46(110)
CABLING AND CONNECTIONS
6
6.1.1.6
Cable and fuse sizes, NX_5, FR10 to FR12
The table below shows typical cable sizes and types that can be used with the converter. The final
selection should be made according to local regulations, cable installation conditions and cable
specification.
Frame
Type
I
L
[A]
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No. of supply
cables
No. of motor
cables
NX0385 5
385
400 (3 pcs)
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd Even/Odd
NX0460 5
460
500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd Even/Odd
FR10
NX0520 5
520
630 (3 pcs)
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88Cu)
Even/Odd Even/Odd
NX0590 5
590
315 (6 pcs)
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even Even/Odd
NX0650 5
650
400 (6 pcs)
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even Even/Odd
FR11
NX0730 5
730
400 (6 pcs)
Cu: 4*(3*120+70)
Al: 4*(3*185Al+57Cu)
Even Even/Odd
NX0820 5
820
500 (6 pcs)
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even Even
NX0920 5
920
500 (6 pcs)
Cu: 4*(3*150+70)
Al: 4*(3*240Al+72Cu)
Even Even
FR12
NX1030 5
1030
630 (6 pcs)
Cu: 4*(3*185+95)
Al: 4*(3*300Al+88Cu)
Even Even
Table 6-4. Cable and fuse sizes for NX_5 (FR10 to FR12)
1)
based on correction factor 0.7
6.1.1.7
Cable and fuse sizes, NX_6, FR10 to FR12
The table below shows typical cable sizes and types that can be used with the converter. The final
selection should be made according to local regulations, cable installation conditions and cable
specification.
Frame
Type
I
L
[A]
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No of
supply
cables
No of
motor
cables
NX0261 6 261
315 (3 pcs)
Cu: 3*185+95
Al: 2*(3*95Al+29Cu)
Even/Odd
Even/Odd
NX0325 6 325
400 (3 pcs)
Cu: 2*(3*95+50)
Al: 2*(3*150Al+41Cu)
Even/Odd
Even/Odd
NX0385 6 385
400 (3 pcs)
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
FR10
NX0416 6 416
500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
NX0460 6 460
500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd
Even/Odd
NX0502 6 502
630 (3 pcs)
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88 Cu)
Even/Odd
Even/Odd
FR11
NX0590 6 590
315 (6 pcs)
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even Even/Odd
NX0650 6 650
400 (6 pcs)
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even Even
NX0750 6 750
400 (6 pcs)
Cu: 4*(3*120+70)
Al: 4*(3*150Al+41Cu)
Even Even
FR12
NX0820 6 820
500 (6 pcs)
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even Even
Table 6-5. Cable and fuse sizes for NX_6 (FR10 to FR12)
1)
based on correction factor 0.7