NetAXS™ Standalone Operation
Standalone Commands
NetAXS™ NX4L1 Access Control Unit Installation Guide
,
Document 7-901099V3
71
3.3 L (Time Zone) Command
_
L=pn_tz_h1:m1-h2:m2_days<CR>
Variables:
pn = panel number (1–31)
tz = time zone number (1–255)
h1 = start time zone: hours (00–23) (Military time)
m1 = start time zone: minutes (00–59)
h2 = end time zone: hours (00–23) (Military time)
m2 = end time zone: minutes (00–59)
days = days of week valid values as listed below:
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
0 = Holiday 1
8 = Holiday 2
9 = Holiday 3
Note:
00:00 is the earliest time possible and 23:59 is the latest time possible. A single
time zone cannot be made to span midnight, through the use of extended commands
we can simulate this. For more information, please seek the guidance of technical
support.
Example 1
_L=5_10_08:00-17:00_1_2_3_4_5<CR>
This command would configure panel 5 to add a time zone entry to time zone number
10 ranging from 8AM to 5PM and would be valid during Monday, Tuesday,
Wednesday, Thursday, and Friday.
Example 2
_L=25_45_16:00-23:59_0_6_7_8_9<CR>
This command would configure panel 25 to add a time zone entry to time zone
number 45 ranging from 4PM to 11:59PM and would be valid during Saturday,
Sunday, Holiday, 1, 2, and 3.