap and water  solu-
tion any time work is done on a gas system.

Gas Leak Test:

1. Ensure that gas supply is turned on at the appliance

service valve.

2. Paint pipe connections upstream of pilot burner

with rich soap and water solution. Bubbles indicate gas
leak.

3. If leak is detected, tighten pipe connections.
4. Set thermostat to call for heat to light main burner.
5. With main burner in operation, paint pipe joints

(including adapters) and gas control inlet and outlet with
rich soap and water solution.

6. If another leak is detected, tighten adapter screws,

joints, and pipe connections.

7. Replace part if leak cannot be stopped.

2

CONNECT PILOT GAS TUBING

1. Cut tubing to desired length and bend as necessary

for routing to pilot burner/igniter-sensor. Do not make
sharp bends or deform tubing. Do not bend tubing at
control after compression nut has been tightened
because this can result in gas leakage at connection.

2. Square off and remove burrs from end of tubing.
3. Push tubing into compression nut clearance hole

until tubing bottoms.

NOTE:  When replacing a control, cut off old

compression fitting and replace with new
compression fitting provided with new pilot
burner. Never use old compression fitting because it
may not provide a gas-tight seal. See Fig. 3.

2. Connect one end of the ignition cable to stud

terminal on igniter-sensor using 1/4 in. [6 mm] diam-
eter snap-spring or cage-clips on cable ends.

3. Connect the other end of the ignition cable to the

igniter terminal on ignition module.

4. Use ceramic or plastic standoff insulators as nec-

essary to prevent cable from contacting metal surfaces.

INSTALL BLEED GAS TUBE (optional)

1. Route bleed tube from bleed tap on gas control to

the pilot burner/igniter-sensor.

2. Push clip into place. See Fig. 4.
3. Insert bleed gas tube until 3/8 in. [10 mm] to

tubing is above pilot burner/igniter-sensor bracket. Tip
of bleed gas tube must not extend into pilot flame.

Fig. 3—Always use new compression fitting.

PILOT BURNER BODY 
ON BRACKET OF PILOT 
BURNER/IGNITER-SENSOR

TIGHTEN NUT ONE TURN 
BEYOND FINGER TIGHT

COMPRESSION FITTING 
BREAKS OFF AND CLINCHES 
TUBING AS NUT IS TIGHTENED

TO GAS CONTROL

M3296

4. While holding tubing all the way in, engage threads

and turn until finger tight.

5. Using a wrench, turn compression nut one turn

beyond finger tight. Do not overtighten.

6. Connect other end of tubing to gas control

according to gas control manufacturer instructions.

WIRE IGNITER-SENSOR

The igniter-sensor must be mounted on the burner.

Connect the control module ground wire to one of the
igniter-sensor mounting screws to complete the system
grounding.

Connect ground wire as follows:
1. Use 221

°

  F [105

°

  C] minimum thermoplastic-

insulated wire for the ground leadwire (asbestos
insulation is not acceptable).

2. A male 1/4 in. [6 mm] quick-connect terminal is

provided on Honeywell ignition modules. Fasten female
quick-connect to wire end at ignition module.

3. Strip other end and fasten under igniter-sensor

mounting screw.

4. If necessary, use shield to protect lead from radi-

ant heat of burner.

5. The pilot burner serves as the grounding area for

the flame signal. Run lead from pilot burner to the
common ground selected.

Connect the ignition cable as follows:
1. The high tension ignition cable must conform to

applicable local or national standards.

Fig. 4—Install bleed gas tube.

THIS DIMENSION SHOULD 
BE MAXIMUM OF 3/8 INCH 
[9.5 mm] WHEN BLEED 
TUBE IS IN FINAL 
POSITION.

BLEED TUBE CLIP

M1261

1/8 IN. STEEL TUBING

Содержание Q348A

Страница 1: ...low appliance manufacturer instructions if avail able otherwise use instructions provided below LOCATION 1 Position pilot burner igniter sensor for easy access and observation In replacement applications replace pilot burner igniter sensor with an identical unit and position new pilot burner igniter sensor in the same location and orientation as the original one Fig 1 Mount pilot burner igniter se...

Страница 2: ...essary to prevent cable from contacting metal surfaces INSTALL BLEED GAS TUBE optional 1 Route bleed tube from bleed tap on gas control to the pilot burner igniter sensor 2 Push clip into place See Fig 4 3 Insert bleed gas tube until 3 8 in 10 mm to tubing is above pilot burner igniter sensor bracket Tip of bleed gas tube must not extend into pilot flame Fig 3 Always use new compression fitting PI...

Страница 3: ...nition sequence as follows Reconnect main valve wire Set thermostat to call for heat Watch ignition sequence at burner If spark still does not stop after pilot lights replace ignition module If main burner does not light or if main burner lights but system locks out check module ground wire and gas control as described in control module instructions 3 8 TO 1 2 INCH 10 TO 13 mm PROPER FLAME ADJUSTM...

Страница 4: ...astic insulated wire with 221 F 105 C minimum rating as replacement 3 Excessive temperature at the ceramic flame rod insulator will permit electrical leakage to ground a If bracket is bent bend it back to correct position b If insulator is cracked replace pilot burner igniter sensor TEST SAFETY LOCKOUT Refer to appliance manufacturer instructions to test for proper safety lockout times LAZY YELLOW...

Отзывы: