60-2150—10

8

L404A-D,F; L604A,L,M

SETTING AND CHECKOUT

SETTING

In  all  models,  the  differential  is  subtractive  from  the

main  scale  set  point.  The  upper  operating  point  is  deter-
mined by the main scale set point, while the lower operat-
ing point is determined by the main scale setting less the
differential setting. The L404F and L604A (with jumper
installed), L,M have spdt switching action. Operating points
are shown in Fig. 10.

Fig. 10—L404 and L604 operating points.

main scale setpoint. They will not automatically return to
their  former  positions.  To  reset  one  of  these  controllers,
wait  until  the  pressure  falls  to  the  set  point  minus  the
differential (Fig. 10). Then depress the manual reset lever
(Fig. 11) and release it. The controller will not be reset until
you release the manual reset lever. This prevents the con-
troller from becoming an automatic-reset device if the reset
lever is stuck, held in, or tied down.

Fig. 11—Setting a Pressuretrol

®

 Controller.

Setting and Checkout

MAIN SCALE SETPOINT

(SWITCH BREAKS)

SUBTRACTIVE
DIFFERENTIAL

DIFFERENTIAL SETTING

(SWITCH MAKES)

PRESSURE
RISE

L404A,C

1

MAIN SCALE SETPOINT

(SWITCH MAKES)

SUBTRACTIVE
DIFFERENTIAL

DIFFERENTIAL SETTING

(SWITCH BREAKS)

PRESSURE
RISE

L404B,D

1

MAIN SCALE SETPOINT

(BREAKS R-B, MAKES R-W)

SUBTRACTIVE
DIFFERENTIAL

DIFFERENTIAL SETTING

(MAKES R-B, BREAKS R-W)

PRESSURE
RISE

L404F;
L604L,M

1

2

MAIN SCALE SETPOINT

(MAKES R1-W, BREAKS R2-B)

SUBTRACTIVE
DIFFERENTIAL

DIFFERENTIAL SETTING

(BREAKS R1-W, MAKES R2-B)

PRESSURE
RISE

L604A

1

2

L404C,D AND L604L MANUAL RESET MODELS HAVE A SMALL, FIXED
DIFFERENTIAL. THEY CAN BE MANUALLY RESET WHEN THE PRESSURE
FALLS TO THE MAIN SCALE SETPOINT MINUS THE DIFFERENTIAL.

L604M HAS A SMALL, FIXED DIFFERENTIAL OF 3.5 PSI (0.25 kg/cm

2

OR 24.1 kPa.)

M8942

Adjust the main scale set point for the desired operating

pressure by turning the main scale adjusting screw (Fig. 11)
on the top of the case until the main scale setting indicator
is at the desired value. On an L404A,B,F with a 5 to 150 psi
(.3 to 10.3 kg/cm

2

 [34 to 1034 kPa]) operating range, or an

L604A,  adjust  the  differential  setting  by  turning  the  dif-
ferential  adjusting  screw  (Fig.  11)  until  the  differential
setting  indicator  is  at  the  desired  value.  L404C,D  and
L604L  are  manual  reset  models:  see  the  next  paragraph.
The  L604M  has  a  fixed  differential.  The  scaleplates  are
marked psi and kg/cm

2

.

Trip-Free Manual Reset Feature
(L404C,D and L604L only)

The L404C breaks, the L404D makes, and the L604L

makes R-W and breaks R-B when the pressure rises to the

MERCURY 
SWITCH

DIFF.

MAIN

PSI

12

10

8

6

4

2

.1

.3

.5

.7

.8

.6

.4

.2

0

.5

1

20

10

30

40

50

3.5

3

2.5

2

1.5

0

DIAPHRAGM
ASSEMBLY

LEVELING
INDICATOR

POINTER

INDEX 
MARK

MANUAL
RESET 
LEVER

MAIN SCALE
ADJUSTING
SCREW

DIFFERENTIAL
ADJUSTING
SCREW

SCALEPLATES

DIFFERENTIAL 
SETTING
INDICATOR

MAIN SCALE
SETTING
INDICATOR

ADJUSTABLE DIFFERENTIAL ON THE L404A,B,F; L404L WITH A 5 TO
150 PSI (0.34 TO 10.3 kg/cm

2

  [34 TO 134 kPa] OPERATING RANGE; 

AND L604A MODELS ONLY.

TRIP-FREE MANUAL RESET LEVER ON THE L404C,D AND L604L 
MODELS ONLY.

M8943

1

2

1

2

CHECKOUT

After the controller has is installed, wired, and set, test it

with  the  system  in  operation.  First  allow  the  system  to
stabilize. Then observe the operation of the controller while
raising and lowering its setpoint. Pressure should increase
when the setpoint is raised and decrease when the set point
is lowered.

Also check the make and break points of the controller.

If they do not agree with a separate, accurately calibrated
pressure gauge, a slight adjustment of the scaleplate(s) may
be necessary.

Use accurate pressure testing equipment when checking

out the controller. Do not rely on inexpensive gauges. The
controllers are carefully calibrated at the factory.

Содержание Pressuretrol L404 Series

Страница 1: ...or visible through cover Hexagonal fitting with 1 4 18 NPT internal threads for direct mounting to 14026 Steam Trap siphon loop Surface mount is available using screws through holes knockouts in case backing Can be used with steam air non combustible gases or fluids non corrosive to the pressure sensing ele ment Stainless steel diaphragm except 300 psi 21 1 kg cm2 2068 kPa models also allows use w...

Страница 2: ...troller case Scales are marked in psi and kPa ELECTRICALCONNECTIONS Internalscrewterminals hole in side of case for 1 2 in conduit MOUNTINGMEANS Hexagonalfittingondiaphragmhas 1 4 18 NPT internal threads for mounting on a pipe or steam trap siphon loop Also can be surface mounted using screws through two holes knockouts in back of case Ordering Information When purchasing replacement and moderniza...

Страница 3: ...ng Action on Pressure Rise Operating Rangesa Midscale Subtractive Differentiala Adjustable Maximum Surge Pressure Model to Setpoint psi kg cm2 kPa psi kg cm2 kPa psi kg cm2 kPa L404A spst breaks circuit 2 to 15b c 5 to 50 10 to 150b 20 to 300d 14 to 1 0 35 to 3 5 66 to 10 6 1 4 to 21 0 14 to 103 34 to 345 69 to 1034 138 to 2068 2 to 6 4 to 12 8 to 16 15 to 40 14 to 41 28 to 82 56 to 1 10 1 04 to 2...

Страница 4: ... 0 91 kg FINISH Gray APPROVALS Underwriters Laboratories Inc listed L404A B C D F L604A L M only file no MP466 vol 10 guide no MBPR CanadianStandardsAssociationcertified L404A B C D F L604A L only file no LR1620 guide no 400 E 0 REPLACEMENT PARTS 129178 Thermoplastic Cover 14026SteamTrap siphonloop 1 4in blackironpipe Necessary for boiler installations ACCESSORIES 33312B Knurled Adjustment Knob wi...

Страница 5: ...on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced flame safe guard control technician 4 After installation is complete check out product operation as provided in these instructions CAUTION 1 Disconnect power supply before beginning in stallation to prevent possible equipment dam age or electrical shock 2 When using the controller wit...

Страница 6: ...ine voltage wiring 3 Fornormalinstallations usemoisture resistantNo 14 wire suitable for at least 167 F 75 C when you are using the controller with a flame safeguard primary control or at least 194 F 90 C when using it with a programming control 4 Forhightemperatureinstallations usemoisture resis tant No 14 wire selected for a temperature rating above the maximum operating temperature 5 Allmodelsh...

Страница 7: ...ON AS REQUIRED BREAKS R TO B AND MAKES R TO W WHEN PRESSURE RISES TO SETPOINT L2 POWER SUPPLY FLAME SAFEGUARD CONTROL MOTOR OR OTHER LOAD SPDT CONTROLLER HIGH LIMIT W R B ALARM Fig 9 L404F or L604 with jumper installed controlling an M644B motor M8940 L1 HOT L2 1 1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VOLT THERMOSTAT LOW VOLTAGE RELAY L404 LOAD THERM POWER SUPPLY 1 2 Fig...

Страница 8: ... the main scale set point for the desired operating pressure by turning the main scale adjusting screw Fig 11 on the top of the case until the main scale setting indicator is at the desired value On an L404A B F with a 5 to 150 psi 3 to 10 3 kg cm2 34 to 1034 kPa operating range or an L604A adjust the differential setting by turning the dif ferential adjusting screw Fig 11 until the differential s...

Страница 9: ...ng on themodelofthecontroller AnL404AorCshouldbreak an L404BorDshouldmake anL404F L604L Mshouldbreak R B and make R W and an L604A should break R2 B and make R1 W If it makes the ohmmeter reads zero if it breaks the ohmmeter reads infinity 5 Raise the set point of the controller simulating a pressure decrease through a range greater than the differen tial The switch should break or make just the o...

Страница 10: ...e pointer may be over the index mark but the controller still may not be operating within the tolerance of its scale setting In this case carefully bend the steam trap siphon loop until the controller switches properly MAINTENANCE The cover of the controller should be in place at all times to protect the internal components from dirt dust and physical damage Routine maintenance should consist of o...

Страница 11: ...11 60 2150 10 ...

Страница 12: ... Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A www honeywell com bbc ...

Отзывы: