AM-8200
FIRE DETECTION PANEL
Programming Manual
Firmware V.1.0
Страница 1: ...AM 8200 FIRE DETECTION PANEL Programming Manual Firmware V 1 0 ...
Страница 2: ... operation to enter data in the programming folders 6 Normal condition 7 Pre alarm condition 8 Alarm condition 9 Condition with fault zone events 10 Condition with System fault events 11 PROGRAMMING MENU 12 Programming Menù 13 System Menù 13 System Type 14 System Address 14 System Line 14 System Timings 15 Faults signaling timings TAB 16 System Password 17 System programming installation 17 Progra...
Страница 3: ...ng Menù 40 Zone Programming Menù 42 Configuration Menù 44 Utility Menù 46 System View 47 Language 47 Date and Time 47 Parameters 48 Local 48 Special 48 Drift warning function 48 Mod NONA 49 Reability parameters 49 Sounder 50 Prints 50 HISTORY LOG 51 History Log Display 51 History Log Disable 52 History Log Save 52 VIEW MODIFY STATUS 53 Detectors 53 Modules 54 Groupes 55 Zones 55 Active Module List...
Страница 4: ...M 8200_manu prog Doc M 162 1 AM8200 ITA Rev A 2 NOTIFIER ITALIA DISABLE MENÙ 57 Modify 58 Detectors 58 Modules 59 Zones 59 System Disable 59 TEST MENU 60 APPENDIX A CONTROL BY EVENT EQUATION 62 Appendix B Software Type_ID for MODULES 70 ...
Страница 5: ...ectly compatible with the control unit may cause damages to the same control unit and a bad operation of the system in any moment Therefore it is essential to only use material which is guaranteed by NOTIFIER and is compatible with its own control units Please consult NOTIFIER Technical Service for any doubt A AT TT TE EN NT TI IO ON N T Th hi is s m ma an nu ua al l r re ef fe er rs s t to o f fu...
Страница 6: ...one for each module that compose the device The same module in a CLIP loop occupies 3 consecutive addresses of 99 available for modules SUB ADDRESS The sub address programming is available only for addressable MODULES SUB ADDRESSs are automatically assigned to the individual components of the multiple module depending on the programmed HARDWARE TYPE Modules with a single input or single output hav...
Страница 7: ...y the position of an event 500 physical zones in stand alone or in 16 loop network configuration 2000 physical zones in128 loop network configuration A maximum of 32 points can be associated to each zone GROUPS A group is a software set of devices that can be used to program associations between Inputs and Outputs and perform actions triggered by input or alarm events 400 groups in 16 loop network...
Страница 8: ...es programmed with SW Type ID SND the output modules activated for a CBE associations By pressing this key you can de activate the following devices Siren Output Output modules programmed through Type ID SND and enabled for silencing All output modules activated through CBE associations and enabled for silencing A subsequent pressure of this key will re activate Siren Output Output modules program...
Страница 9: ... lit during Zone Walk Test POWER Green It is permanently lit if the control unit is powered by 230Vac or by batteries charger FAULTS Yellow It flashes if there is at least one fault of any type and it has not been recognized yet It is on if all faults have been recognized SYSTEM Yellow It is lit if there is at least a system fault watch dog CRC memory error etc POWER SUPPLY Yellow It is lit if the...
Страница 10: ...s you can enter the adjacent folders displays Through the arrows you can scroll the fields inside the folder the selected field is displayed with the characters in REVERSE If the folder has an index field the first two function keys appear through which you can scroll The selected field can be changed by entering in editing mode through the enter key According to the type of datum there are differ...
Страница 11: ... condition The following screen is displayed when the control panel is in Normal Condition If you touch the screen the following screen is displayed Icons that signals the Panel Conditions The NOTIFIER brand symbol appears in the absence of alarms and Faults If there are Pre alarms the alarm clock symbol is displayed If there are Alarms the Fire symbol is displayed If there are Faults the Triangle...
Страница 12: ...keys to scroll through the list of pre alarm zones By pressing the Enter key you will access the list of points in the pre alarm of the selected zone with the arrow keys you can scroll through the list of alarm devices Any subsequent zones in pre alarm Zone Counter in Pre Alarm Pre alarm device Text programmed for the device Zone View Window First zone in pre alarm time date progressive event prog...
Страница 13: ... zones containing Faults By pressing the enter key you can access the list of point in alarm of the zone selected on the display through the arrow keys you can scroll the list of the devices in alarm Counter for zones in alarm FIRST ZONE IN ALARM Date and Time Event Number ID Text for the Zone Device in Alarm D Detector M Module Text programmed For this Device If more zones are in Alarm 2 ZONES IN...
Страница 14: ...ou can scroll the list of the Zone Faults Through a first pressure of the enter key you can display the list of devices with the indication of the point name refer to the following figure Pressing the escape key or leaving the keypad inactive for 30 seconds you return to the list of faulty areas Counter for Faulty zones Zone with Fault events Text programmed for this zone Detail of the Device in F...
Страница 15: ...t th he e l li is st t o of f t th he e S Sy ys st te em m F Fa au ul lt ts s Condition with alarm events from a zone under Test Through a first pressure of the enter key you can display the list of devices with the indication of the point name refer to the following figure through the arrow keys you can scroll the list of the tested devices of the zone Date and Time of the Event Counter for Syste...
Страница 16: ...arn item and press the enter key and subsequently enter the number of lines for which the procedure must be started Through this operation all the devices installed on the lines are recognized and loaded in the control unit memory according to their Hardware TYPE ID and with the default data At the end of the procedure check that the devices detected by the control unit during the Auto Learn are t...
Страница 17: ...mming menu to perform the configuration of the system or make changes to the programming To access the Programming menu you must enter the Level 3A password 44444 is the default password To enter the password use the keyboard that appears on the screen and press ENTER The following screen is displayed Programming System menu By selecting System you can configure the configuration parameters which ...
Страница 18: ...6 Network of Panels with up to 16 lines in total NET 128 Network of Panels with up to 128 lines in total Programming System System Address The Address entry will assign the panel device number on the CAN BUS network Programming System LINE Style OPEN LINE CLOSED LOOP This function allows to change in memory the type of line connection Through a first pressure of the enter key the Line editing func...
Страница 19: ...nction is activated Through the arrow keys or through keyboard the data are entered by pressing the enter key you can confirm entered data Sounder activation delay is programmable in seconds max 600 sec The Siren and TX Alarms activation delay timings are active only in case of alarm if the immediate activation of the outputs has been excluded in the exclusions menu DETECTORS TAB Press the right A...
Страница 20: ...be Silenced by an operator By pressing the enter key the editing function is activated Through the arrows keys data are entered and through the enter key entered data are confirmed FAULTS signalings timings TAB Press the right Arrow key to change the parameters to manage the Fault signallings MAINS FAULT DETECTION TIME is the minimum time during which Mains Fault is signalled if there is no mains ...
Страница 21: ...rough the arrow keys select the item which is required to be changed Press the enter key to activate the Numeric Keyboard to program the Password Type the NEW password and hit Enter Re type and confirm the password entered S Sy ys st te em m p pr ro og gr ra am mm mi in ng g I In ns st ta al ll la at ti io on n This function allows to enter a programmable text for the Panel This text can have a ma...
Страница 22: ...Detectors or Modules Detectors DETECTORS By selecting DETECTORS and by confirming the selection through the enter key you enter the programming procedure for Addressable Sensors This procedure is composed of 4 programming folders to access the folders use the arrow keys The display shows by default the first device of the first line To select another device use the function keys LINE LINE Lines an...
Страница 23: ...tor ION Smoke ionization detector THER Thermal detector PINN Laser High sensitivity Smoke detector OMNI Omni Sensor Detector D De et te ec ct to or rs s P PR RO OG GR RA AM M T TA AB B P Pr ro og gr r o of f C CB BE E E Eq qu ua at ti io on ns s Z Zo on ne e a as ss so oc ci ia at ti io on n Program Zone associated to Detector Points are assigned to a Zone for a proper display of the alarm locatio...
