PW6K1R1E Wiring and Setup

Specifications

After the PW6K1R1E has received its IP address, the following table describes the 
LEDs in the normal running mode. If the communication is lost, the PW6K1R1E 
reverts back to the “waiting for IP address” mode:

2.11  Specifications

The interface must be used in low voltage, class 2 circuits only. 
The installation of this device must comply with all local fire and electrical codes. 

5

Input IN2 Status: OFF = Inactive, ON = Active, Flashing = Trouble

6

Input IN3 Status: OFF = Inactive, ON = Active, Flashing = Trouble

LED

DESCRIPTION

1

On-line, encryption disabled = 0.8 second ON, 0.2 second OFF

On-line, encryption enabled = four pulses, 0.1 second ON, 0.1 second OFF per 
second 

2

Flashes when there is host communication

3

Flashes when data is received from either reader

4

Input IN1 Status: OFF = Inactive, ON = Active, Flashing = Trouble

5

Input IN2 Status: OFF = Inactive, ON = Active, Flashing = Trouble

6

Input IN3 Status: OFF = Inactive, ON = Active, Flashing = Trouble

Power Input

• PoE Power Input 12.95W, compliant to IEEE 802.3af 

     - OR -

•12VDC 10%, 900mA maximum

Notes:

 

• A +12V power input must be powered by a UL 294/UL 609 Listed power 

supply with appropriate ratings (12Vdc, 900mA) and the capability to 
provide adequate standby power.

• If the PW6K1ICE is powered by Power-Over_Ethernet (POE), it must be 

powered by a Listed (ALVY) Altronix, Model NetWay1 POE Injector. 
NetWay1 must be powered by a UL 294/UL 609 Listed power supply with 
appropriate ratings (24Vac/dc, 1.2A) that is capable of providing adequate 
standby power.

Power Output • 12VDC @ 700mA maximum (reader and AUX outputs combined) 

• Reader (TB3) 12 VDC (10.3 through 12.6) @ 150mA maximum
• AUX (TB5) 12 VDC (10.7 through 13.0) @ 700 mA maximum

Output

• Form-C Contacts rated at 5A @ 28VDC

Inputs

• 4 unsupervised/supervised, End of Line resistors
• 1k/1k - ohm, 1% 1/4W watt standard

Содержание PW6K1R1E

Страница 1: ...September 2011 2011 Honeywell All rights reserved 800 07986V1 Revision A PW6K1R1E Input Output Module Installation and Configuration Guide ...

Страница 2: ...the right to change any information in this document at any time without prior notice Microsoft and Windows are registered trademarks of Microsoft Corporation Windows Server is a trademark of Microsoft Corporation Ordering Information Please contact your local Honeywell Integrated Security representative or visit us on the web at www honeywellintegrated com for information about ordering Feedback ...

Страница 3: ...y 4 1 5 Liability 4 1 6 FCC Compliance 4 Chapter 2 PW6K1R1E Wiring and Setup 2 1 PW6K1R1E Hardware 6 2 2 Terminal Connections 7 2 3 Jumper Configuration 8 2 4 DIP Switch Configuration 8 2 5 Input Power 8 2 6 Communication Wiring 9 2 7 Reader Wiring 9 2 8 Input Circuit Wiring 10 2 9 Relay Circuit Wiring 10 2 10 Status LEDs 11 2 11 Specifications 12 2 12 Additional Mounting Information 15 ...

Страница 4: ...iv www honeywell com ...

Страница 5: ...PW6K1R1E Configuration and Installation Guide Document 800 07986V1 Revision A 1 1 Introduction In this chapter 1 1 Overview 2 1 4 Warranty 4 1 5 Liability 4 1 6 FCC Compliance 4 ...

Страница 6: ...inputs are provided for monitoring the door contacts exit push buttons and alarm contacts The PW6K1R1E requires power from PoE or local 12VDC The reader power should be based on peak reader power consumption The PW6K1R1E may be mounted in a 3 gang switch box a mounting plate is supplied with the unit The PW6K1R1E may be mounted in an enclosure the supplied mounting plate has mounting holes that ma...

Страница 7: ...been tested for use with the following Listed ALVY card readers Manufacturer Model Part Number HID ProxPro HU 5355AGN00 ProxPro II HU 5455BGN00 ProxPro K HU 5355AGK00 MiniProx HU 5365EGP00 ThinLine II HU5395CB100 HU 5395CG100 HU 5395CK100 Honeywell OM40 OM40BHONC OM40GHONC OM41 OM41BHONC OM41GHONC OM55 OM55BHONB OM55GHONB OP 10 OP10GENR OP10HONR OP 30 OP30GENR OP30HONR OP 40 OP40GENR OP40HONR ...

Страница 8: ... units are repaired or replaced from a stock of reconditioned units Returns must be accompanied by a Returned Merchandise Authorization RMA number obtained from customer service and prepaid postage and insurance 1 5 Liability You should use the Interface only to control exits from areas where an alternative method for exit is available This product is not intended for nor is rated for operation in...

Страница 9: ...hapter 2 1 PW6K1R1E Hardware 6 2 2 Terminal Connections 7 2 3 Jumper Configuration 8 2 4 DIP Switch Configuration 8 2 5 Input Power 8 2 6 Communication Wiring 9 2 7 Reader Wiring 9 2 8 Input Circuit Wiring 10 2 9 Relay Circuit Wiring 10 2 10 Status LEDs 11 2 11 Specifications 12 2 12 Additional Mounting Information 15 ...

