background image

MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES

5

62-3048—2

Table 3.  Valve Dimensions.

a

B Max dimension is with T100A control installed, except for 

the V2042H, for which it is without the steam/air vent 

installed.

Connections:

Inlets Available:

Internally threaded.

Sweat (1/2 in. and 3/4 in. only).

Outlets Available:

Union nut with threaded tailpiece.

Sweat (1/2 in. and 3/4 in. only).

Union nut with sweat tailpiece (1/2 in. and 3/4 in. only).

Capacity:

Cv (gpm at 1 psi drop across fully-open valve):

1/2 in.: 2.0.

3/4 in.: 2.2.

 1 in.: 2.3.

Btuh (Btu/hr at 7 psi drop across fully-open valve):

1/2 in.: 59,100.

3/4 in.: 63,800.

1 in.: 70,500.

Accessories:

203225 Replacement Bulb Guard for T100F.

272844 Locking Cap and Limit Pins for T100M.

272873 MT100C Cartridge Tool Driver Upgrade Kit.

A104F Limit Pins for T100A,F.

VS1200SL01 Replacement Valve Cartridge.

G111B Bulb Guard to protect T100C sensor when 

wall-mounted.

VA8200A001 Valve Cartridge Replacement Tool for system 

under pressure (V2000).

Q110D Inlet Strainer Inserts for NPT V100 (models available 

for 1/2 in. and 3/4 in. valves).

SA123A Steam/Air Vent for V2042HSL10 One-pipe Steam 

Valve.

Fig. 3. V2042H (Body)/V2043H (Body with Airstream Vent) 

Dimensions.

NOTE: Refer to Table 3 for detailed valve dimensions for 

each valve size.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Equipment Damage Hazard.

Excessive force can distort and damage valve.

Do not overtighten the union nut.

CAUTION

Equipment Damage Hazard.

Driving an unmounted MV100 can damage the 

actuator beyond repair.

Mount the MV100 before applying power to the 

actuator.

CAUTION

Sweat Valve Damage Hazard.

Soldering the valve with the cartridge or controller 

attached can damage the device.

Prior to attaching valve to piping, remove controller and 

cartridge from potential exposure to heat.

IMPORTANT

When installing the valve body, ensure that the arrow 

(cast into the body) points in the direction of the flow.

Valve

Size in 

in.

A

 in in. (mm)

B Max

a

 in in. (mm)

in in. (mm)

V2040D 1/2

3-3/4 (95)

4-1/16 (104) —

3/4

4-3/16 (106) 4-1/16 (104) —

1 4-1/2 

(114)

4-1/2 

(114)

V2040E 1/2

2-5/16 (58)

3-3/16 (98)

1 (26)

3/4

2-5/8 (66)

3-13/16 (98) 1-1/8 (29)

1

2-15/16 (74) 4-5/16 (110) 1-5/16 (34)

V2040A 1/2

2-1/8 (54)

4-1/2 (115)

1-1/8 (28)

3/4

2-1/2 (64)

5-3/16 (132) 1-3/16 (31)

1

2-15/16 (74) 5-3/16 (132) 1-7/16 (37)

V200LD 1/2

2-5/8 (66)

4-1/16 (104) —

3/4

2-15/16 (74) 4-1/16 (104) —

V2042H 3/8

1-11/16 (43) 3-13/16 (98) 1-3/16 (31)

M17016

5

6

0

B MAX.

A

C

Содержание MV100

Страница 1: ...ns T100A F M models have range limiting features to limit adjustment or lock at a fixed setting can require limit pin accessory EPDM valve seat disk assures tight shutoff on steam and hot water systems Nickel plated bronze cast valve body Cartridge containing all working parts inserts into valve body for ease of service Cartridges are replaceable while valves remain in service and under pressurE W...

Страница 2: ...Hz or 24 Vdc Power Consumption 0 125A 3W End Switch Low voltage 24 Vac 5A two position spst normally open switch closes when controller powered Configuration with Controller Mounted Normally closed valve remains closed without power NOTE Normally open model available in Canada Opening Time at 78 F Maximum 5 minutes from cold to fully open Ambient Temperature Rating Maximum 122 F 50 C T100 T200 The...