Страница 24: ...Reverse press the enter key and use the arrow keys to change the parameter at the end press the enter key to confirm the datum Verify By programming YES the control unit is allowed to perform a check on the sensor for the time fixed in the Timing programming before confirming the possible alarm Sensor sensitivity programming Default values Standard sensitivity 5 Low sensitivity 1 High sensitivity ...
Страница 25: ...AB allows the programming of block of points sharing the same programming It can be used if the points have consecutive addresses and have common parameters The Remove From to function allows to eliminate from the control unit programming an entire consecutive block of points by entering the start and end addresses The Copy and Paste functions allow the programming of the block points and can be u...
Страница 26: ...king and Led Blink N B The heat only mode is activated automatically if we have programmed the Day Night function to the zone associated with the SDX 751 TEM sensor ALARM LEVEL Corresponding Percentage of Obscuration inside the Sensor Chamber ALARM 1 1 ft ALARM 2 COMP AUT 1 2 ft ALARM 3 2 ft ALARM 4 COMP AUT 2 3 5 ft Default ALARM 5 3 5 ft enter the ending address through the arrow keys or by usin...
Страница 27: ...nd TAB P Pr ro og gr r o of f C CB BE E E Eq qu ua at ti io on n Z Zo on ne e a as ss so oc ci ia at ti io on n Third TAB Progr of Check Al Level Daytime night Tracking and Led Blink Value Corresponding Percentage of Obscuration inside the Sensor Chamber 1 2 ft defaul for Sens LOW 2 1 5 ft 3 1 ft 4 0 5 ft 5 0 2 ft defaul for Sens STD 6 0 1 ft 7 0 05 ft 8 0 03 ft 9 0 02 ft defaul for Sens HIG Sensi...
Страница 28: ...u ua at ti io on n Z Zo on ne e a as ss so oc ci ia at ti io on n Tird TAB Progr of Check Al Level Daytime night Tracking and Led Blink N B The heat only mode is activated automatically if we have programmed the Day Night function to the zone associated with the NFXI SMT2 sensor ALARM LEVEL Corresponding Percentage of Obscuration inside the Sensor Chamber ALARM 1 1 ft ALARM 2 COMP AUT 1 2 ft ALARM...
Страница 29: ...i ia at ti io on n Tird TAB Progr of Check Al Level Daytime night Tracking and Led Blink The delay counter is initialized when the smoke level exceeds 0 75 ft N B The heat only mode is activated automatically if we have programmed the Day Night function to the zone associated with the NFXI SMT3 sensor Alarm level Percentage of Obscuration inside the Sensor Chamber LIV 1 1 ft No Delay LIV 2 2 ft No...
Страница 30: ...k The delay counter is initialized when the smoke level exceeds 0 75 ft N B The heat only mode is activated automatically if we have programmed the Day Night function to the zone associated with the IRX 751CTEM W SMART 4 Example of programming of BEAM NFXI BEAM Alarm level Percentage of Obscuration inside the Sensor Chamber LIV 1 1 ft smoke or CO concentration more than 45 ppm No Delay LIV 2 2 ft ...
Страница 31: ...m 30 4 40 m 40 3 50 m 50 2 Variable from 30 m to 50 m default for Sens STD Note A1 1 Variable from 40 m to 50 m Note A2 Distance meters The beam detector has two levels of variable sensitivity When one of these two levels is selected the detector will automatically adjust the sensitivity using a software algorithm that selects the optimum sensitivity as a function of the installation environment S...
Страница 32: ...g gr r o of f H HW W T Ty yp pe e I ID D a an nd d r re ea ad di in ng g a as ss so oc ci ia at te ed d w wi it th h t th he e m mo od du ul le e The display shows by default the first device of the first line Use the function keys to select another device P Pr ro og gr r T TA AB B P Pr ro og gr r o of f C CB BE E E Eq qu ua at ti io on n Z Zo on ne e a as ss so oc ci ia at ti io on n HW type Modu...
Страница 33: ... o of f T Tr ra ac ck ki in ng g a an nd d L Le ed d B Bl li in nk k TAB EDIT For the instructions how to operate refer to POINT Programming procedure as this part is the same for Modules OUTPUT MODULES For a description of How to operate and the description of Tracking and Led Blink field please refer to Sensor programming screen before detailed ...
Страница 34: ...il le en nc ci in ng g T Te es st t e en na ab bl li in ng g a an nd d L Le ed d B Bl li in nk k FAAST FL2011El It has a single channel available with a smoke laser detector FL2012El It has a single channel available with two smoke detectors in a common room for combined detection FL2022EI It has two channels available with two smoke detectors with separate chambers One sensor for each channel The...
Страница 35: ...se of AND or OR by the 2 Pinnacle sensors installed Programming TAB for FL2012EI T Th hi ir rd d T TA AB B o or r O Op pt ti io on n P Pr ro og gr r f fo or r d di is sa ab bl le ed d S Si il le en nc ci in ng g T Te es st t e en na ab bl li in ng g a an nd d L Le ed d B Bl li in nk k Led Blink Enable LED flashing of the field device Silence Enabled Enable manual Silence Automatic Silence Enables ...
Страница 36: ...LIA Doc M 162 1 AM8200 ENG Rev A2 AM8200_manu prog ENG NRXI GATE Gateway for wireless System Tabs Main and Program The Options Tab does not contain any entries programming Zone associated to this Module HW Type SW Type Programmable Text max 32 char ...
Страница 37: ...y you enter the self programming procedure of the devices installed on the line Verify Double Address YES By selecting YES panel will check for more than one device programmed with same address in a line When several devices programmed with the same address are found the message shown in the figure is displayed with the indication of the address The user will be able to identify the devices with t...
Страница 38: ...d during the Auto Learn procedure TOT total of devices detected on the line NEW NFO correctly programmed devices MIS Devices previously programmed but not detected during the Auto Learn The SAVE control saves the devices detected during the Self Learn according to the following mode NEW and NFO are initialized through the default data MIS are removed The correctly programmed devices keep the curre...
Страница 39: ...M10 MMX2E Module IN conventional zone MMX2 CLIP MMX 1 Module IN CLIP MCX 55ME Module 5 IN 5 OUT not controlled MCX 55M Module 5 IN 5 OUT not controlled CLIP M721 Module 2 IN 1 OUT not controlled M720 Module 2 IN M710CZR Module di IN IS M710CZ Module IN conventional zone M710 Module IN M701 240 DIN Module OUT 240V M701 Module OUT MMX 10ME Module 10 IN MMX 10ME MMX 10M Module 10 IN MMX 10M CLIP FL20...
Страница 40: ... It is valid for the M710E CZ and M710E CZR module for the connection of conventional sensors It is automatically detected during the self programming NONA Input module Input module used to interface with N O contact with alarm when It is closed The activation of a NONA type module does not generate an Alarm condition that is the alarm LED is not on APND or GPND type modules do not activate Only o...
Страница 41: ...ed to perform remote SILENCING pulse MRES Input module used to perform remote RESET pulse OUTPUT MODULES CONNECTION TYPE SW Type_ID TYPE OF DEVICE FORC Relay output module with potential free contacts CON Output module with supervision of the line of command devices CONV Output module with supervision of the line of controlled devices VdS standard compliant GSND Software type dedicated to the foll...
Страница 42: ...sed output activated when a MAINS Fault is present REM FORC output module activated from a remote command supervisory SW GAS CON output module activated at each alarm It is reset by RESET GTS CON output module activated at each fault It is reset by RESET ZFLTC Output module activated in case of zone fault to here is associated MAINFC Same as MAINF but supervised output REMC CON output module activ...
Страница 43: ...ddress UDS2 UDS Local Disable Condition 6 Address UDS2 UDS Mains Loss 230Vac Removing UDS Units All By setting Type ID NONE on the first address the UDS is completely removed including optional UDS2 modules optionally installed This is also the only system to remove UDS1 Type IDs otherwise the UDS2 Type IDs can be removed individually UDS event fault message connected to AM 8200 UDS 3 with Exclude...
Страница 44: ...s Direct activation group It activates what is contained in its CBE equation It is activated by direct Inputs Groups which have the Group in their CBE equation Reverse activation group It is activated by its CBE equation It activates Reverse Output Groups which have the Group in their CBE equation NOTE One Reverse group can be the sum of several Direct groups This way an activation can be triggere...
Страница 45: ...defined as two groups to be chosen among the inverse ones available for which a CBE equation must be programmed by using the TIM operator to make them active only during a set time These groups are respectively defined as High Sensitivity Groups and Low Sensitivity Groups The purpose of this option is to make all installed sensors operate in control unit at high or low sensitivity when the relevan...
Страница 46: ...ity from 8 30 to 18 the sensitivity values assumed by the detector are those programmed in the Sens Low item in the option folder Night band high sensitivity from 18 to 8 30 the sensitivity values assumed by the detector are those programmed in the Sens High item in the option folder ZONE programming Menu By selecting the Zones sub menu you can enter a descriptive text to be associated with the se...
Страница 47: ... YES NO This feature enables viewing and managing pre alarm for sensors assigned to the zone Alarm Correlation Indicates the number of alarm devices assigned to the zone to activate the siren outputs associated with this zone Example Zone 1 Alarm Correlation 3 and in the Utilities Parameters Specials Sirens menus you have programmed the entry Active sirens on correlation SI you will have to activa...
Страница 48: ...r for CAN BUS line N B Up to 8 AM2 BST C cards can be installed on the CAN BUS network PRN Printer Interface Presence Programming This function allows you to configure the presence of the interface for connecting a serial printer to RS232 port To modify the programmings press the enter key use the arrow keys to change the parameter at the end press the enter key to confirm Press key CPU or CPU to ...
Страница 49: ... function allows you to configure the presence of the interface and the address of the SIB 8200 interface Press key LCD or LCD to program the previous next LCD terminal To modify the programmings press the enter key use the arrow keys to change the parameter at the end press the enter key to confirm This feature allows you to enter a programmable TEXT of max 32 characters which is displayed on the...
Страница 50: ... system state screen you can access the Utility menu which includes some functions generally used by servicing personnel To access the menu enter the Level 3 Password 33333 is the default password To enter the password consult the editing function previously mentioned in the paragraph description of the keyboard operation to enter data The following menu is displayed By pressing the Enter key all ...
Страница 51: ...ect between languages UTILITY Date and Time This function allows to program the time and date of the control unit D Da at te e To change values in Date and Time programming Form use the arrows to select the field to be changed the characters of the selected field are white on dark background Use the arrow keys to change the datum at the end press the enter key to store the datum H Ho ou ur rs s ...
Страница 52: ...rrow keys to change the functions at the end press the enter key to confirm Special Parameters This procedure is composed of 5 programming folders 1 1 P Pr ro og gr r o of f D DR RI IF FT T W WA AR RN NI IN NG G F FU UN NC CT TI IO ON N DRIFT WARNING By enabling this function the control unit generates a signalling when the sensor exceeds 70 of the alarm threshold for more than 5 minutes By select...
Страница 53: ...parameter through the arrow keys the characters of the selected field are in Reverse press the enter key and use the arrow keys to change the parameter at the end press the enter key to confirm the datum By increasing the values of each parameter the control unit becomes less sensitive for the Fault signaling for the Points installed on the lines By decreasing the values of each parameter the cont...
Страница 54: ... alarm from addressed devices Values allowed from 1 to 32 For details refer to the technical data sheets attached to the sirens Alarm volume In the case of alarm from addressed devices Values allowed from 1 to 4 For more details see the technical data sheets attached to the sirens Sound evacuation type Sound tone when activating the central control evacuation control Values allowed from 1 to 32 Se...
Страница 55: ... one or several parameters in this folder select the parameter through arrow keys the characters of the selected field are in Reverse press the enter key and use the arrow keys to change the parameter at the end press the enter key to confirm the datum History Log CLEAR By selecting the Clear function the following display appears Enter start date and time of the search and press the enter key to ...
