AM_8200
Programming Manual
PAGE - 71
AM82000_manu-prog-ENG
Doc. M-162.1-AM8200-ENG Rev A2
NOTIFIER ITALIA
MAINF
Output Module FORC (not supervised) activated for Power Failure
N
MAINFC
Same as MANIF, but with supervised Output
N
REM
Output Module FORC controllable only by external commands.
N
REMC
Same as REM but with supervised Output
N
SND
Output Module which follows the status of the panel Sounder
N
ZFLT
Output Module FORC activated when the associated zone is in fault
N
ZFLTC
come ZFLT but with controlled output in standard mode
N
TABLE ‐2C
Output Modules NOT Supervised Output Advanced
CBE Y/N
FORC
Output Module relay with potential‐free contacts.
Y
PWRC
Output Module
FORC
interrupts momentarily the power supply
N
GPND
Output Module
FORC
activated at every alarm / fault.
N
APND
Output Module
FORC
activated at every alarm.
N
GAC
Output Module
FORC
activated at every alarm.
N
TPND
Output Module
FORC
activated at every fault.
N
GTC
Output Module
FORC
activated at every fault.
N
TRS
Output Module
FORC
activated at every fault.
N
ZDIS
Output Module activated in case of exclusion of point or zone.
N
MAINF
Output Module (not supervised) activated for Power Failure
N
REM
Output Module FORC controllable only by external commands
N
SND
Output Module which follows the status of the panel Sounder
N
ZFLT
Output Module FORC activated when the associated zone is in fault
N
TABLE ‐2D
Output Modules CLIP
CBE Y/N
CON
Output Module with supervised Output
Y
FORC
Output Module relay with potential‐free contacts.
Y
PWRC
Output Module
FORC
interrupts momentarily the power supply
N
GPND
Output Module
FORC
activated at every alarm / fault..
N
APND
Output Module
FORC
activated at every alarm.
N
GAC
Output Module
FORC
activated at every alarm.
N
GAS
Output Module
CON
activated at every alarm.
N
TPND
Output Module
FORC
activated at every fault.
N
GTC
Output Module
FORC
activated at every fault.
N
GTS
Output Module
CON
activated at every fault.
N
TRS
Output Module
F ORC
activated at every fault.
N
ZDIS
Output Module activated in case of exclusion of point or zone.
N
REM
Output Module FORC controllable only by external commands
N
REMC
Same as REM with supervised Output
N
SND
Output Module which follows the status of the panel Sounder
N
GSND
Addressable Sounder that can be Silenced
Y
GSTR
Addressable Strobe that can be Silenced
Y
STR
Addressable Strobe which follows the status of the panel Sounder
N
TABLE ‐2E
Output Modules NOT Supervised Output CLIP
CBE Y/N
FORC
Output Module relay with potential‐free contacts.
Y
PWRC
Output Module
FORC
interrupts momentarily the power supply
N
GPND
Output Module
FORC
activated at every alarm / fault..
N
APND
Output Module
FORC
activated at every alarm.
N
GAC
Output Module
FORC
activated at every alarm.
N
TPND
Output Module
FORC
activated at every fault.
N
GTC
Output Module
FORC
activated at every fault.
N
TRS
Output Module
FORC
activated at every fault.
N
ZDIS
Output Module
FORC
activated in case of exclusion of point or zone.
N
REM
Output Module FORC controllable only by external commands
N
SND
Output Module which follows the status of the panel Sounder
N
GSND
Addressable Sounder that can be Silenced
Y
GSTR
Addressable Strobe that can be Silenced
Y