Страница 3: ...3 5 16 84 MAX 2 50 2 1 8 54 1 25 M12925A TOP T100A 3 77 2 50 M12929 TOP T100M CAPILLARY TUBE LENGTH 4 1 2 FT 1 4 m M12927 CAPILLARY TUBE LENGTH 4 1 2 FT 1 4 m 2 31 32 75 2 5 32 55 2 1 8 54 1 13 16 46 T100C CAPILLARY TUBE LENGTH 6 1 2 FT 2m OR 16 FT 5m M12926 2 5 32 55 2 1 8 54 2 31 32 75 1 13 16 46 T100B 3 76 MAX 1 9 16 40 13 16 20 M12945 TOP T200A H B r a u k m a n n x x x x x x x x x x x x x 2 7...

Страница 4: ... 26 C Direct with remote sensor One 6 1 2 ft 2 m Sensor is remote from combination setpoint dial and valve actuator T100M Directa None Components are in one tamper resistant unit T200A Directa None White body with chrome plated end Model Body Pattern Connection Application Inlet Outlet V2040D Straight NPT Threaded Union Nut with NPT Threaded or Sweat Use where manual valves were not originally ins...

Страница 5: ...n Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in...

Страница 6: ...to correct value One complete revolution of the black pre setting ring equals a pre setting of 10 Fig 7 Fig 7 One complete revolution equals a pre setting of 10 Table 4 CV Values NOTE Pressure drop psi flow gpm cv 2 Product Selection 1 Select the installation diagram from Fig 4 through 16 that most accurately represents your equipment and pip ing configuration 2 Use Table 4 to select the combinati...

Страница 7: ...g 12 Fig 13 Application Figure No Controller Valve 8 T100A T100M T200 MV100 V2040D 9 T100A T100M T200 MV100 V2040A 10 T100A T100M T200 MV100 V2040E 11 T100A T100M T200 MV100 V2042H 12 T100M MV100 V2040A 13 T100F MV100 V2040E 14 T100F MV100 V200LD 15 T100F MV100 V2040D 16 T100F MV100 V2042H 17 T100B MV100 V2040D 18 T100B MV100 V2040E 19 T100C MV100 V2040D 20 T100C MV100 V200LD M4631 M4632 M12934 0 ...

Страница 8: ...flow obstructions such as curtains or enclosures Two essential considerations for choosing the correct controller valve body combination for a particular installation are Adequate dimensional clearances Proper sensor positioning IMPORTANT Install built in sensor type controllers in a horizontal position to prevent air warmed by the hot valve body from influencing the sensor NOTE The most common mi...

Страница 9: ...e capsule contracts the valve opens and flow resumes through the radiation unit T100 The T100 temperature sensitive capsule expands when the temperature rises above the setpoint MV100 When signalled by the thermostat an electric element in the MV100 heats the capsule causing it to expand NOTE For normally open MV100 models the capsule cools when signalled by the thermostat SETTINGS AND ADJUSTMENTS...

Страница 10: ...r initial cost resulting from the use of less piping and elimination of radiator steam traps CAUTION Boiler Flooding Hazard Loss of system control and boiler damage can result For a one pipe steam system radiator install valve only at the vent location IMPORTANT Ensure vacuum breakers are installed on the steam system risers If vacuum breakers that open to the atmosphere at zero psig are not insta...

Страница 11: ...rn a boiler on and off check the manufacturer recommendations b In installations where turning the boiler off at the end of each cycle is undesirable install a control valve such as a Honeywell V5011 Valve on the boiler dis charge line NOTE Install the valve on the boiler side of the condensation takeoff to ensure that the condensation can return to the boiler 3 Verify that the steam pressure has ...

Страница 12: ...tion Change sensor location or change control type Control not properly installed Check for bosses and grooves reset actuator on valve and tighten knurled ring to valve body Capillary tube broken kinked or bent sharply Replace control Dirt or scale under the seat prevents tight shutoff Remove the control from the valve body allowing valve to open fully and flush away scale and debris Reinstall con...

Страница 13: ... 3 Pull handle out to clear VA8200A ball valve A close ball valve B and open drain cock to remove excess water and steam from chamber C See Fig 22 4 Unscrew end cap A and remove cartridge from chamber B See Fig 23 5 Clean or replace cartridge Fig 24 Loosening valve cartridge Fig 25 Attaching VA8200A001 to valve Fig 26 Disconnecting valve cartridge and draining chamber Fig 27 Removing valve cartrid...

Страница 14: ...62 3048 2 14 ...

Страница 15: ...15 62 3048 2 ...

Страница 16: ...ernational Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2006 Honeywell International Inc 62 3048 2 G R Rev 02 06 ...

Отзывы: