AM_8200
Programming Manual
PAGE - 5
AM82000_manu-prog-ENG
Doc. M-162.1-AM8200-ENG Rev A2
NOTIFIER ITALIA
FRONT PANEL LED INDICATIONS
ALARM
(Red)
:
It flashes if there is at least one device in alarm and it has not been recognized yet. It is
permanently lit if all alarm events have been recognized.
REMOTE ALARM
(Red):
it is permanently lit if the output towards the fire alarm transmission devices (telephone dial) has
been activated.
SILENCE SOUNDER
(Yellow):
It is lit after the Sounder Silencing control is performed.
DELAY IN PROGRESS
(Yellow):
It is lit if the immediate output activation has been disabled; apply to type C outputs (sounder
output) and type E (alarm transmission through telephone dial). Through this disablement, in
case of alarm the system delays the above mentioned outputs for the programmed times. During
the delay time the led flashes and it is possible to reset the current delay through the “reset delay”
key at lev.1.
EVACUATION
(Yellow):
It is lit after the evacuation function is performed.
TEST
(Yellow):
It is lit during Zone Walk Test
POWER
(Green):
It is permanently lit if the control unit is powered (by 230Vac or by batteries charger).
FAULTS
(Yellow):
It flashes if there is at least one fault of any type and it has not been recognized yet.
It is on if all faults have been recognized
SYSTEM
(Yellow):
It is lit if there is at least a system fault (watch dog, CRC memory error, etc.)
POWER SUPPLY
(Yellow):
It is lit if there is a power supply Fault.
GROUND FAULT
(Yellow):
It is permanently lit when the positive or negative is earthed.
MASK
(Yellow):
It is lit when there is at least one Zone or a Point Disabled in the system.
SOUNDER
(Yellow):
It is lit if the siren output is disabled.
It flashes when the siren output is in Fault condition
FAULTS
TRANSMISSION
(Yellow):
It is lit if the Fault transmission output is disabled (telephone dial).
It flashes when the Fault
transmission output is in Fault
condition.
ALARM TRANSMISSION
(Yellow):
It is lit if the alarm transmission is disabled (telephone dial).
It flashes when the alarm transmission output is in Fault condition
EXTINGUISHING
(Yellow):
I
t is lit if the output towards the automatic fire-fighting system (UDS) is disabled
It flashes when the fire-fighting control output is in Fault condition