Honeywell NK298S Скачать руководство пользователя страница 10

Honeywell GmbH

10

MU1H-1229GE23 R0905

GB

9. Disposal

The refilling combination consists of:
• Red-bronze
• Brass
• Steel
• Plastic

Observe the local requirements regarding cor-
rect waste recycling/disposal!

10. Troubleshooting
Disturbance

Cause

Remedy

No or too little water flow rate

Refilling combination is not fitted in 
flow direction

Fit refilling combination in flow direc-
tion (note direction of arrow on hous-
ing)

min. inlet pressure is not reached

Call Technical Customer Service on 
(49) 6261 810

Ball valves up- or downstream of 
refilling combination are not fully 
open

Open ball valves fully

Pressure reducing valve is not set to 
the desired outlet pressure

Set outlet pressure (

 chapter 7.2.1)

Filter insert pressure reducing valve 
is contaminated

Clean or replace filter insert 
(

 chapter 8.3.2)

integrated strainer is contaminated Clean filter strainer (

 chapter 8.3.1) 

or replace cartridge insert 
(

 chapter 8.2.1)

Discharge valve opens without rea-
son

Non return valve upstream or dis-
charge valve are contaminated

Clean cartridge insert 
(

 chapter 8.3.1) or replace 

(

 chapter 8.2.1)

Non return valve upstream are faulty Replace cartridge insert 

(

 chapter 8.2.1)

Discharge valve does not close

Discharge valve is contaminated or 
faulty

Clean cartridge insert (

 chapter 

8.3.1) or replace (

 chapter 8.2.1)

Water is escaping from spring hood Diaphragm in valve insert is faulty

Replace valve insert 
(

☞ 

chapter 8.2.2)

The outlet pressure set does not 
remain constant

Filter insert pressure reducing valve 
is contaminated or worn

Clean or replace filter insert 
(

 chapter 8.3.2)

Valve insert, sealing ring or edge of 
nozzle is contaminated or worn - 
unwanted rise above set pressure

Replace valve insert 
(

☞ 

chapter 8.2.2)

OBJ_BUCH-20-001.book  Seite 10  Donnerstag, 15. September 2005  12:53 12

Содержание NK298S

Страница 1: ...EB NK298S Rev C NK298S Einbauanleitung Installation instructions T D V G N Nachfüllkombination Refilling Combination OBJ_BUCH 20 001 book Seite 1 Donnerstag 15 September 2005 12 53 12 ...

Страница 2: ...et Der Druckminderer setzt den eingangsseitigen Druck Vordruck auf den gewünschten Druck auf der Aus gangsseite Hinterdruck herab Der Druckminderer arbeitet nach dem Kraftvergleichs prinzip Der Membrankraft wirkt die Federkraft des Re gelventils entgegen Sinkt infolge einer Wasserentnahme der Ausgangsdruck Hinterdruck und damit die Membrankraft so öffnet die nun größere Federkraft das Ventil Der A...

Страница 3: ...ten z B durch Was serzapfen 4 Absperrkugelhahn ausgangsseitig schließen 5 Absperrkugelhahn eingangsseitig langsam öffnen 6 Hinterdruck einstellen Schlitzschraube drehen bis Manometer ge wünschten Wert anzeigt 7 Absperrkugelhahn ausgangsseitig langsam öffnen 8 Nachfüllkombination ist betriebsbereit 8 Instandhaltung Entsprechend DIN EN 1717 muss eine regelmäßige Wartung durchgeführt werden 8 1 Inspe...

Страница 4: ...itel 7 2 1 8 3 Reinigung 8 3 1 Systemtrenner Abb 6 Bei Bedarf können der Kartuscheneinsatz und der Schmutzfänger gereinigt werden 1 Absperrkugelhähne ein und ausgangsseitig schließen 2 Verschlusskappen entfernen Kugelhähne öffnen und schließen Systemtrenner wird druckentlastet 3 Abdeckung Kartuscheneinsatz abschrauben 4 Kartuscheneinsatz herausnehmen 5 Sieb Schmutzfänger von Kartuscheneinsatz entf...

Страница 5: ...instellen Kapitel 7 2 1 Siebeinsatz Druckminderer ver schmutzt Siebeinsatz reinigen oder ersetzen Kapitel 8 3 2 integrierter Schmutzfänger ver schmutzt Sieb Schmutzfänger reinigen Kapitel 8 3 1 oder ggf Kartu scheneinsatz ersetzen Kapitel 8 2 1 Ablassventil öffnet ohne Grund Eingangsseitiger Rückflussverhinde rer oder Ablassventil verschmutzt Kartuscheneinsatz reinigen Kapitel 8 3 1 oder ggf erset...

