background image

NOVAR ES3.S EXECUTIVE CONTROLLER

9

31-00366—01

ASSEMBLY BOARD DETAILS

Refer to Fig. 6 for LED and configuration switch locations.

Fig. 6. Assembly Board Detail.

Содержание Novar ES3.S

Страница 1: ...RUCTIONS 31 00366 01 Novar ES3 S Executive Controller Contents Introduction 2 Precautions 2 Wiring 4 Installing Executive controller 4 Checking Installation 7 Specifications 8 Assembly Board Details 9 Regulatory Compliance 12 ...

Страница 2: ...OBSERVE NATIONAL AND LOCAL ELECTRICAL CODES Reduce the risk of electrical shock or fire Do not interconnect the outputs of different Class 2 circuits Do not rely on the Novar ES3 S as a final safety device Make sure that the 24 VAC power wiring is connected to a dedicated transformer No other devices including the outputs should be powered by the transformer connected to the Novar ES3 S Do not gro...

Страница 3: ...NOVAR ES3 S EXECUTIVE CONTROLLER 3 31 00366 01 DIMENSIONS Fig 2 Dimensions in in mm 12 6 320 0 13 03 331 0 1 96 49 8 2 02 51 3 19 09 484 89 19 46 494 3 ...

Страница 4: ...of the Savvy or EC base plate with the hex wrench included with the executive controller and lift off the cover 2 Slide the Novar ES3 S electronics assembly down from the top of the base plate assembly and over the mounting posts 3 Guide the DB25 and DB37 connectors on the Novar ES3 S electronics assembly over the corresponding connectors on the Savvy transition circuit board 4 Tighten the two ret...

Страница 5: ...he version of the transition board being used Use the appropriate procedure outlined below Transition Board with or without UL Mark 1 Connect the white wire from the ALS to the transition board at Board with UL Mark Terminal 59 at the Outdoor Light Sensor Input connections Board without UL Mark Terminal 62 at the Outdoor Temperature Sensor Input connections 2 Connect the black wire from the ALS to...

Страница 6: ...onnect the signal wire from a 0 10V source or one terminal of a thermistor resistive or dry contact digital type input to the transition board at Terminal 60 at the Outdoor Temperature Sensor Input connections 2 Connect the return or ground wire from a 0 10V source or one terminal of a thermistor resistive or dry contact digital type input to the transition board at Terminal 61 Shield at the Outdo...

Страница 7: ...cess 5 If the shield is to be earth grounded tie the shield terminal to ground at the xcm 10S for Novar ES3 S and see Fig 7 and Fig 8 for grounding 6 If the expansion interface is used secure wiring using the Wire Clamp provided on the left side of the Novar ES3 S See Fig 6 CHECKING INSTALLATION Hardware When the unit has been mounted and the wiring connections have been completed the procedure pr...

Страница 8: ... Source 24VDC at 500mA max Digital Inputs Contact closure only Universal Inputs Thermistor Type 3 10K 10 to 135 F 23 3 to 57 2C Voltage 0 10VDC Input impedance 5Kohms Current 0 20mA Switch selectable Resistance 0 100K Ohms Digital Contact closure only 330uA Wetting Current Relay Outputs 24 VAC or VDC 2 amp pilot duty Class 2 Output Fault 24 VAC or VDC 2 amp pilot duty Class 2 System Diagnostic Inp...

Страница 9: ...NOVAR ES3 S EXECUTIVE CONTROLLER 9 31 00366 01 ASSEMBLY BOARD DETAILS Refer to Fig 6 for LED and configuration switch locations Fig 6 Assembly Board Detail ...

Страница 10: ...5 6 need to be externally grounded of the communications shields as shown in Fig 7 Even when Comm Ports 2 and 4 are internally connected grounding on the transition board needs to be done as shown in Fig 8 Fig 7 Comm Ports 3 5 6 grounded Fig 8 Comm Ports 2 4 grounded Comm Ports 3 5 6 NOT grounded Comm Ports 3 5 6 correctly grounded Comm Ports 2 4 correctly grounded Comm Ports 2 4 NOT grounded ...

Страница 11: ...onfigured and OK and is ready for operation Off or Blinking If the Novar ES3 S has been powered for less than 10 minutes and the System Status LED fails to illuminate or is blinking the I O module may be receiving a system update Power When lit the green Power LED indicates that system power has been applied If the Power LED does not light while power is applied contact Novar for technical support...

Страница 12: ... interference in which case users at their own expense will be required to take whatever measures may be required to correct the interference Any unauthorized modification of this equipment may result in the revocation of the owner s authority to continue its operation Innovation Science and Economic Development Canada ISED ISED Standard ICES 003 Issue 7 Operation is subject to the following two c...

Страница 13: ...adian Interference Causing Equipment Reg ulations Cet appareil numerique de la Classe A respecte toutes les exigencies du Reglement sur le material broilleur du Canada Waste Electrical Electronic Equip NOTE Customers are advised to dispose of this product at the end of its useful life according to applicable local laws regulations and procedures ...

Страница 14: ... is for information purposes only The content and the product it describes are subject to change without notice Novar makes no representations or warranties with respect to this document In no event shall Novar be liable for technical or editorial omissions or mistakes in this document nor shall it be liable for any damages direct or incidental arising out of or related to the use of this document...

Отзывы: