TECHNICAL
DATA
19(110)
4
4.2.2
NX_6 – Mains voltage 525—690 V
High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min
Following continuous operation at rated output current, 150 % rated output current (IH)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated output
current (IH)
Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 min
Following continuous operation at rated output current, 110% rated output current (IL)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated output
current (IL)
All sizes are available as IP21/NEMA1 Sizes FR4 to FR10 are additionally available as IP54/NEMA12.
FR12 is available only as NXP.
Mains voltage 525-690 V, 50/60 Hz, 3~
Loadability
Motor shaft power
Low High
690V
supply
575V supply
Frequency
converter
type
Rated
continuous
current I
L
(A)
10%
overload
current
(A)
Rated
continuous
current I
H
(A)
50%
overload
current
(A)
Max
current
I
S
10%
overload
40°C
P(kW)
50%
overload
50°C
P(kW)
10%
overload
40°C
P(hp)
50%
overload
50°C
P(hp)
Frame
Dimensions and
weight
WxHxD/kg
NX 0004 6
4.5
5.0
3.2
4.8
6.4
3
2.2
3.0
2.0
FR6
195x519x237/18,5
NX 0005 6
5.5
6.1
4.5
6.8
9.0
4
3
3.0
3.0
FR6
195x519x237/18,5
NX 0007 6
7.5
8.3
5.5
8.3
11.0
5.5
4
5.0
3.0
FR6
195x519x237/18,5
NX 0010 6
10
11.0
7.5
11.3
15.0
7.5
5.5
7.5
5.0
FR6
195x519x237/18,5
NX 0013 6
13.5
14.9
10
15.0
20.0
10
7.5
11
7.5
FR6
195x519x237/18,5
NX 0018 6
18
19.8
13.5
20.3
27
15
10
15
11
FR6
195x519x237/18,5
NX 0022 6
22
24.2
18
27.0
36
18.5
15
20
15
FR6
195x519x237/18,5
NX 0027 6
27
29.7
22
33.0
44
22
18.5
25
20
FR6
195x519x237/18,5
NX 0034 6
34
37
27
41
54
30
22
30
25
FR6
195x519x237/18,5
NX 0041 6
41
45
34
51
68
37.5
30
40
30
FR7 237x591x257/35
NX 0052 6
52
57
41
62
82
45
37.5
50
40
FR7 237x591x257/35
NX 0062 6
62
68
52
78
104
55
45
60
50
FR8
291x758x344/58
NX 0080 6
80
88
62
93
124
75
55
75
60
FR8
291x758x344/58
NX 0100 6
100
110
80
120
160
90
75
100
75
FR8
291x758x344/58
NX 0125 6
125
138
100
150
200
110
90
125
100
FR9
480x1150x362/146
NX 0144 6
144
158
125
188
213
132
110
150
125
FR9
480x1150x362/146
NX 0170 6
170
187
144
216
245
160
132
150
150
FR9
480x1150x362/146
NX 0208 6
208
229
170
255
289
200
160
200
150
FR9
480x1150x362/146
NX 0261 6
261
287
208
312
375
250
200
250
200
FR10
595x2018x602/340
NX 0325 6
325
358
261
392
470
315
250
300
250
FR10
595x2018x602/340
NX 0385 6
385
424
325
488
585
355
315
400
300
FR10
595x2018x602/340
NX 0416 6
416
458
325
488
585
400
315
450
300
FR10
595x2018x602/340
NX 0460 6
460
506
385
578
693
450
355
450
400
FR11 794x2018x602/400
NX 0502 6
502
552
460
690
828
500
450
500
450
FR11 794x2018x602/400
NX 0590 6
590
649
502
753
904
560
500
600
500
FR11 794x2018x602/470
NX 0650 6
650
715
590
885
1062
630
560
650
600
FR12
1210x2017x602/600
NX 0750 6
750
825
650
975
1170
710
630
800
650
FR12
1210x2017x602/600
NX 0820 6
820
902
650
975
1170
800
630
800
650
FR12
1210x2017x602/600
Table 4-2. Power ratings and dimensions of NX, supply voltage 525—690V.
Note:
The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to
or less than the factory default.
Note:
The rated currents for FR10 to FR12 are valid at an ambient temperature of 40
°
C (except for 0416 6, 0590 6
and 0820 6: rated currents valid at an ambient temperature of 35°C).