SERIES 90 MODUTROL IV
™
MOTORS
9
63-2631—07
The motors in the application need to be all symmetrical or all
asymmetrical. The M62 motor needs to be a "-S" slaving
model, as listed in Table 8. In order to get the correct response
the Series 62 needs the appropriate shunt resistor from Table
8. The motors' potentiometer settings are given in the
configuration table (Table 9) below. When slaving more than
one Series 90 motor use the appropriate resistor table as
indicated by the configuration table and install two resistors to
ONE of the motors (Tables 10 and 11). If the motor is the M62
master connect one resistor from terminals T to G and one
from T to Y. If the motor is one of the M90 slaves connect one
resistor from terminals R to B and one from R to W.
NOTE: More than 6 slaves is not recommended.
Table 8. Series 60 and Series 90 in Slaving Application
Table 9. Configuration Table
Table 10. Resistor Table 1
Table 11. Resistor Table 2
OS Number
Feedback
Resistance
Sensitivity
Adjustment
Internal
Shunted
Linear
Feedback
Series 90 Slaving
Shunt Resistor
M6284D1000-S, M6284D1026-S, M6284D4004-S,
M6285A1005-S, M6285A1054-S, M6285A4009-S
600 Ohms
No
Yes
No
187 Ohm
M6274F1009-F, M6284F1070-F, M6284F1078-F,
M6285F1001-F, M6294F1009-F, M6294F1017-F,
M6284D1032-F
10 K Ohms
No
No
Yes
Not Available
M6284A1071-S, M6284A1089-S, M6284C1028-S 196/346 Ohms
Yes
Yes
No
274 Ohm
M6284A1030-S, M6284A1055-S, M6284A1097-S,
M6284B1004-S, M6284C1010-S, M6284C1044-S,
M6284F1013-S, M6284F1039-S, M6285A1039-S,
M6285A1047-S, M6285C1001-S, M6294B1036-S,
M6294D1008-S
119/224 Ohms
Yes
Yes
No
Not Necessary
M6284F1062-S
1800 Ohms
No
Yes
No
Not Available
“-S” Slaving Series 90 Mod IV Motor
“-F” 0-10K Feedback
Symmetrical or
Asymmetrical
Master
Stroke
Slave
Stroke
Master
Stroke Pot
Master
Sensitivity Pot
Slave
Stroke Pot
Slave
Sensitivity Pot
Resistor
Table
Symmetrical
160
160
CW
CW
CW
CW
1
Symmetrical
90
90
CCW
CCW
CCW
CCW
2
Symmetrical
160
90
CCW
CW
CCW
CCW
1
Symmetrical
90
160
Configuration not recommended
Asymmetrical
160
160
CW
CW
CW
CW
1
Asymmetrical
90
90
CCW
CW
CW
CW
1
Asymmetrical
160
90
Configuration not recommended
Asymmetrical
90
160
Configuration not recommended
Number of Motors in Parallel
Resistor Value
1
NONE
2
3500 Ohms
3
2000 Ohms
4
1300 Ohms
5
1000 Ohms
6
800 Ohms
Number of Motors in Parallel
Resistor Value
1
NONE
2
5000 Ohms
3
2400 Ohms
4
1700 Ohms
5
1400 Ohms
6
1200 Ohms