Страница 6: ... 2A i O Ringsatz 10 Stück 0901246 j Siebtasse mit O Ring SK06T 1 2 k Absperrkugelhahn 1 2 2192900 l Manometer 0 4 bar M07M A4 12 Zubehör TK295 Prüfset elektronisches Druckmessgerät mit Digital anzeige Batterie betrieben Mit Koffer und Zubehör ideal zur Inspektion und Wartung der Systemtrenner BA TKA295 Prüfset analoges Druckmessgerät mit Differenz druckanzeige Mit Koffer und Zubehör ideal zur Insp...

Страница 7: ...ion pressure to the level of the desired pressure on the outlet side outlet pressure in individual cases The pressure reducing valve functions on a force equalisation principle The force of a diaphragm oper ates against the spring force of the regulating valve If the outlet pressure and therefore diaphragm force fall because water is drawn then the greater force of the spring causes the valve to o...

Страница 8: ...Close ball valve on inlet 2 Slacken tension in compression spring Turn slotted screw to the left 3 Release pressure on outlet side e g through water tap 4 Close ball valve on outlet 5 Slowly open ball valve on inlet 6 Setting outlet pressure Turn slotten screw until the manometer shows the desired value 7 Slowly open ball valve on outlet 8 Refilling combination is ready for use 8 Maintenance In ac...

Страница 9: ...can be cleaned when nec essary 1 Close ball valve on inlet and outlet 2 Remove closing caps Open and close ball valves Backflow preventer is decompressed 3 Unscrew cover cartridge insert 4 Take out cartridge insert 5 Remove filter strainer from cartridge insert 6 Clean cartridge insert and filter strainer 7 Reassemble in reverse order 8 Check function chapter 8 1 1 8 3 2 Pressure reducing valve fi...

Страница 10: ...t chapter 8 3 2 integrated strainer is contaminated Clean filter strainer chapter 8 3 1 or replace cartridge insert chapter 8 2 1 Discharge valve opens without rea son Non return valve upstream or dis charge valve are contaminated Clean cartridge insert chapter 8 3 1 or replace chapter 8 2 1 Non return valve upstream are faulty Replace cartridge insert chapter 8 2 1 Discharge valve does not close ...

Страница 11: ...ces 0901246 j Filter bowl with O ring SK06T 1 2 k Ball valve 1 2 2192900 l Manometer 0 4 bar M07M A4 12 Accessories TK295 Test kit Electronic pressure measuring device with digital indicator runs by a battery With case and accessories ideal for inspection and maintenance of backflow preventer type BA TKA295 Test kit Analogue pressure measuring device with differential pressure display With case an...

Страница 12: ...ywell com Manufactured for and on behalf of the Environment and Combustion Controls Division of Honeywell Technologies Sàrl Ecublens Route du Bois 37 Switzerland by its Authorised Representative Ho neywell GmbH MU1H 1229GE23 R0905 Subject to change without notice 2005 Honeywell GmbH OBJ_BUCH 20 001 book Seite 12 Donnerstag 15 September 2005 12 53 12 ...

Страница 13: ...sorgung 5 10 Störung Fehlersuche 5 11 Ersatzteile 6 12 Zubehör 6 1 Safety guidelines 7 2 Functional description 7 2 1 Generally 7 2 2 Construction type 7 3 Application 7 4 Technical data 7 5 Scope of delivery 7 6 Assembly 8 6 1 Installation 8 6 2 Assembly instructions fig 1 8 7 Commissioning 8 7 1 Backflow preventer fig 2 8 7 2 Pressure reducing valve fig 2 8 8 Maintenance 8 8 1 Inspection 8 8 2 M...

Страница 14: ...E23 R0905 1 0 2 4 3 bar 500 100 T D V G N 1 1 1 2 2 2 T D V G N 2 T D V G N 6 2 2 2 3 4 5 6 2 2 2 3 4 7 6 2 5 3 4 bar 6 8 10 4 2 0 5 6 4 1 2 6 3 4 5 7 2 2 2 5 OBJ_BUCH 20 001 book Seite 14 Donnerstag 15 September 2005 12 53 12 ...

Отзывы: