10
www.honeywell.com
PW6K1R1E Wiring and Setup
Input Circuit Wiring
2.8 Input Circuit Wiring
Typically, these inputs are used to monitor door position, request to exit, or alarm
contact. Input circuits can be configured as unsupervised or supervised. When
unsupervised, reporting consists of only the open or closed states.
When configured as supervised, the input circuit will report not only open and closed,
but also open circuit, shorted, grounded, and foreign voltage.
Note:
Grounded and foreign voltage states are not a requirement of UL 294 and
therefore not verified by UL.
A supervised input circuit requires two resistors be added to the circuit to facilitate
proper reporting.
The standard supervised circuit requires 1K Ohm, 1% resistors and should be located
as close to the sensor as possible. Custom end of line (EOL) resistances may be
configured via the host software.
The input circuit wiring configurations shown below are supported but may not be
typical:
Figure 2-6: Input Circuit Wiring
2.9 Relay Circuit Wiring
Two relays are provided for controlling door lock mechanisms or alarm signaling. The
relay contacts are rated at 5A @ 30VAC/DC, dry contact configuration.
Each relay has a
Common pole (C), a Normally Open pole (NO)
and a
Normally
Closed pole (NC)
.
•
When you are controlling the delivery of power to the door strike, the
Normally Open and Common
poles are used.
1K,1%
1K,1%
1K,1%
1K,1%
Standard Supervised Circuit,
Normally Closed Contact
Standard Supervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Closed Contact
TB2
IN4
IN2
IN3
1
IN1
TB1
1
}