Страница 56: ...not stored in the historical file In case of History Log was disabled a System Fault is signalled in the Faults List History Log Save This function will save the History Log file in an USB MEMORY STICK Press the enter key to perform the cancellation of all events stored in the historical event To change this parameter in this folder press the enter key and select through the arrow keys YES or NO N...
Страница 57: ...ones or software groups programmed can also be displayed D De et te ec ct to or rs s s st ta at tu us s The display shows by default the first device of the first line To select another device use the function keys D Di is sp pl la ay y o of f N NR RX X O OP PT T d de et te ec ct to or r D De et te ec ct to or r w wi ir re el le es ss s HW Type Name Programmable Text max 32 char Status Detector co...
Страница 58: ...spositivi FAAST SW Type programmed for output of the device Name Programmable Text max 32 char Status of the module Displays the Fan speed Displays the Air flow Displays the Smoke level Module Status depends on Module Type Input or Output Modify the Output Status of a Control Module After selecting the On Off field using the arrow keys user can switch the control module output pressing the OK Key ...
Страница 59: ...y example of NRXI GATE devices Gateway for wireless system G Gr ro ou up ps s S St ta at tu us s The display shows by default the first Group To select another Group use the function keys Z Zo on ne es s S St ta at tu us s The display shows by default the first Zone To select another Zone use the function keys ...
Страница 60: ...function you can examine the active module lists which are connected to the control unit lines Input modules Active input modules display In the case of a line where there are no alarm input modules the following indication is given No active input module In case of no active output modules in a line there will be the following indication shown in the figure below No Output Module Active ...
Страница 61: ...f f t th he e D DI IS SP PL LA AY Y f fi ir rm mw wa ar re e f fr ro om m a an n U US SB B k ke ey y i in ns se er rt te ed d i in n t th he e L LC CD D c co on nn ne ec ct to or r T Th hi is s f fu un nc ct ti io on n h ha av ve e t to o b be e a au ut th ho or ri iz ze ed d f fr ro om m N No ot ti if fi ie er r I It ta al li ia a T Te ec ch hn ni ic ca al l s se er rv vi ic ce e D DI IS SA AB BL...
Страница 62: ... the following display will appear where it is possible to change the state of Enabled Disabled for the various devices Modify Status Detectors The display shows by default the first device of the first line To select another device use the function keys Modify Status Modules The display shows by default the first device of the first line To select another device use the function keys When a detec...
Страница 63: ...ammed with SW Type SW SND terminals CNU 17 and CNU18 of the main board To change this parameter in this folder press the enter key and select through the arrow keys YES or NO and press the enter key to confirm the datum Immediate activation Siren outputs When the exclusion is activated for the immediate activation of the siren outputs Active Exclusion and Delay LEDs are turned on In the event of a...
Страница 64: ...U By pressing the function key TEST in System State you can access the Test menu which includes the functions generally used by the servicing personnel to test the system To access the menu enter the Level 2 Password 22222 is the default password To enter the password consult the editing function previously mentioned in the paragraph description of the keyboard operation to enter data The followin...
Страница 65: ...the enter key and use the arrow keys to change the parameter at the end press the enter key to confirm the datum LED TEST By selecting through the arrow keys the Led item and by pressing the enter key to confirm the control unit performs the lamp test function all the control unit leds flash for some seconds LCD TEST By selecting through the arrow keys the LCD item and by pressing the enter key to...
Страница 66: ...using some logical operators OR AND XGRP NOT DEL SDEL and TIM The ACTIVE condition is valid when Input point input modules or sensors in Alarm Output point output Module ACTIVATED Group one of the points of the group is Active RULES FOR THE CORRECT SYNTAX OF THE EQUATIONS To be valid and accepted by the control unit the control equation must follow some precise syntax rules If a syntax errors occu...
Страница 67: ...on C1L1S2 and C1L1S3 will be ALSO activated Additionally as usual also Direct Groups can take place inside a Direct formula of input Points sensors and input modules Reverse Groups can take place inside operands on reverse formulas for points LED output on sensors and Output modules CBE Null equation You can also not program any equation for a device In this case If the device in question is an in...
Страница 68: ...odule equation is AND G9 G15 G23 Only if ALL THREE operands in this equation are in alarm the output module will be activated that is IF the software group 9 is in alarm or IF the software group 15 is in alarm or IF the software group 23 is in alarm THEN this output module will be activated NOT is the operator which DENIES the operand or the series of operands in brackets which follow it Example t...
Страница 69: ...e the equation of an output module is XGRP G23 IF ANY COMBINATION of two or several input devices sensors or modules which have been programmed with their CBE Equation on this software group through the Double Consent parameter YES they are ACTIVE THEN this output module will be activated Or only when a thermal sensor type id THER and an optical sensor type id PHOT which have been programmed throu...
Страница 70: ...CBE is associated is activated Example2 The equation of an output module is OR FLT Z1 FLT Z2 If any of the two Zones Z1 or Z2 is faulty the output module to which the CBE is associated is activated DIS It is the operator that allows the disarming of zones and points by activating a programmed input module programmed with Type SW NONA does not generate an alarm in the central unit Example1 The equa...
Страница 71: ...time its equation is not true any longer the timer resets and is ready to start at the next event therefore the output device does not activate FORMAT OF MM SS delay MM SS duration optional CONDITION equation which sets the delay start Where MM minutes 2 digits SS seconds 2 digits CONDITION it can be an equation of the type XGRP GXXX NOT Element 1 OR Element 1 Element 2 AND Element 1 Element 2 Ele...
Страница 72: ...M 00 MM Where 00 hours MM minutes This format allows to perform programmings weekly for specific days of the week FORMAT Type 2 TIM MM GG AA OO MM OO MM Where MM month GG day AA year This format allows to perform programmings yearly Example IF the G90 software group equation is TIM SA SU 07 30 13 59 THEN the G90 group will be active on Saturday and Sunday from 07 30 a m to 13 59 N B If the day mon...
Страница 73: ... G1 Module equation L1S1 Module equation GENERAL ALARM The following example shows a method of control unit programming for the general alarm The L1M2 output module is associated with the group G1 and will be activated in case of alarm on the L1S1 and L1S2 detectors The L1M3 output module is associated with the group G2 and will be activated in case of alarm on the L1S3 detectors or on the L1M1 in...
Страница 74: ...ach fault N GTS Output Module CON activated at each fault N GTSV Same as GTS but with controlled VDS output N TRS Output Module FORC activated at each fault N ZDIS Output Module activated in case of exclusion of point or zone N MAINF Output Module not supervised activated for Power Failure N MAINFC Come MANIF supervised N MAINFV Come MANIF ma con uscita supervisionata EOL RES complies VdS N REM Ou...
Страница 75: ... free contacts Y PWRC Output Module FORC interrupts momentarily the power supply N GPND Output Module FORC activated at every alarm fault N APND Output Module FORC activated at every alarm N GAC Output Module FORC activated at every alarm N GAS Output Module CON activated at every alarm N TPND Output Module FORC activated at every fault N GTC Output Module FORC activated at every fault N GTS Outpu...
Страница 76: ...E 4 Sounder Strobe Advanced CBE Y N GSND Addressable Sounder that can be Silenced Y SND Addressable Sounder that follows the status of the panel Sounder N GSTR Addressable Strobe that can be Silenced Y STR Addressable Sounder that follows the status of the panel Sounder N GPND Sounder or strobe activated at each unrecognized alarm fault silenciable N APND Sounder or strobe activated at each unreco...
Страница 77: ... Tel Fax 055 289177 00040 Roma Morena Via Del Casale Santarelli 51 Tel 06 7988021 Fax 06 79880250 E mail notifier roma notifier it 80143 Napoli Palazzo Prof Studi Centre Direzionale Isola G1 Scala D Piano 15 Tel 081 7879398 Fax 081 7879159 E mail notifier napoli notifier it 70125 Bari Via Della Costituente 29 Tel 080 5013247 Fax 080 5648114 E mail notifier bari notifier it 95126 Catania Via del Ro...