Страница 10: ...ND VO GND DAT CLK BZR LED GND VIN NO NC 2 C NO NC 1 C J2 0 2 5 08 2 35 59 69 0 15 3 81 2 55 64 77 2 55 64 77 5 4 137 16 STATUS LEDs 2 75 69 85 DIP SWITCH RESET SWITCH PoE 12Vdc POWER SELECTOR JUMPER ETHERNET RJ45 CONNECTOR ACTIVITY YELLOW LINK GRREN 1 2 3 4 5 6 VO VO IN2 IN1 IN3 IN4 LED BZR CLK DAT GND LED BZR CLK DAT NC GND GND VIN NO RLY 1 NO RLY 2 NC C C TB6 TB5 TB4 TB3 TB2 TB1 J1 6V 5V 3 3V LN...

Страница 11: ... Output TB3 4 CLK Reader 1 CLK Data 1 TR TB3 5 DAT Reader 1 DAT Data 0 TR TB3 6 GND Reader 1 Ground TB4 1 LED Reader 2 LED Output TB4 2 BZR Reader 2 Buzzer Output TB4 3 CLK Reader 2 CLK Data 1 Input TB4 4 DAT Reader 2 DAT Data 0 Input TB5 1 VO Auxiliary Power Output 12VDC TB5 2 GND Auxiliary Power Output Ground TB5 3 VIN Input Power 12VDC from local power supply TB5 4 GND Input Power Ground TB6 1 ...

Страница 12: ...two ways jumper selected 1 The Ethernet connection using PoE fully compliant to IEEE 802 3af 2 Local 12VDC power supply TB5 3 VIN TB5 4 GND J5 Jumper hidden under TB5 Table 2 Jumper Settings Jumper Set at Description J1 N A Factory Use Only J2 N A Factory Use Only J3 N A Factory Use Only J4 N A Factory Use Only J5 PoE PW6K1R1E powered from the Ethernet connection 12V PW6K1R1E powered from an exter...

Страница 13: ...r is 12VDC and its current is limited to 150mA The second reader may be powered from the auxiliary power output on TB5 1 and TB5 2 Readers that require different voltage or have high current requirements should be powered separately Refer to the manufacturer s specifications for cabling requirements In the 2 wire LED mode the Buzzer output is used to drive the second LED Reader port configuration ...

Страница 14: ... circuit requires 1K Ohm 1 resistors and should be located as close to the sensor as possible Custom end of line EOL resistances may be configured via the host software The input circuit wiring configurations shown below are supported but may not be typical Figure 2 6 Input Circuit Wiring 2 9 Relay Circuit Wiring Two relays are provided for controlling door lock mechanisms or alarm signaling The r...

Страница 15: ... 2 7 Relay Circuit Wiring Diagram Note The initial charge of the battery may take up to 24 hours to be fully charged 2 10 Status LEDs At power up LEDs 2 through 6 are turned ON then OFF in sequence After the above sequence has completed successfully the PW6K1R1E goes to the waiting for IP address mode Diode Selection Diode current rating 1x strike count Diode breakdown voltage 4x strike voltage Fo...

Страница 16: ...4 Input IN1 Status OFF Inactive ON Active Flashing Trouble 5 Input IN2 Status OFF Inactive ON Active Flashing Trouble 6 Input IN3 Status OFF Inactive ON Active Flashing Trouble Power Input PoE Power Input 12 95W compliant to IEEE 802 3af OR 12VDC 10 900mA maximum Notes A 12V power input must be powered by a UL 294 UL 609 Listed power supply with appropriate ratings 12Vdc 900mA and the capability t...

Страница 17: ...m 10mA sink maximum Reader Data Inputs TTL compatible inputs or 2 wire RS 485 RS 485 Mode 9600 bps Asynchronous Half duplex 1 start bit 8 data bits 1 stop bit Maximum cable length 4000 1 200m Cable requirements Communication Ethernet Category 5 minimum Power 18 AWG 1 twisted pair Ethernet CAT 5 minimum RS 485 24AWG 120 ohm impedance 4 000ft 1 219 m maximum Twisted pair s with an overall shield Ala...

Страница 18: ... 3 63 92mm L x 1 33 34mm H with bracket Weight 4 2 oz 120g without bracket 5 3 oz 150g with bracket Enclosure Box type The unit must be installed within a UL 514A UL 514C Listed QCIT or QCMZ 3 gang electrical box Box dimensions The minimum dimensions for the electrical box are 2 75 inches by 2 75 inches by 5 8 inches with a minimum capacity of 44 cubic inches Box spacing Minimum spacings must be e...

Страница 19: ...e optional items shown below 3 gang stainless steel blank cover Leviton part number 84033 40 Available from Graybar part number 88158404 Magnetic switch set G R I part number 505 Figure 2 8 Stainless Steel Blank Cover FIELD WIRING PW 6K1R1E WITH INCLUDED MOUNTING PLATE TO ETHERNET NETWORK OPTIONAL 3 GANG JUNCTION BOX OPTIONAL BLANK COVER W SCREWS OPTIONAL MAGNETIC TAMPER SWITCH ...

Страница 20: ...om PW6K1R1E Wiring and Setup Additional Mounting Information Figure 2 9 Mounting Plate Dimensions 3 85 97 8 2 35 59 7 5 50 139 7 3 63 92 1 3 30 83 8 3 63 92 1 Ø0 16 Ø4 0 MR50 MGT HOLES 4PL Ø0 16 Ø4 0 3 GANG MGT HOLES 4PL ...

Страница 21: ... This page is left blank intentionally for double sided printing ...

Страница 22: ... Forest Hill Avenue Oak Creek WI 53154 414 766 1700 414 766 1798 Fax European Office Boblingerstrasse 17 D 71101 Schonaich Germany 49 7031 637 782 49 7031 637 769 Fax www honeywell com Specifications subject to change without notice Honeywell All rights reserved 800 07986V1 Revision A ...

Отзывы: