background image

-- 2 --

462 06 1211 00

3/17/06

Important Information

This kit includes a Honeywell conversion kit for converting

Honeywell VR8200, VR8205S, SV9500, SV9501 or VR8204M

gas valves certified for use with Propane Gas (and so marked) to

units functionally the same as the certified furnace for use with

Natural Gas. If converting from propane gas to natural gas, the

gas valve conversion kit, main burner orifices, and pilot orifice, all

found in this kit, must be installed.

For converting the furnace from standard altitude on natural gas to

high altitude (2001 feet above sea level or greater) on natural gas,

the Honeywell conversion kit and pilot orifice changes are not

needed. Only the main burner orifices require changing. Refer to

Table 1

for proper orifice size for specific model number, input

capacity, and installation altitude.

The orifices provided in this kit are stamped to indicate the size

(twist drill number) and are sized for natural gas ONLY. Do NOT

use them with butane or a mixture of butane and propane. The

parts list specifies the size orifices supplied in the kit. Compare the

size marking on the orifices with the sizes as listed in the parts list.

Make sure you have the correct main burner orifices.

Extreme care is used to assure that this kit contains the proper

orifices.

Oversized orifices could result in hazardous

conditions, especially if the venting is inadequate.

For that

reason, we recommend that the installer check the size of the

orifice with a new twist drill of the correct size. This procedure

assures that the orifices provided are the correct size.

ELECTRIC SHOCK HAZARD/FIRE AND/OR

EXPLOSION HAZARD.
Failure to follow this warning could result in

equipment damage, personal injury, death

and/or property damage.
The gas supply shall be shut OFF prior to

disconnecting the electrical power, before

proceeding with the conversion.
Turn OFF electric power supply at disconnect

switch or service panel before starting

installation.

!

D

Shut off gas supply to furnace at manual shut--off valve be-

fore starting installation.

EXPLOSION HAZARD
Failure to follow this warning could result in

personal injury, death and/or property damage.
If unit is still running, allow 2.5 minutes after gas

shut off before turning off power, Shut Off electric

power at unit disconnect and service panel.

!

D

Disconnect electric power supply to the furnace before

starting installation.

D

Check for gas leaks after installation of kit and before at-

tempting to start furnace.

D

Locate the Natural Gas Conversion Label next to the fur-

nace rating plate.

D

Fill out and attach the Field Conversion Label to the front ex-

terior of the furnace.

FIRE,

EXPLOSION,

CARBON

MONOXIDE

POISONING HAZARD.
Failure to follow these instructions exactly could

result in personal injury, death and/or property

damage.
This conversion kit shall be installed by a

qualified service agency in accordance with the

manufacturer’s instructions and all applicable

codes and requirements of the authority having

jurisdiction.

If

the

information

in

these

instructions is not followed exactly, a fire, an

explosion or production of carbon monoxide may

result causing property damage, personal injury

or loss of life. The qualified service agency is

responsible for the proper installation of this kit.

The installation is not proper and complete until

the operation of the converted appliance is

checked as specified in the manufacturer’s

instructions supplied with the kit.

!

Gas Pressure

D

Refer to the furnace rating plate for the approved gas input

rating.

D

Gas input to burners MUST NOT exceed the rated input

shown on rating plate.

D

Do NOT

allow minimum gas supply pressure to vary down-

ward. Doing so will decrease input to furnace. Refer to

Table 2

for gas supply and manifold pressures.

Table 2

Gas Pressures

Gas

Supply Pressure

Manifold

Type

Recommended

Max.

Min.

Pressure

Natural

7

13

4.5

3.5

Installation

ELECTRIC SHOCK HAZARD/FIRE AND/OR

EXPLOSION HAZARD.
Failure to follow this warning could result in

property damage, equipment damage, personal

injury and/or death.
Turn OFF gas supply at manual gas valve

before turning OFF electric power supply and

starting installation.
Turn OFF electric power supply at disconnect

switch or service panel before starting

installation.

!

Содержание PGF3

Страница 1: ...ied Model Number Orifice Drill Kit Number Orifice Drill Field Supplied PGC K060F GPCM K060 PGC K080F GPCM K080 PGC K100F GPCM K100 PGC K120F GPCM K120 Natural Gas Orifice Kits and Sizes Table 1 PGF K140F GPFM K140 PGAA PGMD All Sizes PGAD PGME All Sizes PGC K040F GPCM K040 Orifice Drill Field Supplied 0 to 2000 ft Elevation Above Sea Level PGF K080F GPFM K080 Parts List Kit 1173865 Description Par...

Страница 2: ...arting installation EXPLOSION HAZARD Failure to follow this warning could result in personal injury death and or property damage If unit is still running allow 2 5 minutes after gas shut off before turning off power Shut Off electric power at unit disconnect and service panel D Disconnect electric power supply to the furnace before starting installation D Check for gas leaks after installation of ...

Страница 3: ...erting from Propane Gas to Natural Gas in the state of California NOx baffles must be installed to comply with California law NOx baffles can be ordered from Fast Parts Remove the two 2 screws holding the burner assembly in place Install the correct NOx baffle for the unit if required and replace the Burner Assembly using the original two screws Figure 2 Installing NOx Baffles Figure 2 or Changing...

Страница 4: ...erting from Propane Gas to Natural Gas Conversion of Honeywell VR8200 SV9500 SV9501 and VR8204M Gas Valves using Natural Gas Conversion Kit 396222 1 Remove the regulator cap screw and pressure regulator ad justing screw See Figure 10 2 Remove the existing regulator spring from the regulator housing 3 Insert the replacement spring stainless steel contained in this kit into regulator housing Typical...

Страница 5: ...a soapy solution All leaks must be repaired immediately Start up and Check out 1 Remove the plug from the Inlet Pressure Tap on gas valve and install a manometer See Figures 7 8 9 10 2 Open manual gas line valve to unit Check for gas leaks and correct as necessary Check supply pressure Refer to Table 2 for proper supply pressure values If not within these limitations DO NOT OPERATE UNIT contact ga...

Страница 6: ... complete 1 revolution 2 3600 38 94 7 3 94 7 x 1 94 7 4 94 7 x 1020 96 632 Btu hr For this example the nameplate input is 100 000 Btu hr so only a minor change in manifold pressure is required In no case should the final manifold pressure vary more than 3 water column from the values in Table 2 Never exceed the required input rate Table 3 Table 3 0 2000 2001 3000 3001 4000 4001 5000 5001 6000 6001...

Страница 7: ...crease clockwise to decrease 3 Replace the cap on the pilot adjusting screw Pilot Burner HSP 10 11 65 Sensor Tip Proper Flame Adjustment Hot Surface Igniter Figure 11 Main Burner Flame Check Check for the following D Stable and blue flames See Figure 12 Dust may cause orange tips or wisps of yellow but flames MUST NOT have solid yellow tips D Flames extending directly from burner into heat exchang...

Отзывы: